POWER MONITORING
INSTALLATION GUIDE
Z204062-0E
page 1
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
06081
H8186-CB
Installer's Specifications
Energy Meter Communications Board
Output Type
BACnet
Connection
2-wire or 4-wire, selectable
Baud Rate
9600, 19200, 38400
Parity
None/Odd/Even, Selectable
Address Range
1-63
Dimensions
2 (51mm) x 6 (152mm)
Data Output:
kWh, Consumption
kW, Real power
kVAR, Reactive power
kVA, Apparent power
Power factor
Voltage, line to line
Voltage, line to neutral
Amps, Average current
kW, Real power ØA
kW, Real power ØB
kW, Real power ØC
Power factor ØA
Power factor ØB
Power factor ØC
Voltage, ØA to ØB
Voltage, ØB to ØC
Voltage, ØA to ØC
Voltage, ØA to Neutral
Voltage, ØB to Neutral
Voltage, ØC to Neutral
Amps, Current ØA
Amps, Current ØB
Amps, Current ØC
quick install
1. Turn off all power to the energy meter and the equipment in which it is installed.
2. Discharge static.
3. Slide the H8186-CB into the channels on either side of the energy meter until the
male connection on the meter clicks into place.
4. Insert the communication terminal onto the RS-485 communication terminals.
5. If the demand subinterval feature is used, wire it into the end of the demand
subinterval terminal.
6. Replace the voltage terminal into the energy meter.
H81xxCB Series interfaces are sold as open devices.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
MODEL
DESCRIPTION
H8163-CB
Modbus® Communications Board for H8100 Series
H8186-CB
BACnet® Communications Board for H8100 Series
H8126-CB
Metasys® N2 Communications Board for H8100 Series
Product identification
H8186-CB
INSTALLATION GUIDE
Z204062-0E
page 2
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
06081
H8186-CB Energy Meter Communication Board is an optional field-installable board
for the H8163 Energy Meter that provides a simple, cost-effective way to network the
H8163 Energy Meter to an existing control/data acquisition systems via BACnet-
MS/TP communications capability. The H8186-CB is designed as a plug-and-play
accessory for the H8163 energy meter.
The H8186-CB features field selectable parity (odd/even/none). It works with 2-wire
and 4-wire systems, and it has a field selectable baud rate (9600, 19200, 38400).
oPeration
configuration
Product diagram
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
1
2
TX
RX
3
RX
4
TX
5
6
7
8
9
ALIVE
LITHIUM BATTERY
1.
RS-485 LED (TX):
Red LED; blinks to indicate that the H8186-CB is transmitting
data to the master.
2.
RS-485 LED (RX):
Red LED; blinks to indicate that the H8186-CB is receiving data
from the master.
3.
LED from Main Board (RX):
Green LED; blinks to indicate that the H8186-CB is
receiving data from the main board.
4.
LED from Main Board (TX):
Green LED; blinks to indicate that the H8186-CB is
transmitting data to the main board.
5.
ALIVE LED:
Green LED; should blink once per second to indicate normal
operation of the H8186-CB.
6.
Network Address DIP Switches:
Use these DIP switches to set the network
address for the H8186-CB.
7.
Connection to Energy Meter:
Install the H8186-CB in the energy meter by
inserting this connector into the connection slot at the top of the energy meter.
8.
Communication DIP Switches:
Use these DIP switches to set the H8186-CB
wiring type, baud rate, and parity.
9.
RS-485 Communication Terminals:
Insert the RS-485 connector into these
terminals. See the Wiring Diagram section of this guide for instructions on wiring
the connector for 2-wire or 4-wire communications.
CAUTION! Danger of Explosion if battery is incorrectly
replaced. Replace only with the same or equivalent type
recommended by the manufacturer. Dispose of used
batteries according to the manufacturers instructions.
This section describes the communications settings you must make to the H8186-CB.
When daisy-chaining devices, follow these guidelines:
You can connect up to 63 H8186-CB devices on a single daisy chain.
Each H8186-CB device on the daisy chain must have a unique address.
Before connecting the H8186-CB to the RS-485 communication wires,
set the address according to directions in Selecting the Network Address
DIP Switches on this page. If you assign the same address to two devices,
neither device will communicate.
Set the wiring type, baud rate, and parity according to directions in
Selecting Wiring Type, Baud Rate, and ParityCommunication DIP
Switches on this page. The settings for each H8186-CB must match the
other devices on its daisy chain.
For RS-485 cables, use shielded, twisted-pair wire (Belden Cable 1120A or
equivalent).
Terminate the last device on the daisy chain. If the H8186-CB is the last
device, per the RS-485 standard (120 ohm nominal impedence).
Selecting The Network Address DIP Switches
Use the Network Address DIP switches to select the network address. Each H8186-CB
on a daisy chain must have a unique network address (from 063). Devices with the
same address will be unable to communicate.
Always set the address before you install the H8186-CB in the energy meter and
before you connect the energy meter to the daisy chain.
Each of the six DIP switches has a unique address value, page 8 lists DIP switch posi-
tions for specific addresses.
Network Address DIP Switch Values
Switch
Value
1
1
2
2
3
4
4
8
5
16
6
32
8 + 32 = 40
In this example, the network address for the
device is 40. Switch 4 and 6 offer the only
combination of values that total 40.
This figure illustrates how to set the
switches. Up is ON; down is OFF.
H8186-CB
INSTALLATION GUIDE
Z204062-0E
page 3
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
06081
Selecting Wiring Type, Baud Rate, and Parity Communication DIP Switches
Use the communication DIP switches (pictured below) to set the H8186-CB wiring
type, baud rate, and parity.
The figures below list the baud rate and parity switch settings and the locations of
the switches that control wiring, baud rate, and parity.
Wiring, Baud Rate, and Parity Settings
Parameter
1
2
ON
OFF
3
OFF
ON
OFF
ON
4
OFF
OFF
ON
ON
5
OFF
ON
ON
6
OFF
OFF
ON
2-wire
4-wire
9600
19200
38400
38400
None
Even
Odd
Wire
Type
Baud
Rate
Parity
Switch Number and Setting
Switch 1 is unused. Always leave it in the OFF
position.
This example illustrates the default switch settings
for a 2-wire device that uses 9600 baud rate no
parity.
Wiring Baud
Parity
Daisy Chain Maximum Distances
The maximum number of devices capable of being supported on a single daisy chain
is determined based on the combination of baud rate, the length of the daisy chain,
and the types of RS-485 devices (2-wire/4-wire) on the daisy chain. The RS-485
interface will support daisy chains that fall within the specifications shown below.
Baud Rate
Maximum Distances
1-16 Devices
17-32 Devices
9600
10000 ft. (3048 m)
4000 ft. (1219 m)
19200
5000 ft. (1,524 m)
2500 ft. (762 m)
38400
2500 ft. (762 m)
1200 ft. (380 m)
Baud Rate
Maximum Distances
1-8 Devices
9-16 Devices
9600
10000 ft. (3048 m)
4000 ft. (1219 m)
19200
5000 ft. (1,524 m)
2500 ft. (762 m)
38400
2500 ft. (762 m)
1200 ft. (380 m)
2-Wire Daisy Chain Maximum Distances
Wiring the Connector
Remove the connector from the RS-485 communication terminals of the H8186-CB
(see Wiring Diagram section). To wire RS-485 communications, follow these steps:
1. Wire the communications connector for either 2-wire communication or 4-wire
communication (see Wiring Diagram section).
NOTE: The Wire Type setting in the communication DIP switch must match this
wiring type (see settings diagram, previous section, for communication DIP switch
settings).
2. Use a small, flat-blade screwdriver to tighten the connector screws.
3. Replace the connector on the RS-485 communication terminals of the H8186-CB.
4. If the H8186-CB is the last device on the daisy chain, terminate it, to ensure
reliable communication per the RS-485 standard (120 nominal impedence).
rs-485 communications
4-Wire Daisy Chain Maximum Distances
H8186-CB
INSTALLATION GUIDE
Z204062-0E
page 4
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
06081
wiring diagram
TX+
SHLD
TX+
RX+
TX
RX
TX
SHIELD
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
TX
RX
RX
ALIVE
SHLD
TX-/RX-
TX+/RX+ TX-
TX+
TX+
SHLD
TX+
RX+
TX
RX
TX
MASTER
SLAVE
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
TX
RX
RX
ALIVE
SHLD
TX-/RX-
TX+/RX+ TX-
TX+
TX+
SHLD
TX+
RX+
TX
RX
TX
TX+
SHLD
RX+
RX
TX
TX+
SHLD
TX+
RX+
TX
RX
TX
SHIELD
RX-
RX+
TX-
TX+
MASTER
SLAVE
SLAVE
2-wire Communications Wiring
4-wire Communications Wiring
Detail showing Communications connector
wired for 2-wire communication.
Detail showing Communications
connector wired for 4-wire
communication.
Figure 6
Figure 7
H8186-CB
INSTALLATION GUIDE
Z204062-0E
page 5
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.co