Spencerport Municipal Electric
Spencerport Municipal Electric
Effective May 1, 2000
The Spencerport Municipal Electric (SME) will no longer be supplying single-phase
meter sockets for residential or commercial use for our customers. A specification sheet
showing approved sockets and approved venders is available from:
Village of Spencerport Office
27 West Ave.
Spencerport NY 14559
Before providing service, SME will require the following items:
A completed electricians report dropped off or faxed to (585) 349-2283
or mailed to the Village of Spencerport 27 West Ave. Spencerport NY 14559
Phone numbers (585) 352-4771 (585) 352-6851 (585) 352-6775
A trench inspection by Spencerport Municipal Electric
An electrical inspection by either the Board of Fire Underwriters, or the Middle Department.
ANCHOR METER SOCKET SUPPLIERS
Maynard Electric Supply
Kovalsky Carr Electric
Rochester, NY
Rochester, NY
Rero Distribution
Wehle Electric
Rochester, NY
Rochester, NY
Graybar Electric
Wesco
Rochester, NY
Rochester, NY
GE Supply
Gates Electric Supply
Rochester, NY
Rochester, NY
Crown Electric Supply
Falcone Electric
Union Hill, NY
Batavia, NY
Country Line Electric
Lake Sales
Silver Springs, NY
Sodus, NY
Colacino Electric Supply
T & G Electric
Newark, NY
Canandaigua, NY
MILBANK METER SOCKET SUPPLIERS
Crown Electric Supply Co
Gates Electrical Supply
Union Hill, NY
Rochester, NY
Kovalsky-Carr Electric Supply Co.
Maynard's Electric
Rochester, NY
Rochester, NY
T & G Electrical Supplies
Wesco Distribution Inc.
Canandaigua, NY
Rochester, NY
VILLAGE OF SPENCERPORT
27 West Avenue Spencerport New York 14559
(585) 352-4771
Spencerport Municipal Electric Approved Meter Sockets
By Application
Description - 200 AMP Overhead/Underground
1,2,3,4,5 and 6 position, 200 AMP capacity per position, hub opening for standard 1" to 2 'h" entry, 4 jaw socket with horn bypass and
provisions for later installation of a 5"jaw. Bussed line conductor, load conductor lay-in style for up to #4/0 Awg. Equip with ring-less
type cover.
Milbank catalog no. U7040-RL-TG-KK Anchor catalog no. URS 1394B-HO
Description - 200 AMP Multiple-Gang, Overhead [Underground I Phase, 3 Wire, 120/240V.:
1,2,3,4,5 and 6 position, 200 ANW capacity per position, hub opening for standard I" to 2112" entry, 4 jaw socket with horn bypass
and provisions for later installation of a 5' jaw. Bussed line conductor-'load conductor lay-in style for up to 94/0 Awg.. Equip with
ring-less type cover.
Milbank catalog no.
Anchor catalog no.
(2-position) U1252-R-KK 2URS180IB-C600-HL
(3-position) U1253-R-KK 3URS1804B-C600-HL
(4-position) U1254-R-KK-EX 4URS1804B-C600-HL
(5-position) U1-255-R-KK-EX 5URS180413-C600-2H
(6-position) U1256-R-KK-EX 6URS1804B-C6002HL0
Description - 320 AMP. - Overhead/Underground l Phase, 3 Wire, 120/240 V.
1 -Position, 320 Amp. top bottom opening for large size
hub. 4"
jaw socket with safety and provision for 5" jaw. Non-removable
bypass lever, single 3/8" studs line/load. Equip with ring-less latch type cover.
Milbank catalog no. Anchor catalogs no.
Underground ONLY U1797-X (30"X15"X4.88")
Overhead or Underground U2448-X (34.13"X17.75"X6.5") TB44542-HlOM (31"X18"X5.44")
Page 1 of 1
05/01/00
Spencerport Municipal Electric
400A 120/240 Volt
Single Phase Residential Service
Frost expansion joints are recommended at this time on a 400-amp service.
Compression type lugs are to be provided by the contractor.
METER SOCKET WIRING
FOR UNDERGROUND SERVICES
Looping of conductor as shown to minimize damage to cable and stress on conductors. Single phase wire 120/240V
Underground services up to 200 amp Meter Box.
Spencerport Municipal Electric
Specifications for Secondary Overhead Electric Services
1) The customer at his expense will install, own and maintain the service riser up to and including the weather head
along with the meter-box.
2) The Spencerport Municipal Electric shall be consulted before work is started to designate the point from which
service will be taken with the route to be followed and the meter location. The meter will be spotted by an authorized
S.M.E. representative for all service changes. The electrician will have to call 352-4771 to schedule a meter spot at least
48 hours in advance.
3) CONDUIT: If conduit is used, it must be UL approved all galvanized steel conduit two inch minimum (2") pipe size.
Conduit must be back-guyed with appropriate steel cable against pull of service conductors.
METER SOCKETS: The Customer will furnish and shall install all meter mounting equipment such as meter sockets.
Meters are to be located within a five-(5) foot radius of the corner of the house that fronts to the nearest S.M.E.
distribution point. All meters are to be located outdoors at a minimum height of 42" and a maximum height of 60". These
measurements are to be taken from the center of the meter-box to final grade. Meter socket specifications are available at
the Village Office 27 West Avenue, Spencerport New York 14559 during working hours. A copy of the building permit
and applicable compliance forms and upgrades is required.
WEATHERHEAD: A rain tight weather head must be furnished and mounted above the house knob. Twenty-four (24)
inches of wire must be left exposed for a drip loop and power company connection.
INSPECTION: Service will not be rendered until a certification of the approval of the customer's wiring from the New
York Board of Fire Underwriters, or the Middle Department Agency has been furnished.
DISCONNECT/RECONNECT: Spencerport Municipal Electric shall DO ALL disconnects/reconnects between the
hours of 7:30AM and 3:30 PM Monday through Friday, excluding Holidays. The customer shall call Spencerport
Municipal Electric 352-4771 to schedule a disconnect/reconnect at least 48 hours in advance.
CONNECTIONS: All connections between Spencerport Municipal Electric Wires and customer wires shall be made and
removed exclusively by Spencerport Municipal Electric personnel. Connection to the S.M.E. electric supply system or any
alteration of existing connections by anyone except S.M.E. personnel is PROHIBITED BY PENAL LAW AND
PUNISHABLE AS A MISDEMEANOR. VIOLATORS OF THIS RULE WILL BE PROSECUTED. THE LAW
PROVIDES THAT THE USER OF SUCH A CONNECTION IS PRESUMED TO HAVE MADE OR CONSENTED TO
THE UNAUTHORIZED CONNECTION AND IS PUNISHABLE THEREFORE UNLESS PROVEN THE
CONTRARY, AS WELL AS THE PARTY MAKING THE CONNECTION.
01/22/01
Spencerport Municipal Electric
SPECIFICATIONS FOR SECONDARY UNDERGROUND
ELECTRIC SERVICE
1) The customer will at his expense install, own, and maintain the service lateral along with the meter box
2) The Spencerport Electric shall be consulted before work is started to designate the point from which service will be taken, the route to be followed
and the meter location. An S.M.E. authorized representative for all service changes will spot the meter. The electrician will need to call 352-4771 at
least 48 hours in advance for a meter spot.
3) The customer will provide the trench, install conduits, and backfill in accordance with the following S.M.E. specifications.
a) SERVICE TRENCH: Shall be uniform to the required thirty-six inch (36") depth and shall be a minimum of twenty-four inches (24") wide. If
joint trench construction is used with other systems (RGE, CITIZENS, and GRC) the trench width shall be adequate to permit a minimum of twelve
inches (12") separation from other utilities.
b) BACKFILL OF TRENCH: The first one foot (1) of backfill shall be a stone free bed of sand, six inches (6") below and a sand safety cover six
inches (6") above the cable. All sand for bedding and an S.M.E. representative before placement shall approve safety cover. The remainder of the
trench may be machine back-filled with excavated materials providing no stones, rocks, or debris with any dimension over two (2") inches is
included.
c) CONDUIT: If conduit is used, it must be UL approved schedule 40 PVC or galvanized steel conduit two and one half inch (2 /12") minimum pipe