VISTA-10

td> Yahoo! is not affiliated with the authors of this page or responsible for its content.
VISTA-10 VISTA-10
SE
N7227V5 5/97
Installation Instructions Installation Instructions Installation Instructions
Security System
THIS ISSUE INCLUDES THE NEW QED (QUICK ENROLLMENT
OF DEVICES) PROCEDURE FOR 5800 SERIES TRANSMITTERS
Previous Menu 2
RECOMMENDATIONS FOR PROPER PROTECTION
The following recommendations for the location of fire and burglary detection
devices help provide proper coverage for the protected premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted
below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all
rooms and areas of the household as follows: For minimum protection a smoke detector should
be installed outside of each separate sleeping area, and on each additional floor of a multi-floor
family living unit, including basements. The installation of smoke detectors in kitchens, attics
(finished or unfinished), or in garages is not normally recommended.
For maximum protection the NFPA recommends that you install heat or smoke detectors in the
living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage
rooms, basements and attached garages.
In addition, we recommend the following:

Install a smoke detector inside every bedroom where a smoker sleeps. Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway
outside may not wake up the sleeper if the door is closed. Install a smoke detector inside bedrooms where electrical appliances (such as portable
heaters, air conditioners or humidifiers) are used. Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12
meters) long. Install smoke detectors in any room where an alarm control is located, or in any room where
alarm control connections to an AC source or phone lines are made. If detectors are not so
located, a fire within the room could prevent the control from reporting a fire or an intrusion.
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
7
7
7
7
7
v
v
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
s
s
s
7
7
7
7
7
7
v
7
7
7
BEDROOM
BEDROOM
TO
BR
s
s
s
s
s
LVNG RM
BASEMENT
KTCHN
v
v
.
CLOSED
DOOR
GARAGE
v
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING FOR FIRE NOTIFICATION APPLIANCES.
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in
a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can
still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm
signals are normally sent over the phone lines, if connected to an alarm monitoring station). 3
TABLE OF CONTENTS
Section 1.
GENERAL DESCRIPTION
............................................................................................

9
Section 2.
INSTALLING THE CONTROL
...................................................................................

11
Mounting the Cabinet .......................................................................................................
11
Installing the Lock (if used) ..............................................................................................
11
Installing the Control's Circuit Board Alone or (if used), With a 4204 Relay Unit..............
11
Installing Control and RF Receiver Circuit Boards Together in the Cabinet.....................
13
Standard Phone Line Connections ...................................................................................
13
Wiring the AC Transformer ...............................................................................................
14
Installing the Back-Up Battery ..........................................................................................
14
Earth Ground Connections ...............................................................................................
14
Section 3.
INSTALLING REMOTE KEYPADS
...........................................................................

15
Keypads that May Be Used ..............................................................................................
15
Wiring to the Keypads ......................................................................................................
15
Wiring Run Chart for Devices Drawing AUX Power From the Control .......................
15
Mounting the Keypads ......................................................................................................
16
Using A Supplementary Power Supply To Power Additional Keypads .............................
16
Preliminary Check-Out Procedure ....................................................................................
17
Section 4.
BASIC HARD-WIRED ZONES 16
..........................................................................

18
Installing the Hard-Wired Zones .......................................................................................
18
Common Characteristics For Zones 16....................................................................
18
Wiring Burglary and Panic Devices to Zones 16 ............................................................
18
Wiring 4-Wire Smoke/Combustion Detectors on Zones 5 ................................................
18
Compatible 4-Wire Smoke/Combustion Detectors .....................................................
19
Programming Hard-Wired Zones ......................................................................................
19
Programming Panic Keys ...........................................................................................
20
Check-Out Procedure for Hard-Wired Zones 16 ............................................................
21
Section 5.
WIRELESS (RF) ZONE EXPANSION (5700 & 5800 RF SYSTEMS)
..............

22
Wireless Systems Available .............................................................................................
22
Wireless System Operation and Transmitter Supervision ................................................
22
Transmitter Battery Life ..............................................................................................
23
Receiver Supervision ........................................................................................................
23
Installation
and Setup of the 4281/5881 Series Wireless Receivers ................................
23
Installing the 5800TM Module ...........................................................................................
24
5700 Series Transmitter Setup .........................................................................................
24
Setting the DIP Switches on 5700 Series Wireless Transmitters ...............................
25
Wireless Zone/ID Assignments for 5700 Series Transmitters ...................................
25
DIP Switch Tables for 5700 RF System Wireless Devices ...............................................
26
Compatible 5700 Series Transmitters ..............................................................................
27
Programming the Control For a 5700 Wireless System ...................................................
28
Using the House ID Sniffer Mode (5700 Systems) ....................................................
28
Zone Programming for 5700 Series Transmitters.............................................................
28
Go/NoGo Test ............................................................................................................
30
5800 Series Transmitter Setup .........................................................................................
31
5800 Series Transmitter Input Loops .........................................................................
31
5800 Series Transmitter Input Types .........................................................................
31
Compatible 5800 Series Transmitters .............................................................................
32
Programming the RF Transmitters (5800 RF Systems) ...................................................
33
Enrolling 5800 Transmitters Into the System ....................................................................
34
Enrolling Through Zone Programming (
D
56) .............................................................
34 4
Section 5.
WIRELESS (RF) ZONE EXPANSION (5700 & 5800 RF SYSTEMS), CONTD
To Either Temporarily or Permanently Remove a Zone From the System
(5800 System) ............................................................................................................
37
Deleting a Transmitter Serial Number From a Zone in
D
56 Mode (5800 System) ...........
37
Check-out Procedure for Wireless Zones ..........