Commercial generator set Standard Diesel

te>
Commercial generator set Standard Diesel Cummins
®
, Onan
®
, the "C" logo, Performance you rely on.
TM
and Standard Diesel
TM
are
servicemarks, trademarks and/or registered trademarks of Cummins Inc.
Specifications subject to change without notice
©2007 Cummins Power Generation. All Rights Reserved.
A-1393d (4/07)

Commercial generator set
Standard Diesel
TM
Series
SD 10.0 60 Hz/8.0 50 Hz




Features and benefits


Weight, size and sound level

Low vibration for smooth operation
Powerful 18.6 hp engine
User-friendly remote control option
Cross-flow radiator for increased cooling efficiency
Installation flexibility with remountable 90° exhaust
elbow and two oil fill locations


Weight:

520 lb (236.9 kg)
Size:
- 60 Hz (single phase) length 39.5 in (1003 mm), width
21.0 in (533 mm), height 26.0 in (662 mm);
- 50 Hz (3 phase) length 40.5 in (1028 mm), width 21.0
in (533 mm), height 26.0 in (662 mm)
Sound:
- 60 Hz (single phase) 78 dB(A) at 10 ft (3 m) before
installation, full load
- 50 Hz (3 phase) 76 dB(A) at 10 ft (3 m) before
installation, full load

Models and ratings



Model Fan

Hz Watts Voltage
Amps
PF
Phase Circuit
breaker









10HDKAG/61731
Pusher 60 10000 120/240
83.3/41.7
1.0
1
2-pole,
45
A
10HDKAG/5008
#

Pusher 60 10000 120/240
83.3/41.7
1.0
1
2-pole,
45
A
10HDKAG/11322
Pusher 60 10000 120/240
30.1
0.8
3
3-pole,
35
A
10HDKAG/61733
Pusher 60 10000 120/208
34.7
0.8
3
3-pole,
35
A
10HDKAG/11509
Pusher 60 10000 100/200
100/50
1.0
1
2-pole,
50
A
10HDKAG/5280
#

Pusher 60 10000 100/200
100/50
1.0
1
2-pole,
50
A
8HDKAG/11378
Pusher 50 8000 Reconnectable* Reconnectable* 0.8
3
3-pole,
reconnectable*
8HDKAG/11473
Pusher 50 8000 110/220
72.7/36.4
1.0
1
2-pole,
40
A
8HDKAG/5007
#

Pusher 50 8000 110/220
72.7/36.4
1.0
1
2-pole,
40
A

- All 60 Hz models operate at 1800 r/min. All 50 Hz models operate at 1500 r/min.
- Ratings apply up to 500 ft (152.4 m) altitude, 85° F (29° C) ambient with No. 2 diesel fuel.
- Maximum power capability decreases 3.5% for each 1000 ft (305 m) above 500 ft (153 m) and 1% for each 10° F (5.5° C) increase in
ambient temperature above 85° F (29° C).
* 12-lead reconnectable for a broad range of voltage applications.
#
With export packaging.

Cummins
®
, Onan
®
, the "C" logo, Performance you rely on.
TM
and Standard Diesel
TM
are
servicemarks, trademarks and/or registered trademarks of Cummins Inc.
Specifications subject to change without notice
©2007 Cummins Power Generation. All Rights Reserved.
A-1393d (4/07)
Standard features

Engine details
4-cylinder diesel engine
Brush type AC alternator
Bi-directionally optimized mounting system with
4-point vibration isolation
Cross-flow radiator
Full flow lube oil filter
Fuel filter/water separator
Vertically mounted fuel and oil filters
Replaceable element air cleaner
Remote mountable DC control box
4-position exhaust elbow
30 A battery charging DC alternator
Lifting bracket
Glow plugs for easy starting
Base pan for drip control
Electric fuel pump


Model: Kubota V1305
Design: 4-cycle, liquid-cooled diesel engine
Cylinders: 4, inline vertical
Bore: 2.99 in (76.0 mm)
Stroke: 2.90 in (73.6 mm)
Displacement: 81.4 in
3
(1336 cm
3
)
Compression ratio: 22:1
Lube oil capacity: 5 qt (4.7 L), including filter
Power (max): At 1800 r/min: 18.6 hp
Cooling system capacity: 1.25 Gal (4.73 L)
Starting system: Remote, 12 V
Fuel injection pump: Bosch K mini
Fuel pump: Electric
Combustion chamber: Spherical


Typical fuel consumption

No. 2 diesel fuel, Gal/hr (L/hr)
No load Half
load Full
load
10HDKAG
0.29 (1.10)
0.55 (2.08)
1.04 (3.90)
8HDKAG
0.26 (0.98)
0.45 (1.71)
0.94 (3.52)
Alternator details
Design: Cummins Onan, brush type, drip proof
construction
Insulation system: Class F, per NEMA MGI-1.65 and
BS 2757; insulating varnish conforms to MIL-I-24092,
grade CB, Class 155 C
Three-phase models: Broad range reconnectable
design for installed voltage flexibility
Exciter system: Electronic voltage regulation
Bearing: Double sealed, pre-lubricated ball bearing.
Cooling: Direct drive centrifugal blower
Damper bar system: Generator set design (100 V
spec unit only) incorporates a damper bar system which
results in low harmonic waveform distortion. This design
feature becomes significant when powering SCR type
loads (converters, etc.)


Generator set details
Control
- Unit mounted, drip-proof, vibration isolated console
DC controls, 12 V system
- Start/stop/preheat switch
- Remote connector for start/stop/preheat switch and
gauge package
- Manual reset fault relay indicating engine shutdown for
high coolant temperature, low oil pressure
- Hour meter
AC controls
- Electronic voltage regulator
- Three-phase models, factory shipped reconnectable
(no breaker on 50 Hz models)
- Three-phase breaker kits available for field fitted
installation



No load/full load Constant
load
Voltage regulation:
±2.5%

±1%

Frequency regulation:
±2.5%

±1%
Cummins
®
, Onan
®
, the "C" logo, Performance you rely on.
TM
and Standard Diesel
TM
are
servicemarks, trademarks and/or registered trademarks of Cummins Inc.
Specifications subject to change without notice
©2007 Cummins Power Generation. All Rights Reserved.
A-1393d (4/07)
Basic dimensions

FAN OPTIONS
PUSHER
SUCKER

Note: This outline drawing is provided for general reference only and is not intended for design or installation. For more information see
Operation and Installation manuals or obtain drawing 500-3105 and wiring diagram from your distributor/dealer.


Options and accessories


USDA Forest Service approved spark arrestor muffler
(P/N 155-2262)
Exhaust resonator (P/N 155-2653)
Remote gauge package with start/stop/preheat switch,
DC voltage meter, water temperature gauge, oil pressure
gauge, running time meter (P/N 300-5026)
Remote control panel, switch only (P/N 300-4939)
Remote control panel, switch and hour meter
(P/N 300-4940)
Remote control panel, switch and DC voltmeter
(P/N 300-4941)
Remote harness (for use with above panels), 15 ft
(P/N 338-2237), 25 ft (P/N 338-2238)

Remote harness pigtail at set (P/N 338-2102)
Remote harness pigtail at panel (P/N 338-3573)
Engine block heater (P/N 333-0593)
Coolant overflow recovery kit (P/N 130-2781)
Fan conversion kit (pusher to suction) (P/N 130-4121)
Fan conversion kit (suction to pusher) (P/N 130-4556)
45 A circuit breaker kit (P/N 320-1840)
Auxiliary alternator air cooling kit on suction fan units
for compartment-mounted generator sets
(P/N 140-3214)

Cummins
®
, Onan
®
, the "C" logo, Performance you rely on.
TM
and Standard Diesel
TM
are
servicemarks, trademarks and/or registered trademarks of Cummins Inc.
Specifications subject to change without notice
©2007 Cummins Power Generation. All Rights Reserved.
A-1393d (4/07)
Standards and testing


After sale support

- Tested at extremes of temperature -20
°
F (-29
°
C) to
120
°
F (49
°
C) for starting and operation
- Tested with commercial loads
- Tested in high humidity conditions
- Tested in salt spray conditions
- Tested in heavy airborne dust conditions
- Field test program
- This product meets U.S. EPA Tier II
- This generator set was designed and manufactured in
facilities certified to ISO 9001

Warranty policy

The Cummins Onan limited warranty covers virtually
everything except routine maintenance for the first two
years you own your generator set, or the first 2,000 hours
of operation, whichever comes first. In addition, it
includes a free 90-day adjustment policy, which provides
that Cummins Inc. will make minor adjustments to your
new generator set during the first three months you own
it - free of charge!





Largest distributor/dealer support network
Cummins Onan generator sets are supported by the
largest and best trained worldwide certified
distributor/dealer network in the industry. This network
of knowledgeable Cummins Onan distributor/dealers will
help you select