Your North and Central Florida Caterpillar Dealer
>Help for Webmasters
« back to results for ""
Below is a cache of http://www.ringpower.com/Documents/PeakingPower/CaterpillarDieselEngines.pdf. It's a snapshot of the page taken as our search engine crawled the Web.
The web site itself may have changed. You can check the current page or check for previous versions at the Internet Archive.
Yahoo! is not affiliated with the authors of this page or responsible for its content.
Your North and Central Florida Caterpillar Dealer
Your North and Central Florida Caterpillar Dealer
JACKSONVILLE
TALLAHASSEE
OCALA
ORLANDO
TAMPA
8040 Philips Hwy
4752 Capital Circle NW
6202 N US 301/441
9901 Ringhaver Dr.
9797 Gibsonton Dr
Jacksonville, FL 32256
Tallahassee, FL 32303
Ocala, FL 34475
Orlando, FL 32824
Riverview, FL 33569
904-737-7730
850-562-1622
352-732-4600
407-855-6195
813-671-3700
SALES
SERVICE
PARTS
LEASING
RENTALS
QUOTATION / SALES AGREEMENT / SECURITY AGREEMENT
Quotation Accepted By: ______________________________Date: ___________Tax No.: ________________________________
Customer: __________________________________Salesman's Signature: ______________________________
Keith R. Moore, EPG Sales Manager - North Florida
TERMS
This offer to sell is made subject to buyers acceptance within ten (10) days from this date (noted above).
All quoted prices are subject to change without notice. Those in effect on the date of shipment shall prevail.
Subject to credit approval.
Used equipment is subject to prior sale.
A 25% restocking fee will be assessed for all canceled orders or returned materials.
No retainage to be withheld. Ring Power Systems is an equipment supplier and is not a sub-contractor. Our terms are Net 10 days.
No sales tax is included.
Buyer grants to seller a security interest in all equipment as described in this agreement until such time as payment is made in full
in accordance with the terms and conditions of this agreement and in accord with the sellers credit application.
Quote No.
03KM090102
Page 1 of 6
DATE: 5/20/2004
QUOTATION NO: 03KM090102
CUSTOMER NAME: INFORMATION ONLY
ADDRESS: TBD
CITY/STATE/ZIP: TBD, FL
PHONE:
SHIPPING LEAD TIME: TBD
SHIPPING VIA/FOB: RING POWER
SUBMITTAL LEAD TIME: TBD
JOBSITE ADDRESS: TBD
CITY/STATE/ZIP: TBD FL
PROJECT NAME: POWER PLANTS
TERMS: Full payment is due from buyer within 10 days of delivery or pickup of the equipment.
DESCRIPTION OF MATERIAL
UNIT PRICE
EXTENSION
CATERPILLAR DIESEL FUELED ENGINES:
TWELVE NEW CATERPILLAR MODEL 3516B DIESEL FUELED GENERATORS
RATED 2000 kW, CONTINUOUS DUTY, 12,470 VAC, 3 PHASE, 60 HZ EQUIPPED
FOR HEAT EXCHANGER COOLING WITH STANDARD ATTACHMENTS AND
INCLUDING ADDITIONAL ITEMS AS DETAILED BELOW:
CATERPILLAR SR4B ALTERNATOR, 2/3 PITCH, PERMANENT MAGNET
EXCITATION, 105 DEG C RISE, TWO BEARING, SIX LEAD, 3 PHASE SENSING,
PLATINUM STATOR RTDS, CLASS H INSULATION, DIGITAL VOLTAGE
REGULATOR, BUS BAR TERMINATIONS, EXTENSION BOX, WINDING
TEMPERATURE DETECTORS, ANTI-CONDENSATION HEATERS
CATERPILLAR LOAD SHARING ELECTRONIC GOVERNOR, ADEM III TYPE,
INSTALLED
CATEREPILLAR EMCP II + CONTROL PANEL, INSTALLED
SPRING TYPE VIBRATION ISOLATORS, SHIPPED LOOSE
DESCRIPTION OF MATERIAL
UNIT PRICE
EXTENSION
03KM090102
Page 2 of 6
RESIDENTIAL GRADE SILENCERS, FLEXIBLE CONNECTOR AND RAIN CAP,
SHIPPED LOOSE
HEAVY DUTY BATTERIES, LEAD ACID TYPE, WITH RACK AND CABLES,
SHIPPED LOOSE
BATTERY CHARGING ALTERNATORS, 45 AMP, INSTALLED
HEAVY DUTY DUAL 24 VDC STARTERS, INSTALLED
BATTERY CHARGERS, 2 RATE, 20 AMP WITH ALARMS, SHIPPED LOOSE
JACKET WATER HEATERS, 12,000 WATTS, 480 VAC/3 PHASE WITH
ISOLATION VALVES
LUBE OIL, FILTERS, DRAIN VALVE AND DIP STICK, INSTALLED
250 GALLON FUEL DAY TANKS, DOUBLE WALL CONSTRUCTION WITH
DUPLEX PUMP SYSTEM, CONTROL PANEL, SHIPPED LOOSE
CRANKCASE VENTLATION SYSTEM, TO VENT TO ATMOSPHERE, SHIPPED
LOOSE
RACOR FUEL WATER SEPERATORS, DUPLEX TYPE WITH STANDS, SHIPPED
LOOSE
HEAT EXCHANGERS FOR JW AND AC CIRCUITS, CIRCULATION PUMPS AND
MOTORS, SHIPPED LOOSE
HIGH VOLTAGE GENERATOR CONTROL SWITCHGEAR:
ONE UTILITY/GENERATOR PARALLELING 12.47KV SWITCHGEAR
LINEUP, NEMA 1* FOR INDOOR USE. THE SWITCHGEAR LINEUP WILL
CONSIST OF ONE (1) UTILITY MAIN CIRCUIT BREAKER SECTION,
TWELVE (12) GENERATOR CIRCUIT BREAKER SECTIONS AND TWO (2)
MASTER CONTROL SECTIONS. THE SWITCHGEAR LINEUP SHALL BE
PROVIDED AS FOLLOWS:
UTILITY MAIN CIRCUIT BREAKER SECTIONS:
ONE (1) UTILITY MAIN CIRCUIT BREAKER SECTION WITH THE
FOLLOWING FEATURES:
1 -
2000A DRAW OUT, 3 POLE, ELECTRICALLY OPERATED,
VACUUM CIRCUIT BREAKER WITH 500MVA INTERRUPTING
CAPACITY AT 12.47KVAC.
LOT -
2000A COPPER MAIN BUS, 3 PHASE, 3 WIRE, FOR USE IN A
12.47KV SYSTEM, NEMA1* ENCLOSURE
1 -
SET VOLTAGE TRANSFORMERS, DRAW-OUT, 12.47KVAC
PRIMARY, 120VAC SECONDARY WITH PRIMARY AND
SECONDARY FUSE PROTECTION, TWO (2) PROVIDED
1 -
SET OF THREE (3) CURRENT TRANSFORMERS, 5 AMPERE
SECONDARIES WIRED TO SHORTING TERMINAL STRIPS
1 -
UTILITY MANAGEMENT SEL 351 MULTI-FUNCTION DEVICE,
MICROPROCESSOR BASED, FIELD PROGRAMMABLE, DRAW-
OUT DESIGN WITH PROTECTION, METERING AND MONITORING
FUNCTIONS. RELAY WILL BE PROGRAMMED TO AFFORD THE
FOLLOWING FUNCTIONS FOR UTILITY PROTECTION:
OVERCURRENT AND INSTANTANEOUS TRIP (PHASE AND
GROUND; VOLTAGE RESTRAINED ON PHASE CURRENT)
VOLTAGE NEGATIVE SEQUENCE
OVER AND UNDER VOLTAGE
OVER AND UNDER FREQUENCY
DIRECTIONAL
OVERCURRENT
25 SYNC CHECK WITH DEAD BUS
DESCRIPTION OF MATERIAL
UNIT PRICE
EXTENSION
03KM090102
Page 3 of 6
1 -
ANSI DEVICE 86, HIGH SPEED, MANUALLY RESETTABLE,
OPERATED BY PROTECTIVE RELAYS, CAUSES TRIPPING OF
THE CIRCUIT BREAKER AND PREVENTS RECLOSING OF THE
CIRCUIT BREAKER FOR UTILITY PARALLEL OPERATION UNTIL
RESET
1 -
REDUNDANT ANSI DEVICE 86 SAME AS ABOVE
1 -
CIRCUIT BREAKER SWITCH, HEAVY DUTY, THREE (3) POSITION
SPRING RETURN TO CENTER WITH MOMENTARY TRIP AND
CLOSE POSITIONS. INCLUDES CIRCUIT BREAKER POSITION
INDICATING LAMPS
1 -
POWERLYNX® MAIN PLC CONTROLS AND METERING
TRANSDUCER
1 -
SPACE HEATER
* DRIP-PROOF ROOF AND GASKETED DOORS ARE INCLUDED ON THE
MAIN CIRCUIT BREAKER
SECTION.
GENERATOR CIRCUIT BREAKER SECTIONS:
TWELVE (12) GENERATOR CIRCUIT BREAKER SECTIONS WITH THE
FOLLOWING FEATURES:
1 -
1200A DRAW OUT, 3 POLE, ELECTRICALLY OPERATED, VACUUM
CIRCUIT BREAKER WITH 500MVA INTERRUPTING CAPACITY AT
12.47KVAC
LOT -
2000A COPPER MAIN BUS, 3 PHASE, 3 WIRE, FOR USE IN A
12.47KV SYSTEM, NEMA1* ENCLOSURE
1 -
SET VOLTAGE TRANSFORMERS, DRAW-OUT, 12.47KVAC
PRIMARY, 120VAC SECONDARY WITH PRIMARY AND
SECONDARY FUSE PROTECTION, TWO (2) PROVIDED
2 -
SETS OF THREE (3) CURRENT TRANSFORMERS, 5 AMPERE
SECONDARIES WIRED TO
SHORTING TERMINAL STRIPS. ONE SET SHIPPED LOOSE FOR
GENERATOR INSTALLATION
1 -
GENERATOR MANAGEMENT SEL 300G MULTI-FUNCTION
DEVICE, MICROPROCESSOR BASED, FIELD PROGRAMMABLE,
DRAW-OUT DESIGN WITH PROTECTION, METERING AND
MONITORING FUNCTIONS. RELAY WILL BE PROGRAMMED TO
AFFORD THE FOLLOWING FUNCTIONS FOR GENERATOR
PROTECTION:
o
OVERCURRENT AND INSTANTANEOUS TRIP (PHASE AND
GROUND; VOLTAGE RESTRAINED ON PHASE CURRENT)
o
OVER AND UNDER VOLTAGE
o
OVER AND UNDER FREQUENCY
o
REVERSE
POWER
o
LOSS
OF
FIELD
o
NEGATIVE SEQUENCE CURRENT
o
VOLTAGE PHASE REVERSAL
o
GENERATOR DIFFERENTIAL OVERCURRENT
o
LOCKOUT
o
BEARING & STATOR TEMPERATURE
DESCRIPTION OF MATERIAL
UNIT PRICE
EXTENSION
03KM090102
Page 4 of 6
o
RS485/232
COMMUNICATION
1 - ANSI DEVICE 86, HIGH SPEED, MANUALLY RESETTABLE, OPERATED
BY PROTECTIVE RELAYS, CAUSES TRIPPING OF THE CIRCUIT
BREAKER AND PREVENTS RECLOSING OF THE CIRCUIT BREAKER
FOR UTILITY PARALLEL OPERATION UNTIL RESET
1 - REDUNDANT ANSI DEVICE 86 SAME AS ABOVE
1 - CIRCUIT BREAKER SWITCH, HEAVY DUTY, THREE (3) POSITION
SPRING RETURN TO CENTER WITH MOMENTARY TRIP AND CLOSE
POSITIONS. INCLUDES CIRCUIT BREAKER POSITION INDICATING
LAMPS
1 - VOLTAGE AND SPEED POTENTIOMETERS, 10 TURN, WITH LOCKING
DIAL
1 - POWERLYNX® GENERATOR PLC CONTROLS AND METERING
TRANSDUCERS
1 - SPACE HEATER
* DRIP PROOF ROOF AND GASKETED DOORS ARE INCLUDED ON
EACH GENERATOR CIRCUIT
BREAKER SECTION.
TWO (2) MASTER CONTROL SECTIONS WITH THE FOLLOWING FEATURES:
1- POWERLYNX® 15 COLOR TOUCH SCREEN
1 -SYSTEM GRAPHIC ONE LINE MIMIC. THE MIMIC SHALL GRAPHICALLY SHOW EACH
GENERATOR SOURCE WITH ITS RESPECTIVE MAIN CB IN A ONE-LINE REPRESENTATION.
UTILIZING COLORED LIGHTS AND DIGITAL METERS, THE MIMIC SHALL ACTIVELY DISPLAY
THE FOLLOWING:
UTILITY CB OPEN/CLOSED/TRIPPED
UTILITY
VOLTS/AMPS/KW/FREQUENCY
GENERATOR #1-12 CB OPEN/CLOSED/TRIPPED
GENERATOR #1-12 VOLTS/AMPS/KW/FREQUENCY
ENGINE #1-12 STOPPED/RUNNING/COOLDOWN/PRE-ALARM/SHUTDOWN
SYSTEM OUTPUT VOLTS/AMPS/KW/FREQUENCY
SYSTEM SUMMARY ALARM
1 -POWERLYNX® SYSTEM METERING (3P VOLTAGE, 3P CURRENT, FREQUENCY,
POWER FACTOR, KW, KVAR), CONTROL (NORMAL MODE,
CLOSED TRANSITION LOAD MANAGEMENT MODE, PEAK SHAVING),
AND PROTECTIVE RELAYING INCLUDING:
D