CBA 1000new-5 ok

1
BU2000
BU2000 -
HIGH CURRENT BOOSTER
HIGH CURRENT BOOSTER FOR T/2000 AND T/3000 TEST EQUIPMENT
1
The current output of T/2000 and T/3000 can be increased
to up to 2000 A with a new type of optional booster
controlled by the T/3000 - 2000 control unit. The BU2000
option is an innovative design concept that allows to avoid
the power losses due to long cables connections.
To achieve this, the BU2000 transformer is placed very
close to the device under test (CT primary side, Circuit
Breaker main contacts), thus avoiding losses on the high
current cables. The BU2000 is then connected with a
long (up to 20 m) low power control cable to T/2000 or
T/3000 unit.
In case of 2 to 4 BU2000 units an Interposing Module is
necessary. This module is connected with low power
cables to the BU 2000 units.
The technical specification of the BU2000 is summarized
in the following table:
Characteristics of the
output transformers:
BU2000 Main Module:
. Supply voltage: 230 V.
. Voltage output (one turn): 0,91 V.
. Steady power: 1000 VA.
. Connection of the transformer: by a cable, 20 m long,
terminated with connectors on both sides.
. Output current metering: by a current transformer
with ratio 1000//1. Accuracy class: 0.5%.
. Connection of the CT: by a cable, 20 m long, that
includes a shunt, rated 0.1 Ohm, accuracy 0.1%.
The cable is terminated with a connector for the
connection to the 10 V input of T2000 - T3000.
BU2000 Auxiliary Module:
. Supply voltage: 230 V.
. Voltage output (one turn): 0,89 V.
. Steady power: 1000 VA.
. Connection of the transformer: by a cable, 20 m long,
terminated with connectors on both sides.
High current cables:
. Number of conductors: 2.
. Conductors cross section: 95 sq. mm.
. Conductors type: high flexibility.
. Conductors length: the total length of the cables
(not considering the transformers) is 1,4 m.
Number of
BU2000 unit
1
2
4
WEIGHT
Kg
20
30
50
MAX. LOAD
mOhm*
1.5
0.15
2.4
0.6
0
12
5
6
2.4
0.8
0.6
2.6
0.6
0
MAX.
CURRENT A*
1000
2000
1000
2000
3000
1000
2000
1000
2000
3000
4000
1000
2000
3000
ON time
S*
100
10
700
30
10
100
10
700
30
10
4
INFINITE
700
100
OFF time
S*
700
300
1700
450
300
1700
450
1700
450
300
200
INFINITE
1700
700
*With mains voltage
of 230 V and ambient
temperature of 23癈
(+/-5癈).
BU2000 Main Module with high current clamp ISA srl
Via Bergamo, 41
21020 TAINO (Va) Italy
Tel. + 39 0331 956.081
Fax + 39 0331 957.091
Web site: www.isatest.com
E-Mail: isa@isatest.com
G
B
-
B
U
2
0
0
0
-
1
0
.
0
7
BU2000
High current clamps:
. Number of clamps: 2.
. Material: aluminium.
.
Opening range: from 5 to 60 mm.
. Short-circuit rating current: 41 kA / 1 s.
. Applicable standard: EN 61230.
. Hole to lift the clamp on the conductor, and ring to
screw it up.
The option comes in a suitable transport case.
Characteristics of the Interposing
Module:
. Mains connection: by a 64 A rated connector, provided.
. Power-on: by means of a circuit breaker rated 64 A.
. Coarse current adjustment: by means of a
four-position selector switch.
. Connections to T3000: power supply cord; Variable
voltage output; auxiliary contact, timer START input.
. Capable to drive up to four transformers.
. Weight: 5 kg;
NOTE: in case of one BU2000 Main, the Interposing Module
is not necessary.
Ordering information:
The document is subject to change without notice
BU2000 - connecting cable
BU2000 - High Current clamp
BU2000 - Interposing Module
BU2000 Auxiliary Module
BU2000 Accessories
CODE
MODEL
BU2000
50102
BU2000 -up to 2000A- Main Module with
high current clamps and high current cables.
51102
BU2000 -up to 3000A- Main Module with
high current clamps, high current cables,
Auxiliary Module (1), Interposing Module.
52102
BU2000 -up to 4000A- Main Module with
high current clamps, high current cables,
Auxiliary Module (3), Interposing Module.
CODE
MODEL
53102
BU2000 Inteposing Module
54102
BU2000 Auxiliary Module
Option for BU2000 Main Module