ROME TELEPHONE POWER CABLE, 600 VOLTS
.acewireco.com/pdfs/7066.pdf. It's a snapshot of the page taken as our search engine crawled the Web.
The web site itself may have changed. You can check the current page or check for previous versions at the Internet Archive.
Yahoo! is not affiliated with the authors of this page or responsible for its content.
ROME TELEPHONE POWER CABLE, 600 VOLTS
ROME TELEPHONE POWER CABLE, 600 VOLTS
Flexible Conductor, HYPALON
®
Insulation, Cotton Braid, Gray Saturant and Finish
Type RHH or RHW, VW-1, Oil Res ll, Sun Res For CT Use
Size AWG
or kcmil
No. of
Strands
Insulation Thickness
Nominal Diameter
Approx. Net Weight
Ampacity*
Mils
mm
Inches
mm
lb/1000 Ft.
kg/km
RHH
90
o
C Dry
RHW
75
o
C Wet/Dry
8
6
4
2
1/0
2/0
4/0
350
500
750
41
63
105
161
266
342
532
888
1258
1850
60
60
60
60
80
80
80
95
95
110
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.41
2.41
2.79
.33
.38
.44
.50
.66
.70
.82
1.04
1.22
1.42
8.4
9.6
11.2
12.7
16.8
17.8
20.8
26.4
31.0
36.1
100
140
215
305
510
577
847
1377
1920
2750
149
208
320
454
759
859
1261
2049
2857
4092
55
75
95
130
170
195
260
350
430
535
50
65
85
115
150
175
230
310
380
475
*AMPACITY in accordance with NEC for not more than three conductors in raceway at the temperature indicated, 30
o
C ambient temperature.
NOTES:
1. Standard color is gray. Other colors available upon request.
2. Size 6 AWG and larger.
3. HYPALON
®
is a DuPont synthetic rubber.
4. This cable also referred to as CK-20921 List 2 (with braid).
Information on this sheet subject to change without notice.
SPEC 7066
January 1, 2002
APPLICATION: General purpose wiring in telecommunications central office
and transmission stations. Cables are intended for use in 600 volt ac or dc
distribution circuits, in wire-ways, conduits and cable trays where a flexible
cable with outstanding resistance to abrasion, heat, moisture and flame is
required. Cables are rated 90
o
C in dry locations and 75
o
C in wet locations.
STANDARDS:
1.
Listed by UL as Type RHH or RHW per Standard 44.
2.
Cables pass UL and IEEE-383 ribbon burner flame test and are UL listed
Sunlight Resistant For CT Use (1/0 AWG and larger).
3.
All sizes UL listed as VW-1.
4.
Insulation UL listed as Oil Resistant ll.
5.
Listed by CSA as 105
o
C AWM, 600V, FT1 and FT4 (4 AWG and larger).
6.
Insulation and treated cotton braid have LOI of 28% minimum per ASTM
D-2863.
7.
Class I stranding per ASTM B-172.
8.
Cable complies with Bellcore Spec GR-347-CORE.
CONSTRUCTION: Annealed tinned bunch rope stranded copper conductor,
separator, black HYPALON
®
(chlorosulfonated polyethylene) insulation, poly-
ester tape, cotton braid, gray saturant and finish, surface printed.
Cotton Braid
with Gray Saturant
and Finish
Hypalon
Insulation
Polyester
Tape
(2)
Tinned
Copper
Conductor
SPEC 7066
1-1-02
Specification
ROME TELEPHONE POWER CABLE, 600 VOLTS
Flexible Conductor, HYPALON
®
Insulation, Cotton Braid, Gray Saturant and Finish
Type RHH or RHW, VW-1, Oil Res ll, Sun Res For CT Use
1. SCOPE
1.1
This specification describes a flexible single conductor HYPALON
®
(chlorosulfonated polyethylene) insulated, cotton
braided Telephone Power Cable suitable for general purpose wiring in telecommunications central office power plants.
Cables may be installed in raceways, on racks or trays, or internally in equipment. Cables are listed by UL as Type
RHH or RHW for general purpose building wire applications in circuits not exceeding 600 volts at a maximum
continuous conductor temperature of 90
o
C in dry locations or 75
o
C in wet locations. Cables are listed by UL as
VW-1 and Oil Resistant ll. Sizes 1/0 AWG and larger may be used in cable tray in accordance with Article 336 of the
NEC. Cables are also listed by CSA as 105
o
C AWM and have FT1 (all sizes) and FT4 (4 AWG and larger) flame ratings.
2. APPLICABLE STANDARDS
2.1
The following standards form a part of this specification to the extent specified herein:
2.1.1
Underwriters Laboratories Standard 44 for Rubber Insulated Wires and Cables.
2.1.2
Canadian Standards Association Standard C22.2 No. 210.2 for Appliance Wiring Material.
2.1.3
ASTM D-2863, latest issue - Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics.
2.1.4
Bellcore Spec GR-347-CORE Generic Requirements for Central Office Power Wire.
2.1.5
ASTM B 172 Rope Lay Stranded Copper Conductors.
3. CONDUCTORS
3.1
Conductors shall be bunch (size 8 AWG) and rope-lay stranding with No. 24 AWG soft tinned copper wires conforming
to ASTM B 172, Class I.
4. SEPARATOR
4.1
An opaque polyester separator tape shall be applied between the conductor and the insulation. (On size 750 kcmil,
a fabric tape is used).
5. INSULATION
5.1
Each conductor shall be insulated with Rome-HYPALON, a black chlorosulfonated polyethylene rubber compound
complying with the physical and electrical requirements of UL Standard 44 for Type RHH or RHW and 105
o
C AWM
requirements of CSA C22.2 No. 210.2 The insulation shall have a minimum LOI of 28% when tested in accordance
with ASTM D-2863.
5.2
The average thickness of insulation shall be as specified in UL Standard 44 for Type RHH or RHW. The minimum
thickness at any point shall be not less than 90% of the specified average thickness. The insulation shall be applied
tightly to the conductor and shall be free stripping.
6. TAPE
6.1
On sizes 6 AWG and larger, the insulation shall be covered with a wrapped opaque polyester tape.
7. BRAID
7.1
A close-weave cotton braid shall be applied over each cable. The braid shall comply with the requirements of UL
Standard 44.
8. SATURANT/FINISH
8.1
The cotton braid shall be saturated with a heat, moisture and flame-retardant compound complying with requirements
of UL Standard 44. Color of the saturant compound shall be gray.
8.2
The saturated cotton braid shall be coated with a lacquer paint to provide a gray color.
8.3
The saturated lacquered cotton braid forming the external finish shall present a uniform external appearance, shall be
smooth, dry and free from irregularities and shall not flake-off.
8.4
The saturated, finished cotton braid shall have a minimum LOI of 28% when tested in accordance with ASTM D-2863.
9. SURFACE MARKING
9.1
An ink print legend shall be applied to each cable indicating manufacturer, size, voltage, UL and CSA designations.
10. TESTS
10.1 Completed cables shall be tested in accordance with the applicable requirements of UL Standard 44, CSA Standard
C22.2 No. 210.2 and Bellcore Spec GR-347-CORE.