SOUTH CENTRAL POWER COMPANY

supplied by the
Company remains property of the Company.
All service entrance equipment, including mast, is to be supplied and installed on the house by the Consumer.
A weatherhead shall be used, of proper size and type for the number and size of wire to be used.
Roof riser shall only be rigid galvanized steel conduit, of proper size as shown on reverse side and shall be securely
fastened to the building. It shall be of such length that the weatherhead must be a minimum of three (3) feet and not
to exceed a maximum of (5) feet above roof. Weatherhead shall be at (14) feet minimum above ground level.
Roof riser passage through the roof shall be completely waterproof.
From meter base to main switch, installations may be either service entrance cable or wire in conduit, as desired by
Consumer. If cable is used from meter base to main switch, a non-watertight connector shall be used at the bottom
of the meter base.
Main switch and fuse box must be located at a readily accessible location nearest the point of entrance of the
service conductors, when this is not possible, a UL approved external disconnect switch box must be installed.
GROUNDING:

Ground wire must be one continuous length without splice or joint from main switch to grounding electrode.
Driven ground rod shall be 5/8 X 8 copperclad or 5/8 X 8 solid galvanized steel, in undisturbed soil.
Ground rod clamp shall connect ground wire securely to the ground rod.
NOTES:

1. All installations to be made according to this sketch.
2. All materials to be approved by the Underwriters Laboratories or equivalent.
3. All wiring to be in accordance with the National Electrical Code.
4. Always have a qualified electrician take care of your wiring needs.
5. Consumers not following these minimum specifications will be refused service connection.
6. Service connections and/or meter removal shall be done only by authorized company personnel.
7. Reduced neutral may be allowed.
*** BEFORE ANY DIGGING FOR SAFETYS SAKE CALL OUPS (1-800-362-2764) ***

FORM 3-76-NEP-Revised 7-03
WIRING DIAGRAM MATERIAL SPECIFICATIONS:

100 Amp Meter Roof Riser Installation
150 Amp Meter Roof Riser Installation
ITEM
MATERIAL
100 AMP
SERVICE
ITEM
MATERIAL
150 AMP
SERVICE
1
Weather head ( Galvanized ) sized appropriately
When ready for
service connection,
please call the
Area Service Department at:
1
Weather head ( Galvanized ) sized appropriately
Service entrance cable, Type SE ( Copper )
# 4
Service entrance cable, Type SE ( Copper )
# 1
Service entrance cable, Type SE ( Aluminum )
# 2
Service entrance cable, Type SE ( Aluminum )
# 2/0
COPPER WIRE, Type THHW/THHN installed in conduit
# 4
COPPER WIRE, Type THHW/THHN installed in conduit
# 1
2
ALUMINUM WIRE, Type THHW/THHN installed in conduit
# 2
2
ALUMINUM WIRE, Type THHW/THHN installed in conduit
# 2/0
3
Conduit Galvanized Minimum size for Consumer service
entrance cable/conductors - Roof Riser Installation
2
3
Conduit Galvanized Minimum size for Consumer service
entrance cable/conductors Roof Riser Installation
2
4
Conduit PVC or Galvanized Minimum size for Consumer
service entrance cable/conductors if required
2
4
Conduit PVC or Galvanized Minimum size for Consumer
service entrance cable/conductors if required
2
5
Cable or conduit clamp spaced 18 maximum
5
Cable or conduit clamp spaced 18 maximum
6
Watertight connector ( for cable or conduit )
6
Watertight connector ( for cable or conduit )
7
Meter base -- must be supplied by the consumer and approved by the Company
7
Meter base -- must be supplied by the consumer and approved by the Company
8
Non-watertight connector ( for cable or conduit )
Lancaster :
Canal Winchester :
Circleville :
Hillsboro :
Barnesville :
1-800-282-5064
1-800-524-0802
1-800-206-0745
1-800-207-0020
1-800-468-4717
8
Non-watertight connector ( for cable or conduit )
9
Main switch and fuse box -- as required
100 AMP
9
Main switch or fuse box -- as required
150 AMP
10
Continuous ground wire from main disconnect switch box to
ground rod
# 6
Bare Copper
10
Continuous ground wire from main disconnect switch box to
ground rod
# 6
Bare Copper
11
Ground Rod : 5/8 x 8 copperclad or 5/8 x 8 galvanized steel
11
Ground Rod : 5/8 x 8 copperclad or 5/8 x 8 galvanized steel
12
Ground Rod Clamp
BEFORE ANY DIGGING
FOR SAFETYS SAKE
CALL OUPS ( 1-800-362-2764 )
12
Ground Rod Clamp

200 Amp Meter Roof Riser Installation
ITEM
MATERIAL
200 AMP
SERVICE
1
Weather head (Galvanized ) sized appropriately
Service entrance cable, Type SE ( Copper )
# 2/0
Service entrance cable, Type SE ( Aluminum )
# 4/0
COPPER WIRE, Type THHW/THHN installed in conduit
# 2/0
2
ALUMINUM WIRE, Type THHW/THHN installed in conduit
# 4/0
3
Conduit Galvanized Minimum size for Consumer service
entrance cable/conductors - Roof Riser Installation
2
4
Conduit PVC or Galvanized Minimum size for Consumer
service entrance cable/conductors if required
2
5
Cable or conduit clamp spaced 18 maximum
6
Watertight connector ( for cable )
7
Meter base -- must be supplied by the consumer and approved by the Company
8
Non-watertight connector ( for cable or conduit )
9
Main switch and fuse box -- as required
200 AMP
10
Continuous ground wire from main disconnect switch box to
ground rod
# 6
Bare Copper
11
Ground Rod : 5/8 x 8 copperclad or 5/8 x 8 galvanized steel
12
Ground rod clamp