SDZ / Spot Detector for Zone Panels

ation is greater than or
equal to 100 feet from the water
sensing cable. If less than 100 feet,
consider using water sensing cable. Company Confidential
Copyright © RLE Technologies
16
RLE
Technologies
RLE Technologies
SDZ / Spot Detector for Zone Panels
3/8"
1"
3/16"
3 1/2"
2"
2 1/4"
Approx 3/4"
12" leader,
with 4 pin
connectors
Water Sensing Probes
2 holes for mounting, ram set
studs to floor or use concrete
anchors. For drip pans J Clips?
Adjust nut to set water sensing
level and/or bend sensing
probes
Connect to RLE Non-sensing cable or end-of-line terminator. Company Confidential
Copyright © RLE Technologies
17
RLE Technologies
RLE Technologies
SDZ / Spot Detector for Zone Panels
Pin 1
Pin 2
Pin 3
Pin 4
Pin
1
Pin 2
Pin 3
Pin 4
Schematic
The water sensing probes function the same as the
water leak detection sensing cable in the sensing cable.
The SDZ will technically add 1 to the overall cable
length. Company Confidential
Copyright © RLE Technologies
18
RLE Technologies
RLE Technologies
SDZ / Spot Detector for Zone Panels
LDZ1
Power
Fault
Leak
Quiet/Reset/Test
R
RLE Technologies
SeaHawk
Typically installed in-line with Non-sensing cable.
Leader Cable
Sensing Cable
Non-
Sensing
Cable
End-of-line
Terminator Company Confidential
Copyright © RLE Technologies
19
RLE Technologies
RLE Technologies
SDZ / Spot Detector for Zone Panels
Pin 1
Pin 2
Pin 3
Pin 4
Pin
1
Pin 2
Pin 3
Pin 4
Troubleshooting:
Verify < 1 Ohm, Pin 1 to Pin 1, Pin 2 to Pin 2, etc.
Verify an open circuit between pins (no shorts)
If water is between the probes, the meter may read 100K to 2M Ohms
between pins 2 and 3.
Testing:
Place water between the probes and verify that the LD panel alarms on leak.
Remove the water and verify the panel returns to normal.
Disconnect one end and verify the panel alarms on cable fault, reconnect the
SDZ and verify the panel returns to normal.