DLP-37A and DLP-37A1 with DLM4
strumentation, Telecom and Telco equipment
1.0
GENERAL
1.1
DESCRIPTION
These specifications describe the electrical and mechanical requirements for a rapid- responding
transient voltage surge suppressor. The specified surge protective device shall provide effective
high-energy surge diversion of transient over-voltages on Instrumentation, Telecom and Telco
conductors, up to 14 pairs. Tested & certified per UL 497. The specified surge protective device
shall provide:
10,000A (8/20us) surge current/line, ratings must be independently tested & verified.
Series resistance of each circuit not greater than 2.4 ohms.
All signal lines protected with respect to chassis ground.
DLP-37A wires must be terminated to 6/32 screw terminals (provided).
DLP-37A1 wires must be terminated to 66 punch -down type (provided).
TWENTY YEAR WARRANTY. Replacement units are sent from factory, located in Deer
Park, New York, USA.
1.2
STANDARDS
The specified suppressor shall be designed, manufactured, tested and installed in compliance with:
Institute of Electrical and Electronic Engineers IEEE-472
Federal Communications Commission Docket 68
Bellcore standards 974 and 1089
National Fire Protection Association (NFPA 20, 70, 75 and 78)
Underwriters Laboratories (UL-497A and 497B ) listed
CAN/C22.2 No. 8-M1986; CSA Electrical Certification Notice No. 516
1.3
PROTECTED EQUIPMENT ELECTRICAL REQUIREMENTS
1.3.1 Environmental Requirements
A.
Operating Requirements:
1.
Operating temperature range shall be -40 to +71 degrees C (-40 to +160 degrees F).
2.
Storage temperature range shall be -40 to +85 degrees C.
3.
Operation shall be reliable in an environment with 0% to 95% non-condensing relative
humidity.
4.
The system shall be capable of operation up to an altitude of 13,000 feet above sea level.
1.3.2
Electrical Requirements
A.
Electrical Requirements:
1.
Preferred method of ground connection is protector to protected device, 6 or less.
2.
Clamp voltages available shall be 6,25,60 and 200 Volts and the attenuation less than 1
db @ 70 MHz.
12 Burt Drive Deer Park, NY 11729 USA
1-800-851-1508
MCG Surge Protection
2
9/11/2007
3.
The transient suppression capability shall be bi-directional and suppress both positive
and negative impulses.
4.
The suppressor shall be designed so as to minimize the internal surge path impedance.
Direct point-to-point internal wiring is inherently inductive and not acceptable.
Connection to the protected device shall be constructed as shown in the installation notes
for best performance.
5.
Equipment shall be as manufactured by MCG Surge Protection; Model: DLP-37A and
DLP-37A1 with required protection cards: DLM4 or engineering department approved
equal with supporting data.
2.0
MODEM, FACSIMILE, TELCO PROTECTION SYSTEM
A.
Protection Cards (DLM4): The protection circuits shall be provided on plug-in, pluck out
cards, (4 circuits/card). Maximum 7 cards per unit Each circuit shall be protected by a high-
speed avalanche diode and a gas discharge tube. Protector will be made available, with no
additional cost to user, UL 497A (fused for accidental crossing of power and signal lines) or
UL 497B (no fuse). Care should be taken to adhere to installation notes supplied with
protector for optimum protection.
B. Enclosure: No enclosure. Unit offered with base PC board to accommodate 7 DLM cards.
C. Dimensions: Base PC board, DLP-3.7A 4.8x 7.0x 0.5
. Base PC board, DLP-3.7A1 4.8x7.0x 1.7
DLM4, 2.52 x 2.29
3.0
INSTALLATION AND MAINTENANCE
A. The unit shall be installed in accordance with the manufacturer's printed instruction to maintain
warranty. All local and national codes must be observed.
B. Units shall be installed as close as possible to the device to which it is connected
C. Detailed installation/maintenance notes shall be provided to insure safety of maintenance
personnel.
D. Repair time should not exceed 5 minutes.
4.0
20 YEAR WARRANTY
Manufacturer to provide 20-year warranty to cover repair or replacement with a new device.
Manufacturer to provide no cost replacement of DLP-37A and DLP-37A1. Restrictions apply.
See Warranty & Limitations of Liability, document part No. 299-200-06.
12 Burt Drive Deer Park, NY 11729 USA
1-800-851-1508