MEA

d to the console. The user can then connect that
off-hook phone to the main riser for the voice evac system.
Wiring to individual telephone jacks and handsets is su-
pervised, and status is reported to the panel as NORMAL,
TROUBLE, or OFF HOOK. This module has two pairs of
output termination points available for fault-tolerant wiring
(Style Z), and includes a panel-controlled LED indicator.
FlashScan®
(U.S. Patent 5,539,389) is a new communica-
tion protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog in-
telligent devices. Intelligent devices communicate in a
grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and
concentrates on single points. The net effect is response
speed
greater than five times that of other designs.
FEATURES
Supports two firefighter telephones in either NFPA Style Y
or Style Z (Fault Tolerant) telephone circuits.
Direct-dial entry of address 01 159 for FlashScan®.
Built-in type identification automatically identifies itself to
the control panel.
Internal circuitry and relay powered directly by two-wire SLC
loop. Internal relay feature available on FlashScan® sys-
tems only.
Integral LED blinks green each time a communication is
received from the control panel.
LED blink may be deselected globally (affects all devices).
High noise immunity (EMF/RFI).
Wide viewing angle of LED.
SEMS screws with clamping plates for wiring ease.
FTM-1(A)
Firephone Control Module
with FlashScan®
September 15, 2005
DN-6989 H-250
Section: Intelligent/Addressable Devices
FlashScan® and NOTIFIER® are registered trademarks of Hon-
eywell International Inc. Noryl® is a registered trademark of GE
Plastics, a subsidiary of General Electric Company.
6724mod2.tif
CONSTRUCTION
The face plate is made of off-white Noryl®.
Controls include two rotary switches for direct-dial entry of
address (01-159).
The FTM-1 is configured for either a single Class B (Style
Y) or Class A (Style Z) telephone circuit.
6724face.wmf
S3705
NFS-640
NFS-3030
LCM
FTM-1 Software Compatibility
As of Ver. 3.1.3
As of Ver. 2.3.7
As of Ver. 2.2.9
CS762
MEA
110-04-E
FTM-1 Module
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472 Page 2 of 3 DN-6989 09/15/05
FTM-1(A) OPERATION
The FTM-1 uses one of 159 possible module addresses on
a SLC loop. It responds to regular polls from the control panel
and reports its type and status, including NORMAL,
TROUBLE, or OFF HOOK status of its telephone circuits.
The LED blinks with each poll received.
Upon code command from the panel, the FTM-1 will discon-
nect the supervision and connect the telephone riser to it's
telephone circuit. The telephone riser is always relay isolated
from the communication loop so that a trouble condition on
the riser will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the
control panel, so as to differentiate between a module and a
sensor address.
SPECIFICATIONS for FTM-1
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 7.5 mA (LED on).
Average operating current: 7.5 mA group poll (FlashScan®
mode) with LED flashing.
External supply voltage
(between Terminals T3 and T4):
maximum 28 VDC.
EOL resistance: 3.9K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
PRODUCT LINE INFORMATION
FTM-1
Intelligent Addressable Firephone Control
Module, 3.9K ohm End-of-Line Resistor included.
FTM-1A
Same
as FTM-1 with ULC listing.
SMB500
Optional Surface-Mount Electrical Backbox.
CB500
Control Module Barrier required by UL for sepa-
rating power-limited and non-power-limited wir-
ing in the same junction box as FTM-1.
6724mt1.wmf
6724mt2.wmf
MOUNTING
DIAGRAMS
Note CB500 Module Barrier,
which
creates isolated quadrant.
9
8
7
6
5
4
3
2
1
0
0
1
2
3
45
6 7 8 9
0
7 8
6
5
4
3
21
91011121314
15 DN-6989 09/15/05 Page 3 of 3

Fig. 1

M500MPJ: Typical circuit configuration, NFPA Style Y:
Connect modules to Listed compatible NOTIFIER control panels only.
All wiring shown is supervised
(required).

Fig. 2

M500MPJ: Typical fault tolerant circuit configuration, NFPA Style Z:
Connect modules to Listed compatible NOTIFIER control panels only.
All wiring shown is supervised
(required).
9
8
7
6
5
4
3
2
1
0
0
1
2
3
45
6 7 8 9
0
7 8
6
5
4
3
21
91011
12
13
14
15
9
8
7
6
5
4
3
2
1
0
0
1
2
3
45
6 7 8 9
0
7 8
6
5
4
321
91011
12
13
14
15
C0220-00.wmf
C0221-00.wmf