New Product Bulletin
/font>.
Yahoo! is not affiliated with the authors of this page or responsible for its content.
New Product Bulletin
Belden
®
2-hour Rated Safe-T-Line
CI and CIC cables ensure the
continued operation of a buildings
EVAC systems in the event of fire.
ABS-approved CI cables are
suitable for shipboard application
and PLTC-CI cables handle
controlled shutdown situations in
industrial environments.
Belden Offers a Full Line
of Fire-resistive, 2-hour
Rated New Generation
®
Circuit Integrity (CI)
and Circuit Integrity in
Conduit (CIC) Cables
Belden now offers a full line of high quality, high
reliability 2-hour rated CI and CIC cables, including:
Safe-T-Line CI cables that meet the Fire Alarm
Cable System Survivability requirements of
NFPA 70 and NFPA 72/2002 - non-conduit only
Safe-T-Line CIC (CI cables in conduit) that meet NEC
Fire Alarm Survivability requirements in 1/2" conduits
PLTC-CI cables for controlled emergency
shutdowns of industrial processes
ABS-type Approved Low Smoke Zero Halogen
(LSZH) CI cables for shipboard use
Survivable System Choices
When life-saving Emergency Voice-Alarm
Communications (EVAC) systems are installed, there
are three means by which to meet the 2-hour circuit
integrity code requirements:
Structural/architectural 2-hour chase that is not
a means of exit a very expensive and often
unsightly or impossible choice if the building is
being rehabilitated
Mineral Insulated (MI) cables a very expensive
cable type that is also laborious to install
Belden Safe-T-Line continuous length, flexible-
extrusion, fire-resistive circuit integrity cables, or
similar make the most economical choice and
the easiest installation option
EVAC System Solutions
To be effective, EVAC systems must remain
operational for two hours. To meet this 2-hour
operational need Belden offers:
Safe-T-Line Circuit Integrity Riser-rated cables
(codes with UM and FM suffixes); these cables
are FPLR-CI rated and UL Listed for circuit
integrity when installed exclusive of conduit.
Their installation should include fire stop materials,
cable runs without splices through the fire zone
and terminations no less than 12 inches beyond
the fire-rated wall or floor bounding the fire zone.
Safe-T-Line Circuit Integrity in Conduit (CIC)
Riser-rated cables (codes with UZ and FZ suffixes);
these cables are FPLR rated, and UL Listed for
circuit integrity when installed in conduit
according to FHIT #30 (UL).
Easier to Terminate and Install
To meet the needs of installers, Belden Fire Resistive
Safe-T-Line cables are manufactured with a user-
friendly, aluminum-polyester Beldfoil® shielding
tape, instead of the copper tapes used by other
manufacturers. This makes Belden's CI cable the
most easily terminated cable of its kind.
Shipboard 2-hour Rated CI Cables
Belden also offers ABS-type approved products
(Part Nos. 1320SB and 1321SB) with type approved
Low Smoke, Zero Halogen properties for use in
demanding marine applications.
ABS (the American Bureau of Shipping) is the leading
international classification society devoted to
promoting the security of marine-related life and
property. With ABS-type approval, no additional
special approvals or insurance company exceptions
are required for Belden cable system installations.
Industrial 2-hour Rated CI Cables
Belden Type PLTC-CI shielded multi-conductor cables
are for industrial use, to be employed in controlled
shutdown or emergency situations in circuitry that
pertains to mission-critical industrial processes.
Belden Part Nos. 5240FR and 5201FR are for
installation in risers or Power Limited Trays, but
cannot be used in conduit if UL listing must be
retained. These cables are UL2196/NEC listed to
suit the requirements of particularly hazardous
environments such as petrochemical facilities.
New Product Bulletin
NP 249
2-hour Fire Rated Cables
In conduit,
1
/
2
EMT Minimum
1
NFPA 101 Life Safety Code
NFPA 72/2002
Safe-T-Line CIC
2
Types (UZ and
FZ part numbers suffix)
UL Electrical Circuit Protective Systems
System No. 30 ( FHIT.30) and NFPA
70 (NEC)
R22303 (UL) and FPLR, 105ºC. Not 2-hour rated by itself in
standard risers unless in conduit and installed according to
UL FHIT.30
Not in conduit,
Not in plenum,
May be in standard riser
NFPA 101 Life Safety Code
NFPA 72/2002
Safe-T-Line CI Types (UM and
FM part numbers suffix)
NFPA 70 (NEC) standard building practices
Circuit Protective Systems (UL, NEC)
41 V devices
FPLR-CI. 105ºC. Not listed by UL for 2-hours when installed
in conduit. Not for use in plenum spaces. 2-hour rated in
standard risers, non conduit routings; 41 V devices
NFPA 70 Article 725;
PLTC-CI, ITC, UL 2196
Not in conduit
NFPA 70/2005 Article 725.61(H)
and 725.82(F)
NFPA 101 as applicable
Safe-T-Line PLTC-CI Cable (FR
part number suffix) - or special
production of other types
Per plant engineering or per NFPA 70
(NEC) standard building practices and
NFPA 101 Life Safety Code as applicable.
UL 2196, FPLR-CI, 105ºC, PLTC, ITC, Sunlight Resistant.
NEC 760, UL 1666, IEC 603331. Not listed by UL for 2
hours when installed in conduit
Where ABS Type Approval
is preferred. Aboard ship.
Shipboard safety, LSZH, ABS Type
Approval. Ship designers and archi-
tects, licensed PE
1320SB
1321SB
Per Ship Designers or NFPA 70 (NEC)
standard building practices and NFPA 101
Life Safety Code, as applicable
ABS Type Approved, CMG-LS, FPRL-CI, NEC 760, IEEE Std. 45,
clause 23, IEC 60092-376 clause 17, 60092-351, 60754-1,
60754-2, 61034, UL1685 FT4 loading, limited smoke
2
Safe-T-Line
®
Cable
Circuit Integrity in Conduit (CIC) Fire Alarm
Flame Retardant, Low Smoke Zero Halogen Jacket, Riser-Rated; R22303; FPLR
Unshielded Multi-conductor
Thermoset Elastomer Insulation Red Polyolefin Jacket
18 AWG
NEC: FPLR
5320UZ
2
solid
1000
304.8
57
25.90
.041
1.0
.36
9.14
15
49
5.9
16 AWG
5220UZ
2
solid
1000
304.8
57
25.85
.035
.89
.35
8.89
15
49
4.1
5200UZ
2
7 x 24
1000
304.8
61
27.67
.035
.89
.37
9.40
16
52
4.1
14 AWG
5120UZ
2
solid
1000
304.8
71
32.21
.035
.89
.38
9.65
17
56
2.5
5100UZ
2
7 x 22
1000
304.8
78
35.38
.035
.89
.40
10.16
18
59
2.5
12 AWG
5020UZ
2
solid
1000
304.8
93
42.18
.035
.89
.42
10.67
19
62
1.6
5000UZ
2
7 x 20
1000
304.8
99
44.91
.035
.89
.44
11.18
19
62
1.6
Shielded Multi-conductor Thermoset Elastomer Insulation Beldfoil
®
Shield Red Polyolefin Jacket
18 AWG
NEC: FPLR
5320FZ
2
solid
1000
304.8
59
26.80
.041
1.0
.36
9.22
20
66
5.9
16 AWG
5220FZ
2
solid
1000
304.8
63
28.58
.035
.89
.36
9.14
20
66
4.1
5222FZ
4
solid
1000
304.8
102
46.27
.035
.89
.41
10.41
16
52
4.1
5200FZ
2
7 x 24
1000
304.8
67
30.39
.035
.89
.37
9.40
22
72
4.1
14 AWG
5120FZ
2
solid
1000
304.8
81
36.74
.035
.89
.38
9.65
23
75
2.5
5122FZ
4
solid
1000
304.8
133
60.33
.035
.89
.44
11.18
18
59
2.5
5100FZ
2
7 x 22
1000
304.8
88
39.92
.035
.89
.41
10.41
26
85
2.5
12 AWG
5020FZ
2
solid
1000
304.8
108
48.99
.035
.89
.42
10.67
27
89
1.6
5022FZ
4
solid
1000
304.8
180
81.65
.035
.89
.48
12.19
20
66
1.6
5000FZ
2
7 x 20
1000
304.8
114
51.71
.035
.89
.44
11.18
27
89
1.6
Notes: All 2-conductor versions are color-coded black and red; 4 or more conductor versions are all black and numbered.
Available through 8 conductor by special order. Contact Belden distribution.
Description
Stranding
No. of
Cond.
m
Ft.
Standard
Lengths
mm
Inch
kg
Standard
Unit Weight
Insulation
Thickness
Nominal OD
Inch
mm
Lbs.
Part
No.
Nominal
Capacitance
Nominal DC
Resistance
/Mft.
pF/m
pF/Ft.
UL R22303
UL-Standard 2196
in Conduit
UL R22303
UL-Standard 2196
in Conduit
Cable Installation
Code Compliance Requirements
Cable Solution
Installation Guidelines
Cable Rating,listings, and
Special Considerations
1
In UL Listed Flexible Metallic Conduit not exceeding 6 feet in length also permitted per FHIT No. 30 (all other conditions thereof still apply).
2
Continuous lengths of cable and coupled conduit passing completely through a fire zone and terminating a minimum of 12 inches beyond the fire rated wall or floor bounding the fire zone (FHIT.30).
3
Safe-T-Line
®
Cable
Circuit Integrity (CI) Fire Alarm
Flame Retardant, Low Smoke, Zero Halogen Jacket, Riser-Rated; FPLR-CI
Unshielded Multi-conductor
Thermoset Elastomer Insulation Red Polyolefin Jacket
18 AWG
NEC: FPLR-CI
5320UM
2
solid
1000
304.8
40
18.14
.034
.86
.31
7.87
17
56
5.9
UL Standard 2196
5322UM
4
solid
1000
304.8
65
29.48
.034
.86
.35
8.89
17
56
5.9
X-conduit
5324UM
6
solid
1000
304.8
95
43.09
.034
.86
.42
10.67
17
56
5.9
5326UM
8
solid
1000
304.8
120
54.43
.034
.86
.45
11.43
17
56
5.9
16 AWG
5220UM
2
solid
1000
304.8
49
22.23
.034
.86
.33
8.38
19
62
4.0
5222UM
4
solid
1000
304.8
81
36.74
.034
.86
.38
9.65
19
62
4.0
14 AWG
5120UM
2
solid
1000
304.8
71
32.21
.034
.86
.36
9.14
21
69
2.5
5122UM
4
solid
1000
304.8
121
54.88
.034
.86
.41
10.41
21
69
2.5
1
12 AWG
5020UM
2
solid
1000
304.8
100
45.36
.034
.86
.39
9.91
23
75
1.6
5022UM
4
solid
1000
304.8
168
76.20
.034
.86
.45
11.43
23
75
1.6
Shielded Multi-conductor Thermoset Elastomer Insulation Beldfoil
®
Shield
Red Polyolefin Jacket
18 AWG
NEC: FPLR-CI
5320FM
2
solid
1000
304.8
45
20.41
.034
.86
.31
7.87
27
89
6.5
UL Standard 2196
5322FM
4
solid
1000
304.8
70
31.75
.034
.86
.35
8.89
27
89
6.5
5324FM
6
solid
1000
304.8
100
45.36
.034
.86
.42
10.67
27
89
6.5
5326FM
8
solid
1000
304.8
125
56.70