Document 53119 Rev A December 18, 2006 ECN 06-857
MS-5UD/MS-10UD
with Keltron RCVR/XMTR
Wiring Diagram
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Sprinkler Supervisory Signal
Alarm/Trouble Signal
* Note: For more information,
refer to Keltron manual.
53119 Rev. A 12/18/06 ECN 06-857
4XTMF
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair of terminals.
CAUTION!
For reasons of wiring diagram clarity, terminal designations
of Keltron modules are not shown in actual order. Follow
Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
MS-5UD/MS-10UD Control Panel
(terminal blocks not shown in actual positions)
4XTMF Module
IMPORTANT!
All connections between the FACP and Keltron modules must be made within 20 feet
and enclosed within conduit or equivalently protected against mechanical injury.