LZS-A500-3 POWER SUPPLY
« back to results for ""
Below is a cache of http://www.lambdapower.com/ftp/manuals/lzsa500_man.pdf. It's a snapshot of the page taken as our search engine crawled the Web.
The web site itself may have changed. You can check the current page or check for previous versions at the Internet Archive.
Yahoo! is not affiliated with the authors of this page or responsible for its content.
LZS-A500-3 POWER SUPPLY
LZS-A500-3 POWER SUPPLY
Installation, Operation, and Maintenance Manual
IM-LLZSA500-33
January 2008
Revision H
Revision H : January 2008
3055 Del Sol Blvd San Diego, CA 92154 1-800-LAMBDA-4
LZS-A
A500-33 Power Supply
Page. 1
Table of Contents
1) Safety and Recommended Practices
2
1.1
General safety instructions
2
1.2
Safety Agency Approvals
2
2) RATINGS AND SPECIFICATIONS
4
3) FEATURES
5
4) GUIDE TO APPLICATION
7
4.1
Safety Notice
7
4.2
Input Voltage
7
4.3
Output Voltage
7
4.4
Overvoltage Protection Circuit Adjustment
7
4.5
Overtemperature and Overvoltage Shutdown
7
4.6
Auxiliary Control and Alarm Signals
7
5) FIGURES
8
LZS-A
A500-33 Power Supply
Revision H : January 2008
Page. 2
1 Safety and Recommended Practices
1.1 General Safety Instructions
This power supply is a switch mode power supply for use in applications meeting a Pollution Degree
2 environment. A suitable mechanical and fire enclosure must be provided by the end use equip-
ment for shock hazard protection, fire protection and protection from hazardous energy levels.
READ SAFETY INSTRUCTIONS carefully before working on the unit.
HIGH VOLTAGE WARNING: Dangerous voltages are present within the power supply.
NO USER SERVICEABLE PARTS INSIDE.
1. Do not install, test or operate this product near water, and do not spill any liquid on it.
2. Do not operate this product unless it is in a secure position.
3. This product must be installed and put into service by authorized competent personnel only
who are fully conversant with the hazards of AC line operated equipment and with the
particular dangers associated with switch mode power supplies.
4. This product is designed for use within other equipment or enclosures which restrict access to
authorized competent personnel only and must not be user accessible.
5. This product must be reliably earthed and professionally installed in accordance with the
prevailing electrical wiring regulations and safety standards. The product's PE connection is via
the tapped standoff and screw on the front panel marked with IEC 60417-1 Symbol 5019.
6. The case is connected to the products PE connection with screws. Therefore, screws at the case
must not be removed or loosened.
7. The output power taken from the power supply must not exceed the rating stated on the power
supply label.
8. Openings in the product case are designed for ventilation and must not be obstructed when
the product is installed and/or operated.
9. Never push objects of any kind into the product through openings in its case as this could
result in electric shock or fire hazard.
10. Use copper stranded wire only, 12 to 14 AWG rated at 105°C for the AC input. All strands
must be secured in the terminal block to avoid potential danger of short circuit.
11. Properly torque AC input terminals to 9 in-lb.
12. An internal fuse protects the unit and must not be replaced by the user. In case of internal
defect, the unit must be returned to the manufacturer.
13. The output of this power supply is hazardous and must not be user accessible in the end use
equipment. The (+) or (-) output can be earthed. Use wire rated at 105°C
and
sized for 150%
of the rated load.
14. The unit contains components that require special disposal. Make sure that the unit is
properly disposed of at the end of its service life.
1.2 Safety Agency Approvals
Regulatory agency compliance applies only for operating frequencies between 47- 63Hz.
No safety agency approvals for 100-380 VDC operation.
This product is approved to UL 60950-1/CAN CSA C22.2 No. 60950-1-03, First
Edition, UL 508, Seventeenth Edition, EN 60950-1:2001, IEC 60950-1:2001, FM.
The CE Marking, when applied to the product, indicates conformance to the
provisions of the following European Directives:
72/23/EEC
Low Voltage Directive as amended by 93/68/EEC
89/336/EEC EMC Directive as amended by 92/31/EEC and 93/68/EEC
3055 Del Sol Blvd San Diego, CA 92154 1-800-LAMBDA-4
LZS-A
A500-33 Power Supply
Revision H : January 2008
Page. 3
Emissions
Table 1
AC Line Conducted Emissions
EN55022/EN55011
(0.15-30 MHz) Class B
Radiated RF Emissions
EN55022/EN55011
30-1000 MHz Class B
Powerline Harmonics
EN61000-3-2
Class A Limits
Powerline Fluctuation/Flicker
EN61000-3-3
Complies
Immunity
Electrostatic Discharge
IEC61000-4-2
+/-8 kV Air
+/-6 kV Contact
RF Radiated Fields
IEC61000-4-3
10 V/m, 80 MHz-2.5GHz
80% AM @ 1kHZ
Electrical Fast Transients
IEC61000-4-4
+/-2 kV AC Line, Criteria A
+/-1 kV I/O Line > 3m, Criteria A
Lightning Surge
IEC61000-4-5
+/-2 kV line to GND (CM), Criteria A
+/-1 kV line to line (DM), Criteria A
Conducted RF Common Mode
IEC61000-4-6
10 V/m RMS, 150 kHz-80 MHz
80% AM at 1kHz
Power Frequency Magnetic Field
IEC61000-4-8
3 A/m
Voltage Dips/Short Variations
IEC61000-4-11
5% of nom. line for .5 cycles - Criteria A
40% for 5 cycles - Criteria A
70% for 25 cycles - Criteria A
95% Dip for 5 seconds -
Unit should not latch
SEMI-F47 (100 VAC)
50% of nom. line for 200 msec
70% for 500 msec
80% for 10 seconds
90% for 15 seconds
0% for 1 cycle or 20mS
Additional Immunity
Ring Wave Lightning Surge Test
IEEE C62.41
6 kV/30 Ohm Criteria A
Revision H : January 2008
Page. 4
LZS-A
A500-33 Power Supply
This manual is a description of specifications, features and applications of LZS-A500 power supplies.
RATINGS AND SPECIFICATIONS *
Maximum Ratings
Units
LZS-A500-3
Table 2
Output Voltage Range
V
18-29.4
Output Current (Power) @ 60°C**
A(W)
21 (504)
DC Output @ 24V
Output Current (Power) @ 70°C**
A(W)
12.6 (302)
Operating Temperature
°C
100% rated load from -30°C to 60°C derate linearly to
60% @ 70°C (4%/°C)
Start-up Temperature
°C
-40° to +70°
Input Specifications
Units
LZS-A500-3
Table 3
Input Voltage Range***
VAC
85-265 (47-440Hz) Single Phase
VDC
100-380
Input Current (RMS, maximum)
A
8 RMS
Inrush Current (Peak, at cold start)
A
25A /110VAC; 45A / 220VAC
Power Factor Harmonics
-
EN61000-3-2 Compliant
Power Factor (at max output power)
-
0.99 typical @ 85VAC
Input Power (maximum)
W
615W @ 21A (504W) and 85VAC line
Input Surge Protection
-
1kV Differential Mode; 2kV common mode
Input EMI Conducted Emissions
-
FCC Class B, CISPR 22 Class B
Efficiency (at max.output power)
%
84 typical @ 110VAC line
Output Performance Specifications
Units
LZS-A500-3
Table 4
Voltage Line Regulation
%
0.1
Voltage Load Regulation
%
0.1
Ripple and Noise @ 20 MHz
measurement Bandwidth.
(PARD-mVP-P)
75
Temperature Coefficient
%/°C
.01
Startup Time (at 110 VAC input)
Sec.
Less than 1 second
Overshoot
mV
No overshoot at turn on or turn off
Holdup Time (Full Power/220VAC)
mS
10
Ride through (Full Power/220VAC)
mS
20
Voltage Sag Immunity
(Full Power/110VAC)
-
Semi-F47 compliant
Load Transient Response
+/-1% of Vo ; 1A/µS; Recovers to within
(25% step load change)
-
+/-0.2% in < 1.25 mS
* Refer to figures 1-7 for supply-load connection information.
** Output current and power, as measured at output terminals, must be less than or equal to
quoted maximum values for a given ambient temperature.
*** Regulatory agency compliance applies only for operating frequencies between 47-63Hz.
No safety agency approvals for 100-380 VDC operation. Minimum turn-ON voltage for
DC Input is 110 VDC, unit will operate as low as 65 VDC after Power-up. Lambda doesnt
recommend operation below 100 VDC for more than one minute, or damage may occur.
Revision H : January 2008
Page. 5
3055 Del Sol Blvd San Diego, CA 92154 1-800-LAMBDA-4
LZS-A
A500-33 Power Supply
Operating Modes
Table 5
Series Operation
Yes (see Fig. 7)
Parallel Operation
Two or more identical units (see Fig. 6). (Use of D. con. terminal 5 will
(with current sharing)
provide current sharing to within 3% nominal of rated 40°C current.)
DC Output Controls and Indicators
Table 6
Output Voltage Adjust
Screwdriver adjustment over entire range. Output voltage range is from
18-29.4V. (Multi-turn potentiometer accessible from terminal end of chassis.)
Overvoltage Protection Adjust
Screwdriver adjustment over entire range. Overvoltage trip range is from
20-34V. Factory setpoint is 31.0V. (Multi-turn potentiometer accessible
from terminal end of chassis.)
Output Good Indicator
Green colored LED illuminates when output is within specified operating range
Fault Indicator
Red colored LED illuminates if overvoltage, overtemperature, or overcurrent
shutdown occurs. The LED is also illuminated if the output is less than approximately
95% of its adjusted output or if the output is inhibited (stand-by mode).
Remote Control Features
Table 7
Remote Voltage Sensing
Provides precise regulation directly at load (see Fig. 3). Maximum tot