Entrelec Switching Power Supplies

content.
Entrelec Switching Power Supplies Switching Power Supplies Selection Guide
DIN Rail Mount
Output Voltage
Output Current
Input Voltage
Spacing
Type
Page #
(mm)
5 V DC
3 A
90 - 260 V AC
45
PS 5 V DC / 3 A
642
105 - 260 V DC
6 V DC
3 A
90 - 260 V AC
45
PS 6 V DC / 3 A
642
105 - 260 V DC
12 V DC
2 A
90 -260 V AC
45
PS 12 V DC / 2 A
643
105 - 260 V DC
12 V DC
2 A
90 - 260 V AC
45
PS 12 V DC / 2 A
643
9-15 V DC
105 - 260 V DC
Adjustable
24 V DC
0.3 A
90 - 260 V AC
45
PS 24 V DC / 0.3 A
644
105 - 260 V DC
24 V DC
0.5 A
90 - 260 V AC
22.5
PS 24 V DC / 0.5 A
645
105 - 260 V DC
24 V DC
1 A
90 - 260 V AC
45
PS 24 V DC / 1 A
646
105 - 260 V DC
24 V DC
1.5 A
90 - 260 V AC
45
PS 24 V DC / 1.5 A
646
21 - 28 V DC
105 - 260 V DC
Adjustable
24 V DC
2 A
90 - 140 V AC
45
PS 24 V DC / 2 A
647
24 V DC
2 A
140 - 260 V AC
45
PS 24 V DC / 2 A
647
160 - 260 V DC
24 V DC
2 A
140 - 260 V AC
45
PS 24 V DC / 2 A
647
21- 28 V DC
160 - 260 V DC
Adjustable
24 V DC
4.2 A
90 - 260 V AC
90
PS 24 V DC / 4.2 A
648
127 - 260 V DC
24 V DC
5 A
90 - 260 V AC
90
PS 24 V DC / 5 A
649
127 - 260 V DC
24 V DC
5 A
90 - 260 V AC
90
PS 24 V DC / 5 A
649
23 - 28 V DC
127 - 260 V DC
Adjustable
24 V DC
10 A
93 - 132 V AC
100
PS TSL 24 V DC / 10 A
650
24 - 28 V DC
187 - 264 V AC
Adjustable
24 V DC
20 A
93 - 132 V AC
220
PS TSL 24 V DC / 20 A
651
24 - 28 V DC
187 - 264 V AC
Adjustable
48 V DC
0.7 A
90 - 260 V AC
45
PS 48 V DC / 0.7 A
652
105 - 260 V DC
Redundant
to 5 A max.
40 V DC max.
22.5
PSR
653
Power Supply
Switching Module
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com Linear Power Supplies Selection Guide
DIN Rail Mount
Output Voltage
Output Current
Input Voltage Spacing
Type
Page #
(mm)
5 V DC
1 A
115 V AC
78
PS-L 5 V DC / 1A 115 V AC
656
5 V DC
1 A
230 V AC
78
PS-L 5 V DC / 1A 230 V AC
656
12 V DC
0.5 A
115 V AC
78
PS-L 12 V DC / 0.5A 115 V AC
656
12 V DC
0.5 A
230 V AC
78
PS-L 12 V DC / 0.5A 230 V AC
656
12 V DC
1 A
115 V AC
90
PS-L 12 V DC / 1A 115 V AC
656
12 V DC
1 A
230 V AC
90
PS-L 12 V DC / 1A 230 V DC
656
15 V DC
0.5 A
115 V AC
78
PS-L 15 V DC / 0.5A 115 V AC
656
15 V DC
0.5 A
230 V AC
78
PS-L 15 V DC / 0.5A 230 V AC
656
15 V DC
1 A
115 V AC
90
PS-L 15 V DC / 1A 115 V AC
656
15 V DC
1 A
230 V AC
90
PS-L 15 V DC / 1A 230 V DC
656
24 V DC
0.25 A
115 V AC
78
PS-L 24 V DC / 0.25A 115 V AC
657
24 V DC
0.25 A
230 V AC
78
PS-L 24 V DC / 0.25A 230 V AC
657
24 V DC
0.75 A
115 V AC
90
PS-L 24 V DC / 0.75A 115 V AC
657
24 V DC
0.75 A
230 V AC
90
PS-L 24 V DC / 0.75A 230 V DC
657
±12 V DC
0.5 A
115 V AC
90
PS-L ± 12 V DC / 0.5A 115 V AC
657
±12 V DC
0.5 A
230 V AC
90
PS-L ± 12 V DC / 0.5A 230 V AC
657
±15 V DC
0.5 A
115 V AC
90
PS-L ± 15 V DC / 0.5A 115 V AC
657
±15 V DC
0.5 A
230 V AC
90
PS-L ± 15 V DC / 0.5A 230 V AC
657
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com 6 V DC / 3 A
Switching Power Supply
systron
®
PS
Approvals:
systron
®
PS 5 V DC / 3 A
2 423 418 30
Supply voltage
Marker
green LED:
ON: output
voltage OK.
+6 V DC
Common
GND
Power high
Neutral
Gr
ound
Supply voltage
Marker
green LED:
ON: output
voltage OK.
+5 V DC
Common
GND
Approvals:
Power supply systron
®
PS
P/N:
systron
®
PS 6 V DC / 3 A
2 423 418 40
Power supply systron
®
PS
P/N:
5 V DC / 3 A
The switching power supplies, systron
®
PS, offer many
advantages over conventional supplies:
DIN Rail mount compact modules
Low weight
High efficiency
Low heating
Wide range of supply voltage
Constant output voltage with good regulation
UL, CSA listed, EN 50178 (VDE 0160)
Short-circuit and overload proof
Fused input
Technical data
Power high
Neutral
Gr
ound
Input
Supply voltage
90...260 V AC
90...260 V AC
105...260 V DC
105...260 V DC
Frequency, AC input
47... 400 Hz
47... 400 Hz
Output load hold time
With input voltage drop out, min.10 ms at 100 % load
With input voltage drop out, min. 10 ms at 100 % load
Input current at nominal load
0.4 A (90 V AC) / 0.2 A (260 V AC)
0.5 A (90 V AC) / 0.25 A (260 V AC)
Inrush current 25° C ( 2 ms)
7.5 A
7.5 A
Internal input fuse
3.0 A (slow blow)
3.0 A (slow blow)
Output
Output voltage
5 V DC ± 3 %
6 V DC ± 3 %
Output current
3 A
3 A
Current derating at temperature > 45°C
- 25 mA/°C
- 25 mA/°C
Current derating at input voltage < 100 V AC
-
-
Residual ripple / noise
max. 50 mVpp
max. 50 mVpp
Deviation of output with input change
max. ± 0.5 %
max. ± 0.5 %
Deviation of output with static load change
max. ± 0.5 %
max. ± 0.5 %
Deviation of output with dynamic load change
max. 5 %
max. 5 %
Short circuit protection
overcurrent switch off with automatic restart
overcurrent switch off with automatic restart
Overload protection
overtemperature and overcurrent switch off
overtemperature and overcurrent switch off
Reset after thermal overload
disconnection of AC power input min. 30 s
disconnection of AC power input min. 30 s
Norms, tests
Electrical safety standards
EN 50178 (VDE 0160) / UL 508 / CSA 22.2
EN 50178 (VDE 0160) / UL 508 / CSA 22.2
Galvanic isolation
reliable isolation acc. to IEC 664-1, DIN VDE 0106-101
reliable
isolation acc. to IEC 664-1, DIN VDE 0106-101
Voltage withstand input <-> output
2.5 kV AC, 3 kV AC type test
2.5 kV AC, 3 kV AC type test
Clearance and creepage distances
overvoltage category 2, pollution degree 2
overvoltage category 2, pollution degree 2
Electromagnetic immunity (EM) acc. to EN 50082-2:
ESD:
EN 61000-4-2 level 3
6/8 kV
ESD:
EN 61000-4-2 level 3
6/8 kV
RF field:
EN 61000-4-4 level 3
10 V/m
RF field:
EN 61000-4-4 level 3
10 V/m
Burst:
EN 61000-4-5 level 4
4 kV
Burst:
EN 61000-4-5 level 4
4 kV
Surge:
EN 61000-4-5 level 3
3 kV
Surge:
EN 61000-4-5 level 3
3 kV
conducted RF:
EN 61000-4-6 level 3
10 V
conducted RF:
EN 61000-4-6 level 3
10 V
Electromagnetic compatibility (EMC) acc. EN 50081-2
radiated noise EN 55011, class B
radiated noise EN 55011, class B
Input current harmonics
no limitation
no limitation
Protection against contact
Terminals
IP 20
IP 20
Housing
IP 50
IP 30
Protection class
1
1
General characteristics
Efficiency
approx. 81 %
approx. 85 %
Status indication
green LED, power OK
green LED, power OK
Operating temperature
... +55°C
0° ... +55°C
Storage temperature
-25° ... +75°C
-25° ... +75°C
Terminals
screw terminals, 2 x 14 AWG (2.5 mm
2
)
screw terminals, 2 x 14 AWG (2.5 mm
2
)
Weight
approx. 0.22 kg (0.49 Ib)
approx. 0.22 kg (0.49 Ib)
Dimensions (W x H x D)
1.77 x 3.07 x 3.94" (45 x 78 x 100 mm)
1.77 x 3.07 x 3.94" (45 x 78 x 100 mm)
Mounting hints
Normal position: horizontal onto DIN rail. Spacing to other
Normal position: horizontal onto DIN rail. Spacing to other
modules: left side min. 1 cm, vertical distances min. 5 cm
modules: left side min. 1 cm, vertical distances min. 5 cm
Class I & II, Div. 2
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com 12 V DC / 2 A
Switching Power Supply
systron
®
PS
Approvals:
systron
®
PS 12 V DC / 2 A
2 423 418 10
Supply voltage
Marker
green LED:
ON: output
voltage OK.
+12V DC
Common
GND
Power high
Neutral
Gr
ound
Supply voltage
Marker
green LED:
ON: output
voltage OK.
+12 V DC
Common
GND
Power supply systron
®
PS
P/N:
systron
®
PS 12 V DC / 2 A
2 423 418 11
Power supply systron
®
PS
P/N:
12 V DC / 2 A
The switching power supplies, systron
®
PS, offer many
advantages over conventional supplies:
DIN Rail mount compact modules
Low weight
High efficiency
Low heating
Wide range of supply voltage
Constant output voltage with good regulation
UL, CSA listed, EN 50178 (VDE 0160)
Short-circuit and overload proof
Fused input
Adjustable output voltage
Technical data
Power high
Neutral
Gr
ound
Input
Supply voltage
90...260 V AC
90...260 V AC
105...260 V DC
105...260 V DC
Frequency, AC input
47... 400 Hz
47... 400 Hz
Output load hold time
With input voltage drop out, min. 10 ms at 100 % load
With input voltage drop out, min.10 ms at 100 % load
Input current at nominal load
0.6 A (90 V AC) / 0.27 A (260 V AC)
0.7 A (90 V AC) / 0.3 A (260 V AC)
Inrush current 25° C ( 2 ms)
7.5 A
33 A
Internal input fuse
3.0 A (slow blow)
3.0 A (slow blow)
Output
Output voltage
12 V DC ± 3 %
12 V DC ± 3 % (9...15 V DC adjustable with pot. max. 36 W)
Output current
2 A
2 A / 48 W
Current derating at temperature > 45°C
- 20 mA / °C
- 0.3 W / °C
Current derating at input voltage < 100 V AC
- 20 mA / V
-
Residual ripple / noise
max. 300 mVpp
max. 200 mVpp
Deviation of output with input change
max. ± 0.1 %
max. ± 0.5 %
Deviation of output with static load change
max. ± 0.5 %
max. ± 0.5 %
Deviation of output with dynamic load change
max. 5 %
max. 5 %
Short circuit protection
overcurrent switch off with automatic restart
overcurrent switch off with automatic restart
Overload protection
overtemperature and overcurrent switch off
overtemperature and overcurrent switch off
Reset after thermal overload
disconnection of AC power input min. 30 s
disconnection of AC power input min. 30 s
Norms, tests
Electrical safety standards
EN 50178 (VDE 0160) / UL 508 / CSA 22.2
EN 50178 (VDE 0160) / UL 508 / CSA 22.2
Galvanic isolation
reliable isolation acc. to IEC 664-1, DIN VDE 0106-101
reliable
isolation acc. to IEC 664-1, DIN VDE 0106-101
Voltage withstand input <-> output
2.5 kV AC, 3 kV AC type test
2.5 kV AC, 3 kV AC type test
Clearance and creepage distances
overvoltage category 2, pollution degree 2
overvoltage category 2, pollution degree 2
Electromagnetic immunity (EM) acc. to EN 50082-2:
ESD:
EN 61000-4-2 level 3
6/8 kV
ESD:
EN 61000-4-2 level 3
6/8 kV
RF field:
EN 61000-4-4 level 3
10 V/m
RF field:
EN 61000-4-4 level 3
10 V/m
Burst:
EN 61