Model PT-SMLA

r>

Model PT-SMLA SECTION
M POWERTRIP TVSS PRODUCTS
M-16
828.646.9290 www.allteccorp.com
The PT-SMLA Series TVSS Device is the designed for AC Power protection for industrial and commercial
services. This device was engineered for installation on high ampacity service entrances, distribution panels,
and main disconnects to provide robust protection from severe lightning surges and transients.The PT-SMLA
is the perfect TVSS device for protecting expensive industrial and manufacturing equipment. The device can
be installed at the motor control panels or at the load to protect from power supply surges and from the ever-
present internally generated transients in the industrial & manufacturing environment.
IEEE-C62.41.1 & C62.41.2-2002 environments:
Suitable for Categories: A, B & C
(Most Severe Electrical Environments)
IEC Environments:
Suitable for use in IEC 61643-11
environments
Circuit Topology:
Optimal Response Circuitry circuit
design incorporating component-level, thermal fusing and
Patent Pending internal, circuit board mounted, over-current
fusing; and discrete "All Mode" protection (10 modes for 3 phase
Wye units). All protection circuits are encapsulated in our high
dielectric compound to assure long component life and
complete protection from the weather and vibration.
Protection Modes:
Industry-best practice of true all mode
dedicated protection components for all operational modes of
the electrical system. Discrete L-N, L-L (Normal Mode) and L-G, N-
G (Common Mode) Example: Directly Connected Protection
Elements in All 10 modes for a 3 phase, 4 wire, Wye system, (i.e. 3
L-N modes, 3 L-L modes, 3 L-G modes and 1 N-G mode).
Input Power:
50-400 Hz (60 Hz nominal)
Temperature Rating:
Up to 80°C
Response Time:
1 ns
Standard Enclosure:
NEMA 4 ABS Composite - UL94-5VA
(gasket kit P/N: GA001)
Diagnostics:
Green LED's, one per phase, normally on. A wide
range of optional diagnostics is available
(see next page for details).
Circuit Interrupt:
Internal component-level, thermal fusing
and patent pending, circuit board mounted, over-current fusing.
UL Short Circuit Current Rating:
200 kAIC
(UL's Highest Rating)
Product Qualifications:
UL Lightning Protection System Certified ComponentSecondary Surge
Arrestor (Q option) UL1449 2nd Edition, UL1283, cUL, and CE Compliant ISO 9001 Certified Manufacturing
Facility.
Warranty:
25 Years Unlimited Free Replacement
300 kA Per Phase
N o n Tr a c k i n g M o d e l
Model PT-SMLA Discrete "All Mode" Circuitry: Directly
Connected Protection Elements in
"All Modes" (10 modes for 3 phase, 4
wire Wye circuits) as recommend by
NEMA LS-1 and IEEE Std. 1100-1999 Industry Leading Measured Limiting
Voltage (let-through) Performance Local & Remote Diagnostics Independent Verification of
Performance and Safety Component-Level, Thermal Fusing Patent Pending, Internal, Circuit
Board Mounted, Over-Current Fusing
LISTED 1449
Second Edition
KEY FEATURES
M
ADE IN THE
U.S.A. SECTION
M POWERTRIP TVSS PRODUCTS
www.allteccorp.com 828.646.9290
M-17
Model
PT-SMLA1S1
PT-SMLA3Y1
PT-SMLA1P2
PT-SMLA3Y2
PT-SMLA3N2
PT-SMLA3N4
Circuit Type
120/240 V 1Ř (Split)
(3 wire + ground)
120/208 V 3Ř Wye
(4 wire + ground)
240V, Single Ř
(2 wire + ground)
277/480 V 3Ř Wye
(4 wire + ground)
240 V 3Ř Delta (NN)
(3 wire + ground)
480 V 3Ř Delta (NN)
(3 wire + ground)
MCOV
150 V L-N
300 V L-L
150 V L-G
150 V N-G
150 V L-N
300 V L-L
150 V L-G
150 V N-G
320 V L-N
320 V L-G
320 V N-G
320 V L-N
550 V L-L
320 V L-G
320 V N-G
320 V L-L
320 V L-G
550 V L-L
550 V L-G
* B3/C1
393 V
543 V
364 V
668 V
393 V
543 V
364 V
668 V
588 V
588 V
1045V
529 V
777 V
533 V
1025 V
533 V
533 V
777 V
777 V
Mode
L-N
L-L
L-G
N-G
L-N
L-L
L-G
N-G
L-N
L-G
N-G
L-N
L-L
L-G
N-G
L-L
L-G
L-L
L-G
* A3
289 V
436 V
296 V
570 V
289 V
436 V
296 V
570V
450 V
450 V
940 V
410 V
686 V
420 V
806V
420 V
420 V
686 V
686 V
* C3
938 V
1,153 V
824 V
860 V
938 V
1,153 V
824 V
860 V
1070 V
1029 V
1320 V
1,176 V
1,395 V
1,029 V
1,320 V
1,153 V
1,153 V
1,395 V
1,395 V
* Let-through Voltage Test Results
*Let-through Voltage Test Parameters: Positive Polarity, All voltages are peak (±10%). All tests are static except 150 V MCOV modes. Let-through voltages
on static tests calculated by subtracting sinewave peak from let-through measured from zero. 150 V MCOV mode let-through voltages measured from
the insertion point on the sinewave. (Scope Settings: Time Base = 20 microseconds, Sampling Rate = 250 Megasamples/sec. These settings assure Let-
through voltages test results are accurate). All tests performed with 6" lead length (external to the enclosure), simulating actual installed performance.
MODEL PT-SMLA VOLTAGE PERFORMANCE AND ELECTRICAL SPECIFICATIONS
Surge Current Testing: Single-pulse surge current testing for all modes at rated currents as recommended by NEMA LS1-1992. Single pulse surge current
capacities of 200,000 amps or less are determined by testing all suppression components within each mode as a group. Present industry test equipment
limitations require testing of individual suppression components or sub-assemblies within a mode for single-pulse surge capacities over 200,000 amps.
A
D
B
F
C
B
E
Enclosure Dimensions
Enclosure Options
Standard
Model
8.25
5.00
3.00
9.37
8.87
3.37
*NEMA 4
(ABS)
5.0 lbs.
W
10.00
8.00
4.00
11.50
10.75
6.00
NEMA 4
(Steel)
14.0 lbs.
M
10.00
8.00
4.00
11.50
10.75
6.00
NEMA 12
(Steel)
14.0 lbs
X
12.00
10.50
6.00
12.50
12.00
8.00
NEMA 4X
(Composite)
11.0 lbs
Dim.
(in.)
A
B
C
D
E
F
Type
Weight
* Let-through Voltage Test Results - ANSI/IEEE C62.41.1 & C62.41.2
(tested w/6" lead length external to the enclosure per UL 1449)
* A3 - 6kV, 200A,100KHz Ring Wave @ 90ş Phase Angle
* B3/C1 - 6kV, 3kA Impulse Wave @ 90ş Phase Angle
* C3 - 20kV, 10kA Impulse Wave @ 90ş Phase Angle
Green LED indicators
one per phase
normally on.
*UL94-5VA ABS Composite.
Flush mount trim plate
available for standard and
"M" option models.
External Accessories: EACS = Externally mounted diagnostic module, combines AC, C, and S options (Also available: EAC, EC, ECS, and ES)
Options:
AC = Internal Audible Alarm w/ test button, mute switch and red LED
C = Form C dry relay contacts
D1 = Integral, non-fused disconnect switch (TVSS unit mounts inside)
D2 = External non-fused disconnect switch (TVSS mounts to outside)
D3 = Same as D1, except no external handle
E1 = Hub on side of enclosure
E2 = No hub, wires only exiting from side of enclosure
E3 = No hub, wires only exiting the end of the enclosure
F = Internal, circuit board mounted over-current fuses
LP = Remote LED indicators in individual NEMA 4X housings
M = NEMA 12 Steel Enclosure
N
= Removes neutral to ground Sinewave Tracking Circuit
P = Flush Mount Plate
Q = Labeled as a secondary surge arrester - UL category OWHX
(Requires "F " option)
R1 = Remote lights on separate circuit board (no enclosure)
R2 = Remote lights on separate circuit board in separate enclosure
S = Surge counter w/ reset button
W = NEMA 4 Steel Enclosure
X = NEMA 4X Composite Fiberglass Enclosure
XS = NEMA 4X Stainless Steel Enclosure