A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4x ...

Code No. LIT-1927385 Issued July 1, 2006 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4x Watertight Enclosures
Description
The A419 series controls are single-stage, electronic temperature controls with a Single Pole, Double Throw output relay. They feature a lockable front-panel touchpad for setup and adjustment, and a Liquid Crystal Display for viewing the temperature and status of other functions. A Light-Emitting Diode indicates the controls' output relay (On/Off) status. The A419 controls are available in 24 VAC or 120/240 VAC models. The A419 controls have heating and cooling modes, adjustable setpoint and differential, an adjustable anti-short cycle delay, and a temperature offset (setback) function. The setpoint range is -30 to 212°F (-34 to 100°C). The controls feature remote sensing capability and interchangeable sensors. The A419 controls are available in either NEMA 1, highimpact plastic enclosure suitable for surface or DIN rail mounting or NEMA 4X Watertight surface-mount enclosures. · the 30° (F° or C°) temperature differential adjustment range allows precise (1F° or C°) temperature differential settings that are much tighter than electromechanical controls the Adjustable Anti-Short Cycle Delay (0 to 12 Minutes in 1-Minute Increments) ensures that the output relay remains off for a user-set time delay, and helps avoid hard starts, nuisance overload outages, and unnecessary equipment wear the Temperature Offset Function shifts the cut-in and cut-in setpoints by an adjustable offset when a user-installed, external switch closes the A419 control's binary input circuit the high-impact thermoplastic type NEMA 1 allows surface or snap-fit DIN rail mount; the Noryl® high-impact thermoplastic type NEMA 4X enclosures allow watertight surface mount lockable front-panel touchpad allows easy set up and adjustment of the A419 control setpoint, differential, and other functions; a · concealed jumper locks the touchpad, and deters unauthorized adjustment of the · control settings · · · · · · A419 Control and Sensor Features
· low- and line-voltage models provides options for almost any refrigeration or HVAC control-voltage application easy-to-read LCD displays the sensed temperature and control-function status clearly and custom icons on the display indicate the control and system status at a glance Applications
The A419 can be used to control a wide variety of single-stage refrigeration or HVAC equipment. Typical applications include: · · freezer control in convenience stores reach-in coolers · · · · supermarket display cases for produce or meats restaurant or convenience store walk-in coolers boiler control compressor lockout (disables the compressor when temperature exceeds limits) condensor fan cycling pump control for cooling towers space and return air temperature Selection Chart
A419 Series Electronic Temperature Control with NEMA 1 or NEMA 4X Watertight Enclosure Code Number Item Lead Length
A419ABC-1C1 A419ABC-2C1 A419ABC-3C1 A419ABC-4C
1 Description Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display Line Voltage, NEMA 4X Enclosure Electronic Temperature Control with Display Line Voltage, NEMA 4X Enclosure Electronic Temperature Control with Display 24 VAC, NEMA 1 Enclosure Electronic Temperature Control with Display 24 VAC, NEMA 4X Enclosure Electronic Temperature Control with Display 6-1/2 ft (2m) 9-3/4 ft (3m) 13 ft (4m) 19-1/2 ft (5m) 9-3/4 in. (0.25m) 6-1/2 ft (2m) 6-1/2 ft (2m) 9-3/4 in. (0.25m) Supply Voltage: 24 VAC, Class 2 Range: -30 to 212°F (-34 to 100°C) Differential: 1 to 30F° (1 to 30C°) Supply Voltage: 120 or 240 VAC Range: -30 to 212°F (-34 to 100°C) Differential: 1 to 30F° (1 to 30C°) A419AEC-1C1 A419AEC-2C
1 A419GBF-1C1 A419GEF-1C1 1. A99 Sensor included with all models Accessories and Replacement Parts Code Number Item
A99BB-200C A99BA-200C A99BB-25C BKT287-1R BKT287-2R PLT344-1R CLK350-2 WEL11A-601R Digital Clock Immersion Well Accessory Mounting Hardware Replacement Temperature Sensors1 Description
PTC Sensor with 6-1/2 ft (2 m) Leads PTC Sensor with 6-1/2 ft (2 m) Shielded Leads PTC Sensor with 9 in (0.25 m) 12 in. (305 mm) long DIN Rail 36 in. (914 mm) long DIN Rail Two End Clamps for DIN Rail Mounting 7-Day Programmable Digital Clock for controlling Temperature Offset Function Immersion Well for applying sensor in fluid applications 1. For other available sensors, see A99B Series Temperature Sensor Catalog Page.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. www.johnsoncontrols.com Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2006 Johnson Controls, Inc. 1 of 2 Electronic Temperature Controls with NEMA 1 or NEMA 4x Watertight Enclosures
Technical Specifications and Electrical Ratings
A419 Series Electronic Temperature Controls with NEMA 1 General Purpose or NEMA 4x Watertight, Corrosion-Resistant Enclosures
Setpoint Range Differential Range Supply Voltage 24 VAC, 60 Hz, Class 2 120 or 240 VAC, 60 Hz Power Consumption Output Relay Contacts 24 VAC models Electrical Ratings 120/240 VAC models Applied Voltage Horsepower N.O. (N.C.) Full Load Amperes N.O. (N.C.) Locked Rotor Amperes N.O. (N.C.) Non-inductive Amperes N.O. (N.C.) Pilot Duty -30 to 212°F (-34 to 100°C) 1 to 30F° (1 to 30C°) A419GBF (NEMA 1 Enclosure Model) A419GEF (NEMA 4X Watertight Enclosure Model) A419ABC (NEMA 1 Enclosure Model) A419AEC (NEMA 4X Watertight Enclosure Model) 1.8 VA Maximum A419GBF (NEMA 1 Enclosure) A419GEF (NEMA 4X Watertight Enclosure) 100 VA, 30 VAC maximum, Class 2 A419ABC (NEMA 1 Enclosure) A419AEC (NEMA 4X Watertight Enclosure) 120VAC 1 (0.25) hp 16 (5.8) A 96 (34.8) A 15 (10) A 208VAC 1 (0.33) hp 9.2 (4.0) A 55.2 (24) A 10 (10) A 240VAC 1 (0.5) hp 8.0 (4.9) A 48 (29.4) A 10 (10) A 125 VA (N.O. contacts) @ 24 to 240 VAC 125 VA (N.C. contacts) @ 120 to 240 VAC 50 VA (N.C. contacts) @ 24 VAC A99BB Type PTC Sensor (See attached Selection Chart) -30 to 140°F (-34 to 60°C) -40 to 185°F (-40 to 85°C) 0 to 95% RH Noncondensing; Maximum Dew Point: 85°F (29°C) NEMA 1 High-impact Thermoplastic NEMA 4X Watertight Corrosion-Resistant, High-Impact Noryl® Thermoplastic UL: File E27734; CCN's XAPX (US), XAPX7 (Canada) FCC: CFR 47, Part 15, Class A. DOC, Class A Sensor Type Control Ambient Temperature Ambient Humidity Control Material Case and Cover Operating Shipping Agency Listings The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. www.johnsoncontrols.com Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2006 Johnson Controls, Inc. 2 of 2