500-21 200 A 15 kV Class Insulated Protective Cap
cover for energized bush-
ings. The cap can be used for per-
manent or temporary installation on
bushings, junctions or feedthru
devices that meet the requirements
of ANSI/IEEE Standard 386.
INSTALLATION
No special tools are required. A shot-
gun stick tool is used to place the
protective cap on an exposed bush-
ing interface. Refer to Installation
Instruction Sheet S500-21-1 for
details.
PRODUCTION TESTS
Tests are conducted in accordance
with ANSI/IEEE Standard 386-1995.
ac 60 Hz 1 Minute Withstand
34 kV
Minimum Corona Voltage Level
11 kV
Tests are conducted in accordance
with Cooper Power Systems require-
ments.
Physical Inspection
Periodic Dissection
Periodic Fluoroscopic Analysis
TABLE 1
Voltage Ratings and Characteristics
Voltage ratings and characteristics are in accordance
with ANSI/IEEE Standard 386-1995.
ORDERING INFORMATION
To order the 15 kV Class Insulated
Protective Cap Kit, refer to Table 2.
TABLE 2
Insulated Protective Cap Kit
Each kit contains:
Protective Cap with stranded
copper ground wire
Silicone Lubricant
Installation Instruction Sheet
200 A 15 kV Class
Insulated Protective Cap
Figure 1.
Insulated Protective Cap electrically insulates and mechanically seals loadbreak
bushing interfaces.
Description
kV
Standard Voltage Class
15
Maximum Rating Phase-to-Phase
14.4
Maximum Rating Phase-to-Ground
8.3
ac 60 Hz 1 Minute Withstand
34
dc 15 Minute Withstand
53
BIL and Full Wave Crest
95
Minimum Corona Voltage Level
11
Description
Catalog Number
Protective Cap
LPC 215
P.O. Box 1640
Waukesha, WI 53187
Features and Detailed Description
2
Figure 2.
Illustration shows construction of insulated protective cap.
RTE
®
is a registered trademark of Cooper Industries, Inc.
&
_
`
SEMI-CONDUCTIVE SHIELD
Molded semi-conductive EPDM
shield meets requirements of
ANSI/IEEE Standard 592.
LATCHING RING
Semi-conductive molded
locking ring locks cap
onto nose piece of mating
interface.
GROUNDING WIRE AND
GROUNDING EYE
48-Inch, #14 AWG stranded
copper ground wire is tin
plated and ensures dead-
front construction when tied
off to ground.
GROUNDING EYE
(Optional for larger
grounding wire)
PULLING EYE
Stainless steel reinforced
pulling eye ensures high
strength for shotgun stick
operation.
SEMI-CONDUCTIVE INSERT
Semi-conductive insert is molded of
semi-conductive EPDM and controls
electrical stresses at nose of mating
loadbreak product.
PROBE
Probe provides reliable
conductive path with
mating female contacts.
EPDM INSULATION
High quality peroxide
cured EPDM insulation
is mixed and formulated
in-house for complete
control of insulating
rubber characteristics.
Figure 3.
15 kV Insulated Protective Cap profile and stacking dimensions.
02.82
(71.5 mm)
S3 = 2.15
(54.5 mm)