INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNERS USE.
ZoneTrol
Zone Pump Controller
Models ZT-2, ZT-3, ZT-4 & ZT-6
Installation, Operation and Service Instructions
SAFETY
INSTRUCTION
This safety alert symbol will be used in this manual to draw
attention to safety related instructions. When used, the safety
alert symbol means ATTENTION! BECOME ALERT! YOUR
SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN-
STRUCTIONS MAY RESULT IN A SAFETY HAZARD.
DESCRIPTION
The ZoneTrol is a ready-to-install multiple-zone controller for
circulator pumps in hydronic systems. The ZoneTrol con-
trollers feature switchable priority, powerful transformer, auto-
matic resetable fuse and a built-in 30 minute timer on priority
circuit. The units are operated by two-wire 24-volt thermo-
stats and requires connection to a 120 V, 60 Hz source voltage.
BEFORE STARTING THE JOB
Please read instructions completely before starting work
The applications for the ZoneTrol zone pump controllers are
too numerous to show all the various illustrations for the dif-
ferent models. The ZT-4 (four zone) and ZT-2 (two zone) pump
controller will be illustrated in this manual for installation and
application purposes. The other multiple zone pump con-
trollers are installed in a similar matter. The circuit diagrams
indicate the proper terminals for wiring the ZoneTrol for most
applications.
All work must be performed by qualified personnel in
accordance with all applicable codes and ordinances.
Electrical connections must be made using copper wire
only.
Maximum
Maximum
Single Phase Motor Rating
Model
Numbers
Relay
Thermostat
Transformer
Ambient
(Each Relay)
No.
of Zones
Type
Current
Voltage
Temperature
120 V AC
240 V AC
ZT-2
2
120V, 60HZ; 20VA
ZT-3
3
DPST
0.085 A
105癋 (40癈)
10A,
1
/
3
HP
10A,
1
/
2
HP
ZT-4
4
120V, 60HZ; 30VA
ZT-6
6
WARNING LABEL PART NO. V56871
INSTALLED ON PRODUCT. IF
MISSING, IT MUST BE REPLACED
Bell & Gossett
Instruction Manual P80925B
MECHANICAL INSTALLATION INSTRUCTIONS
The ZoneTrol unit should be securely mounted on a wall, shelf,
or partition near the pumps using four #8 screws (not included).
ELECTRICAL INSTALLATION INSTRUCTIONS
FOR MODELS ZT-4 AND ZT-6
Cold Start Boiler Applications
The cold start boiler application provides circulator operation
whenever a zone thermostat calls for heat (regardless of boiler
water temperature) and will start the burner when used in con-
junction with an isolated end switch connected to the aquastat
on the boiler.
1) A factory installed jumper is connected between the ZC/ZR
terminals. Leave the jumper in its current position.
2) Attach the low voltage SPST thermostat leads to the
respective thermostat teminals.
3) Attach circulator leads to respective terminals.
4) Connect supply voltage line to the terminals marked 120
VAC, located on the lower right side of the circuit board.
5) Connect isolated switch (terminals XX) to TT terminals on
boiler aquastat. Note: The required aquastat connections
may vary, depending on model. Refer to aquastat manufac-
turers instructions to ensure appropriate interconnections.
2
WARNING: Electrical shock and potential circuit
damage. Disconnect power supply before beginning
installation. Failure to follow these instructions could result
in serious personal injury or death and property damage.
WARNING: Improper wiring and wire can cause elec-
trical shock and fires. Wiring connections must be
made in accordance with all applicable electrical codes and
ordinances. Use copper wire only. Failure to follow these
instructions could result in serious personal injury or death
and property damage.
Class 2 Terminals
Primary Terminals
Class 2
T
e
rminals
JUMPER
WARNING: Electrical shock and potential circuit
damage. Disconnect power supply before beginning
installation. Failure to follow these instructions could result
in serious personal injury or death and property damage.
WARNING: Improper wiring and wire can cause elec-
trical shock and fires. Wiring connections must be
made in accordance with all applicable electrical codes and
ordinances. Use copper wire only. Failure to follow these
instructions could result in serious personal injury or death
and property damage.
WARNING: Potential electrical overload. Each circuit
is limited to a maximum of 10 amps and
1
/
3
HP. The
combined load for the controller is limited to 20 amps and
1 HP maximum. Failure to follow these instructions could
result in serious personal injury or death and property
damage.
Tankless Coil Boiler Applications
The tankless coil boiler application activates the boiler and
permits circulator operation only after boiler water has reached
the low temperature limit settings. If boiler temperatures drop
below the low limit setting, all circulators will cease operation
until the low limit temperature of the boiler is satisfied.
1) A factory installed jumper is connected between the ZC/ZR
terminals. Remove the jumper.
2) Connect the ZC/ZR terminals to the corresponding ZC/ZR
terminals on the boiler aquastat. The XX terminals are not
used. Note: The required aquastat connections may vary,
depending on model. Refer to aquastat manufacturers'
instructions to ensure appropriate interconnections
3) Attach the low voltage SPST thermostat leads to the
respective thermostat teminals.
4) Attach circulator leads to respective terminals.
5) Connect supply voltage line to the terminals marked 120
VAC, located on the lower right side of the circuit board.
Priority
If the priority switch is in the ON position, Zone 1 is the priority
zone. When the priority zone 1 circulator is actuated, the other
circulators will not operate. The ZoneTrol has a 30 minute
timer on the priority zone. After 30 minutes of continous oper-
ation, the priority zone function will default allowing all zones
to operate preventing possible house freeze up. The timer is
automatically reset after the priority zone is satisfied.
If the priority switch is not in the ON position, all zones operate
independent of each other.
ELECTRICAL INSTALLATION INSTRUCTIONS
FOR MODELS ZT-2 AND ZT-3
Tankless Coil Boiler Applications
The tankless coil boiler application activates the boiler and
permits circulator operation only after boiler water has reached
the low temperature limit settings. If boiler temperatures drop
below the low limit setting, all circulators will cease operation
until the low limit temperature of the boiler is satisfied.
1) A factory installed jumper is connected between the L1/ZC
terminals. Move the jumper to the terminal as shown on
the circuit board.
2) Attach the low voltage SPST thermostat leads to the
respective thermostat teminals.
3) Attach circulator leads to respective terminals.
4) Connect supply voltage line to the L1 and L2 terminals
located in the lower center portion of the circuit board.
5) Connect the ZC/ZR terminals to the corresponding ZC/ZR
terminals on the boiler aquastat. The XX terminals are not
used. Note: The required aquastat connections may vary,
depending on model. Refer to aquastat manufacturers'
instructions to ensure appropriate interconnections.
Priority
The ZT-2 and ZT-3 pump controllers are supplied from factory
ready for priority applications. When the priority zone 1 circu-
lator is actuated, the other circulator(s) will not operate. The
ZoneTrol has a 30 minute timer on the priority zone. After
30 minutes of continous operation, the priority zone function
will default allowing all zones to operate preventing possible
house freeze up. The timer is automatically reset after the
priority zone is satisfied.
For applications where priority is not desired, add second
jumper (remove one from L1 and ZC terminals) between the
terminals that are marked ADD JUMPER FOR PRIORITY
OFF and cut jumper wire between S-J (see drawing). This will
disable the priority feature allowing all zones to operate inde-
pendent of each other.
SERVICE INSTRUCTIONS
The ZoneTrol is quality constructed and should provide many
years of trouble-free service when installed and operated in
accordance with the instruction manual. To ensure optimum
long-term performance, once each heating season, visually
inspect the unit to check the condition of the contacts on the
plug-in replaceable relays. Replace the relay(s) if contacts
appear pitted or severely blackened.
The 24 volt fuse is temperature sensitive and will automatically
reset after a couple of minutes cooling time.
WARNING: Potential electrical shock. Disconnect all
power to unit before removing chassis cover. Failure
to follow these instructions could result is serious personal
injury or death and property damage.
3
Cold Start Boiler Applications
The cold start boiler application provides circulator operation
whenever a zone thermostat calls for heat (regardless of boiler
water temperature) and will start the burner when used in con-
junction with an isolated end switch connected to the aquastat
on the boiler.
1) A factory installed jumper is connected between the L1/ZC
terminals. Leave the jumper in this position.
2) Attach the low voltage SPST thermostat leads