Power Protection and Conditioning

="text/css">
Contact
Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com.
11
1
Power Protection and Conditioning
STV 200/400K Series - Surge Protective Devices
SolaHD STV 200/400K Series offers continuous protection
from damaging voltage transients and electrical noise
commonly found at the service entrance or distribution
panel. The modular design of the STV 200/400K allows
for installation flexibility and its robust design allows for
installation in the most severe exposure locations. They are
capable of handling the high-impulse, potentially damaging
transients commonly found at the service entrance or
distribution panels. The modular design of the STV
200/400K allows for installation flexibility. Its robust design
allows for placement in the most severe exposure locations.
The STV 200/400K utilizes patented circuitry to monitor
the status of all protection modes, including neutral to
ground. Should protection be unavailable in any mode, the
Green LED will be extinguished, and the Red LED will be
illuminated. In addition, high isolation form C dry contacts
provide remote monitoring of suppression system failure,
under voltage, phase and power loss. The STV 200/400K
patented suppression integrity monitoring indicates failure
for both shorted or opened suppression components.
These devices are designed to meet UL 1449 (second
edition), UL 1283 and cUL Listed. These units are ANSI/IEEE
C62.11, C62.41, C62.45 Categories A, B, and C3 tested.
They are built to meet your unique requirements, and are
available in hardwire, three phase configuration. They are
designed for years of trouble free operation and require little
or no operator intervention after installation.
Features
Modular design allows for flexibility
Surge current capacity of 200 to 400 kA per phase
Industrys highest surge current repeatability
All modes transient protection (L-N, L-G, and N-G)
Form C contact and audible alarm status indications
Internal/external monitoring, including neutral to ground
UL rated 200 kAIC with component level fusing


for safe operation
EMI/RFI Filtering
UL 1449 (second edition), UL 1283, and cUL Listed
ANSI/IEEE C62.11, C62.41, C62.45


Categories A, B, and C3 tested
Tested to NEMA LS1, ISO 9001
NEMA 12 enclosure, available options


NEMA 3R, 4, and 4X
Optional rotary disconnect, transient counter,


and remote monitor panel
5 Year Limited Warranty
Applications
The STV 200/400K Series can be a facility-wide product
family and may be installed from service entrances to distri-
bution panels to branch panels.
Industrial Plants

Commercial Buildings

Institutional Facilities

Any facility that has an environment with

electronics based equipment
Related Products
Power Conditioners
Uninterruptible Power System
Transformers
STV 25K, STV 100K, STF, STFV and STC Series
Selection Table
Catalog
Number
Input Voltage
STV 400K-10Y
120/208 V
Three Phase Wye 4 wire + Ground
STV 200K-10Y
120/208V
Three Phase Wye 4 wire + Ground
STV 400K-27Y
277/480 V
Three Phase Wye 4 wire + Ground
STV 200K-27Y
277/480 V
Three Phase Wye 4 wire + Ground
STV 400K-48D
480 V
Three Phase
3 wire + Ground
STV 200K-48D
480 V
Three Phase
3wire + Ground Contact
Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com.
12
1
Power Protection and Conditioning
STV 200/400K Specifications
Description
Catalog Number
STV 200K-10Y
STV 200K-27Y
STV 200K-48D
STV 400K-10Y
STV 400K-27Y
STV 400K-48D
Input Vac
120Y/208 V
277Y/480 V
480 V
120Y/208 V
277Y/480 V
480 V
Three Phase Wye,
4 W + G
Three Phase Wye,
4 W + G
Three Phase Delta,
3 W + G
Three Phase Wye,
4 W + G
Three Phase Wye,
4 W + G
Three Phase Delta,
3 W + G
Maximum Continous
Operating Voltage (MCOV)
120 V = 125%, All others voltages 115%
Line Frequency
4763 Hz
Connection/
Mounting Type
Internally connected/Wall Mounted (Mounting hardware 1/4 in.)
Enclosure
NEMA 12 (NEMA 3R, 4, 4x optional)
Modes of Protection
All Modes: L-N, L-L, L-G, N-G
Saftey Agency Approvals
UL 1449, UL 1283, cUL
UL 1449 (2nd Edition) Suppressor Classification
L-N
400 V
700 V
N/A
400 V
700 V
N/A
L-L
700 V
1,500 V
1,500 V
700 V
1,500 V
1,500 V
L-G
400 V
700 V
1,500 V
400 V
700 V
1,500 V
N-G
400 V
700 V
N/A
400 V
700 V
N/A
AIG Rating
200 kAIC
Status Indication
LEDs status indicator, Audible alarm, and Form C contact only relay
Response Time
< 0.5 nsec.
Operating Temperature
-40癈 to +50癈
Operating Humidity
0% to 95% Non-condensing
Noise Attenuation
50 dB Maximum
Circuit Ampacity Limitations
Per Phase
200 kA
400 kA
200 kA
400 kA
200 kA
400 kA
Line to Neutral
100 kA
200 kA
100 kA
200 kA
100 kA
200 kA
Line to Line
100 kA
200 kA
100 kA
200 kA
100 kA
200 kA
Line to Ground
100 kA
200 kA
100 kA
200 kA
100 kA
200 kA
Neutral to Ground
100 kA
200 kA
100 kA
200 kA
100 kA
200 kA
Warranty
5 year limited warranty Contact
Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com.
13
1
Power Protection and Conditioning
Dimensional Drawings
E
F
B
A
D
C
1.35
Max.
Service Panel for
Loads to be Protected
Phase L1/A
Phase L2/B
Phase L3/C
Disconnect/Main
Breaker for
Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Recommended Wire
Entrance
SOLA
SOLA
Dimensional & Wiring Specifications
STV 200/400K Series
Catalog
Number
Dimensions (in/mm)
Weight
lbs (kg)
Suggested
Breaker Size
Suggested Wire
Size (AWG)
Allowable Breaker
Range
Allowable
Wire Range
A
B
C
D
E
F
STV 200K
16
14
8
16.75
12
.31
41 (18.60)
40 A
#8
15 A100 A
#14#2
STV 400K
20
16
9
21.25
10
.44
56 (25.40)
100 A
#2
15 A100 A
#14#2
STV 200/400K Series with Rotary Disconnect
Catalog
Number
Dimensions (inches)
Weight
lbs (kg)
Suggested
Breaker Size
Suggested Wire
Size (AWG)
Allowable
Breaker Range
Allowable
Wire Range
A
B
C
D
E
F
STV 200K
16
14
8
16.75
12
.31
41 (18.60)
40 A
#8
15 A175 A
#142/0
STV 400K
20
16
9
21.25
10
.44
56 (25.40)
100 A
#2
15 A175 A
#142/0