Current Supply Units

age or responsible for its content.
Current Supply Units
GE Energy
CSU600A
CSU600AT Current Supply Units
Programma® Products CS
U
6
0
0
A
/
6
0
0
A
T
CSU600A /600AT Current Supply Units
These high-current supply units have two main elds of application. The rst is to conduct primary tests on
protective relays. A primary test shows whether all parts of the protection system are functioning together properly
within the speci ed time limits under operating conditions.
The second eld of application involves conducting current tests on low-voltage circuit breakers and overcurrent
devices.
The CSU600A is a compact instrument which, together with Timer TM200 and an external ammeter, meets
stringent requirements for accuracy, easy handling and performance. This current supply unit is ideal for a)
performance and turn-ratio tests of current transformers, b) primary tests of protective relays, c) current tests on
low- and high-voltage circuit breakers and d) commissioning tests that require variable currents.
The more sophisticated CSU600AT provides a more comprehensive solution. It has a built-in timer and an analog
ammeter that provide rough current settings quickly and easily. As a result, connection time has been reduced to the
bare minimum.
The CSU600A and CSU600AT current supply units have an excellent weight/performance ratio. CS
U
6
0
0
A
/
6
0
0
A
T
Optional accessories
Cable set (for 115 V), 2 x 5 m (16 ft), 70 mm
2
Weight: 8.4 kg (18 lbs)
Cable set, 2 x 10 m (33 ft), 70 mm
2
Weight: 16.8 kg (37 lbs)
Cable set, 2 x 15 m (49 ft), 95 mm
2
Weight: 29.4 kg (65 lbs)
TM200
External timer
See the TM200 product pages for more information
b
a
Application example
IMPORTANT!
Read the Users manual before using the instrument.
Primary test of protective relay equipment and low-voltage
circuit breaker
1. Connect the CSU600A's current outputs across the current

transformer (diagram a) or to the breaker terminals (diagram b).
2. Connect Timer TM200's start input to output T and the stop input

to the protective relay equipment's auxiliary contact.
3. Set the current.
4. Execute the test.
5. Read the time from Timer TM200.
Ammeter
Timer TM2
Timer TM2 CS
U
6
0
0
A
/
6
0
0
A
T
Speci cations CSU600A/AT
Speci cations are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Speci cations are subject to change
without notice.
Environment
Application eld
The instrument is intended for use in
high-voltage substations and indus-
trial environments.
Temperature
Operating
0°C to +50°C (32°F to +122°F)
Storage & trans-
port
-40°C to +70°C (-40°F to +158°F)
Humidity
5% 95% RH, non-condensing
CE-marking
LVD
Low Voltage Directive 73/23/ EEC am.
by 93/68/EEC
EMC
EMC Directive 89/336/EEC am. by
91/263/EEC, 92/31/EEC and 93/68/EEC
General
Mains voltage
115 or 230 V AC, 50 / 60 Hz
Power consumption
(max)
115 V, 667 VA cont. (interm. 3738 VA)
230 V, 851 VA cont. (interm. 6440 VA)
Protection
Thermal cut-outs and miniature
circuit breakers
Dimensions
Instrument
356 x 203 x 241 mm
(14.0 x 8.0 x 9.5)
Transport case
610 x 290 x 360 mm
(24.0 x 11.4 x 14.2)
Weight
21.9 kg (48 lbs)
38.3 kg (84.4 lbs) with accessories and
carrying case
Current cables
2 x 5 m (16 ft), 50 mm²
Measurement section
Ammeter
Built-in, 0 600 A (only on CSU600AT)
Output for external ammeter
Current transformer
500/5 A, class 0.5
Timer (only CSU600AT)
Range
0-999.999 s
Resolution
1 ms
Inaccuracy
±0.02% of shown value + 0 to 2 ms
Other
Output for starting external timer
Outputs, AC, intermittent output
1)
(CAT I)
115 V mains voltage
230 V mains voltage
Current
Load time
Minimum
output
voltage
Load time
Minimum
output
voltage
0 A
Cont.
6.0 V
Cont.
9.5 V
75 A
Cont.
9.3 V
100 A
Cont
5.6 V
1 h
9.0 V
200 A
15 min
5.3 V
5 min
8.5 V
300 A
1.5 min
4.9 V
2 min
8.0 V
400 A
1 min
4.6 V
1 min
7.5 V
500 A
20 s
4.2 V
30 s
7.0 V
600 A
15 s
3.9 V
20 s
6.5 V
1) Maximum load time from cold state 25°C (77°F). Not valid for repeated tests.
Maximum cable lengths at 600 A
115 V mains
2 x 5 m (16 ft), 70 mm²
230 V mains
2 x 5 m (16 ft), 50 mm²
2 x 10 m (33 ft), 70 mm²
2 x 15 m (49 ft), 95 mm² CS
U
6
0
0
A
/
6
0
0
A
T
Ordering information
CSU600A
Art.No.
Complete with:
Cable set GA-05052
Transport case GD-00182
115 V Mains voltage
BF-11190
230 V Mains voltage
BF-12290
CSU600AT
Complete with:
Cable set GA-05052
Transport case GD-00182
115 V Mains voltage
BF-21190
230 V Mains voltage
BF-22290
Optional accessories
Cable set 5 m (for 115 V)
GA-07052
Cable set 10 m
GA-07102
Cable set 15 m
GA-09152
TM200
BE-29090
Cable set GA-05052 NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS
© 2005, Programma Electric AB. All rights reserved.
The contents of this document are the property of Programma
Electric AB. No part of this work may be reproduced or transmitted
in any form or by any means, except as permitted in written
license agreement with Programma Electric AB.
Programma Electric AB has made every reasonable attempt
to ensure the completeness and accuracy of this document.
However, the information contained in this document is subject to
change without notice, and does not represent a commitment on
the part of Programma Electric AB.
TRADEMARK NOTICES
Programma® is a registered trademark of Programma Electric
AB. IEEE® is claimed as a registered trademark by the Institute
by Electrical Electronics Engineers, Inc. The GE logo is registered
trademark of General Electric Company.
All other brand and product names mentioned in this document
are trademarks or registered trademarks of their respective
companies.
Programma Electric AB is certied according to ISO 9001.
Programma Electric AB
Eldarvägen 4
SE-187 75 TÄBY
Sweden
Tel
+46 8 510 195 00
Fax
+46 8 510 195 95
E-mail programma@ge.com
Internet www.gepower.com
Subject to change without notice. Extract from catalog Electrical Test Equipment Art. No. ZG-9906E R100 GEA 13466A ENG