JVW-4/JVW-5
width=100%>Yahoo! is not affiliated with the authors of this page or responsible for its content.
JVW-4/JVW-5
2-8
Data subject to change without notice.
GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555
2,400 V to 14,400 V BIL 75 kV to 110 kV
Outdoor Voltage
JVW-4/JVW-5
60 Hz
Application
Designed for outdoor service; suitable for operating
meters, instruments, relays, and control devices.
Thermal Rating (Volt-Amperes)
55
癈 Rise above 30癈 Ambient ............................. 1500
ANSI Meter Accuracy Classification, 60 Hz
Operated at rated voltage
W, X, M, Y, Z; all models ........................................ 0.3
ZZ; all models ......................................................... 1.2
Operated at 58% of rated voltage
W, X, M, Y; all models ............................................ 0.3
Z; all models ........................................................... 1.2
Burden impedance as at rated voltage, but operated at
58% of rated voltage
W', X' M', Y', Z'; all models .................................... 0.3
Weight - Shipping/Net
(approximate, in pounds)
Transformer ...................................................... 120/105
Reference Drawings
JVW-4
Accuracy Curve at
120 Secondary Volts, 60 Hz ....................... 9689241659
Excitation Curves:
60:1 & 70:1 ............................................... 9689241591
100:1 & 120:1 ........................................... 9689241629
Outline Drawing; Two-Bushing
Transformer ...................................................... 9932529
Wiring Diagram .................... refer to page 42, figure 5
JVW-4 -5, two-bushing model
Notes:
For continuous operation, the transformer-rated primary voltage should not be
exceeded by more than 10%. Under emergency conditions, over-voltage must be
limited to 1.25 times the transformer primary-voltage rating for two-bushing models,
and 1.40 times the rating for single-bushing models.
Applies to transformers connected Y-Y on a circuit in which the line-to-line voltage
is the same as the transformer-rated primary voltage. In each case, the transformer
is operated with reduced voltage and reduced excitation (58% of normal). In
determining the accuracy classification under such conditions, the Volt-Ampere
rating of the burden is maintained constant, regardless of the transformer
secondary voltage.
The prime symbol () is used to signify that these burdens do not correspond to
standard ANSI definitions.
Single-bushing design with removable grounding strap.
12,470 in Y configuration.
14,560 in Y configuration.
AVAILABLE
When choosing your GE Instrument Trans-
former, don't forget to explore the benefits of
using GE's 0.15 accuracy class AccuBute line.
See page 2.10.
JVW-4/JVW-5 DATA TABLE
Catalog Number
Circuit Voltage
Transformer
JVW-4
JVW-5
For Permissible
Rating
BIL 75 kV
BIL 110 kV
Primary Connection
Primary
Two-Bushing
Single-Bushing
Two-Bushing
Y
Y Only
GY Only
Voltage
Ratio
Model
Model
Model
2,400
2,400
4,160
---
2,400
20:1
764X030011
---
---
4,200
4,200
7,280
---
4,200
35:1
764X030012
---
---
4,800
4,800
8,320
---
4,800
40:1
764X030013
---
---
7,200
7,200
---
---
7,200
60:1
764X030014
---
---
---
---
---
7200
7,200
60:1
---
765X030051
765X030042
---
---
---
8400
8,400
70:1
---
765X030052
765X030044
12,000
12,000
12,000
---
12,000
100:1
---
---
765X030045
14,400
14,400
14,400
---
14,400
120:1
---
---
765X030046
Line-To-Line
GE Meter 130 Main St., Somersworth, NH 03878 USA & Canada: (800) 626-2004 Fax: (518) 869-2828; GE Worldwide: (518) 869-5555
2-9
Data subject to change without notice.
Outdoor Voltage JVW-4/JVW-5
JVW-5
Accuracy Curve at
120 Secondary Volts, 60 Hz ....................... 9689241659
Excitation Curves:
60:1 & 70:1 ............................................... 9689241591
100:1 & 120:1 ........................................... 9689241629
OutlineDrawings:
Two-Bushing Model ...................................... 9932529
Single-Bushing Model ................................... 9932530
Wiring Diagram .................... refer to page 42, figure 5
Accessories ........................... Catalog Number
Mounting Hardware
L Mounting Brackets ........................... 8944634002
Channel Bracket ..................................... 5466227001
Suspension Hooks ................................... 8944630001
Secondary Conduit Box ............................. 9689897001
Construction and Insulation
Please refer to General Product Information, item 1.4.
Core and Coils
Please refer to General Product Information, item 3.8.
Primary
Terminals
Please refer to General Product Information, item 4.6.
Secondary
Terminals
Please refer to General Product Information, item 4.18.
Ground Terminal
Please refer to General Product Information, item 4.23.
Conduit Box
Please refer to General Product Information, item 12.1.
Polarity
Please refer to General Product Information, item 7.2.
Baseplate and Mounting
Please refer to General Product Information, items 5.3,
5.15, and the Applications Information Section of this
volume.
Nameplate
Please refer to General Product Information, item 6.4.
Rating Identification
Please refer to General Product Information, item 13.1.
Maintenance
Please refer to General Product Information, item 10.1
and pages 24-27.
Note:
1. Voltage transformers of this type are available for use in 50 Hz appli-
cations in many ratings. However, Industry Standard IEEE 57.13 to which
we test transformers does not apply at 50 Hz. Customers who order
voltage transformers for 50 Hz application should provide an accuracy
specification including Burden VA and Power Factor. If an accuracy
specification is not made available, the transformer(s) will be tested at
60 Hz with test burdens as defined in IEEE 57.13 for 60 Hz application.
H1
12000
X1
GRD
13.19
(33.50)
16.88
(42.88)
12.25
(31.12)
14.25
(36.20)
9.94
(25.25)
10.00
(25.40)
11.00
(27.94)
13.13
(33.35)
9.50
(24.13)
8.63
(21.92)
0.44 (1.12) Dia.
(8 holes)
Inches
(CM)
JVW-4/JVW-5 mechanical dimensions