OPERATING MANUAL SERIES SMTBM BRUSHLESS SINGLE AXIS MODULE
ty provision carefully before attempting to adjust or service the
unit.
2
RECEIVING AND HANDLING
Upon delivery of the equipment, inspect the shipping containers and contents for indications of
damages incurred in transit. If any of the items specified in the bill of lading are damaged, or the
quantity is incorrect, do not accept them until the freight or express agent makes an appropriate
notation on your freight bill or express receipt.
Claims for loss or damage in shipment must not be deducted from your invoice, nor should
payment be withheld pending adjustment of any such claims.
Store the equipment in a clean, dry area. It is advisable to leave the equipment in its shipping
container until ready for use. Each amplifier is checked carefully before shipment. However,
upon receipt, the user should make sure that the amplifier received corresponds to or is properly
rated in terms of rated voltage and current for the type of motor which is to be driven. The
descriptive label affixed to the amplifier specifies electrical ratings.
Infranor Inc. reserves the right to change any information contained in this manual without notice.
Infranor Inc. does not assume any responsibilities for any errors that may appear.
©
1998 INFRANOR INC.
3
OPERATING MANUAL
INFRANOR
SERIES SMTBM
BRUSHLESS SINGLE AXIS MODULE
(April 1998)
1.0.0 GENERAL ............................................................................................................................................. 4
1.1.0
I
NTRODUCTION
.................................................................................................................................. 4
1.2.0
S
PECIAL FEATURES
............................................................................................................................. 4
2.0.0 SPECIFICATIONS................................................................................................................................ 4
2.1.0
T
ECHNICAL SPECIFICATIONS FOR
SMTBM M
ODULE
........................................................................... 4
3.0.0 CONNECTIONS.................................................................................................................................... 7
3.1.0
SMTBM
CONNECTIONS
..................................................................................................................... 7
3.2.0
SMTBM
DIAGRAM OF CONNECTIONS
................................................................................................. 8
4.0.0 DIMENSIONS ..................................................................................................................................... 11
4.1.0 SMTBM S
INGLE AXIS MODULE
....................................................................................................... 11
4.2.0
S
HUNT RESISTOR MODULE
................................................................................................................ 11
5.0.0 SHIELDING RECOMMENDATIONS .............................................................................................. 12
4
1.0.0 GENERAL
1.1.0
Introduction
The SMTBM single axis module is designed for the SMTBSI and SMTBD Series amplifier fitted
with the braking regulator option ("d" or "dp") integrated in the amplifier. Maximum current
capabilities is 20 Arms with 60 Arms peak (5% duty cycle).
1.2.0
Special features
Back Panel mounting
Fan and heatsink cooling
Standard shunt regulator depending on amplifier output (100-280W)
Easy amplifier plug-in connections
Three or single phase autotransformer
Can operate with auto-transformer
Direct line input connection (with line filter)
2.0.0 SPECIFICATIONS
2.1.0
Technical specifications for SMTBM Module
The SMTBM Module is designed for the SMTBSI or SMTBD Brushless amplifier fitted with the
optional shunt regulator ("dp") mounted in the amplifier. The module incorporates a DC bus
power supply capable of driving a motor with an output of 20 Arms continuous and 60 Arms
peak maximum (5% duty cycle).
A three phase isolation transformer or an auto-transformer is required to power the unit. Direct
connection to the main 220 VAC line is possible (10Arms or less) when using the appropriate line
filter.
The shunt resistor needs to be mounted outside the unit in an area protected against any physical
contact and if possible near a cooling fan.
The single-axis rack housing MUST BE GROUNDED in order to ensure physical protection in
case of insulation failures to the mains. INFRANOR will withdraw any warranty on all material
which does not meet this requirement.
Rated input voltage
3Ø 220VAC +10% -15%
Rated auxiliary input voltage
1Ø 220VAC +10% -15%
Maximum continuous output current
20ARMS
Maximum peak output current
60ARMS (5% duty cycle)
5
The continuous current capabilities according to the different cooling type are as follows:
AMPLIFIER
IMAX (1 Sec)
CONT. CURRENT (Irms) *
NO FAN
FAN
FAN /HEATSINK
220/04
220/08
4
8
2
4
-
-
-
-
220/12
13
6
-
-
220/17
17
8.5
-
-
220/30
29
10.0*
12
15
220/45
220/60
46
58
10.0*
10.0*
15
19
20
20
*Maximum ambiant temperature = +40ºC
Fan = 36 CFM
An auxiliary DC supply is incorporated in the SMTBM Module to maintain the logic voltage
separate from the main DC power. See section 3.1.0 for connections
Designation of SMTBM Single Axis Module
SMTB - M - 20
- -
__ __ __ __
__
B series
V
= Fan
Single axis
A = Auxiliary supply
20 Arms
Shunt regulator specifications
The shunt resistor size depends on the amplifier current capabilities and is mounted outside the
unit.
AMPLIFIER
RESISTOR (ohms)
RATED (W)
PEAK POWER (W)
220/04
100
100
1600
220/08
100
100
1600
220/12
100
100
1600
220/17
100
100
1600
220/30
50
200
3200
220/45
220/60
15
15
280
280
10000
10000
6
The shunt resistor is delivered with the amplifier and must be connected to the 2 point connection
mounted on the side of the amplifier (option "dp"). The resistor is mounted inside a protective
housing to avoid electrical shocks (see chapter 4.3.0 for dimensions).
2.1.1
Standard compatibility
The SMTBSI and SMTBD series amplifiers operating in the SMTBM-20A single-axis rack,
which is equipped with the mains filter BF 35, have been approved for their conformity with the
Electromagnetic Compatibility standards:
EN 55011, Group 1, Class A (conducted and radiated radioelectric disturbances)
IEC 801 - 2 - 3 - 4 (noise immunity).
Results and test conditions of the LCIE (Laboratories Central des Industries Electriques), which is
approved by the European Community, are referenced with n° 416040, 416041, 416042, and
416043.
Results of the tests made according to the Low Voltage directive is referenced in the LCIE report
n° 413777.
Standard to be applied to the electrical equipments of industrial machines: EN 60204.1.
2.1.2
"CE"
Marking
CE
recognition marking has been affixed since 1995.
7
3.0.0
CONNECTIONS
3.1.0
SMTBM connections
3.1.1
Upper connector location
1
2
3
1
2
3
1
2
3
4
Earth
XA2
XA1
XM
U
V W
L1
L2
L3
Braking
resistor
3.1.2
XA1 - Power connector
Pin
L1
220 VAC phase 1
L2
220 VAC phase 2
L3
220 VAC phase 3
3.1.3
XM - Motor connector
Pin
U
Motor phase U
V
Motor phase V
W
Motor phase W
The Earth/Ground log has to be connected to the motor shield and to the system
earth ground
. Failure to do so may result in dangerous situation.
3.1.4
XA2- Auxiliary connector
Pin
1
220VAC single phase auxiliary supply
2
220VAC single phase auxiliary supply
3
220VAC for optional fan cooling
4
220VAC for optional fan cooling
8
3.2.0
SMTBM connections diagram
3.2.1
Auto-transformer connections
Solution 1:
M
U
V
W
Logic relay
1AT
20A
Power relay
AUTO
TRANSFO
3 x 220VAC
MAIN
LINE
Earth
Ground
SMTBM-20A
L1
L2
L3
XA1
XA2
1
2
Ground
Earth
o
o
o
o
XM
.
.
.
BF-35
K
Solution 2:
M
U
V
W
Logic relay
1AT
20A
Power relay
AUTO
TRANSFO
3 x 220VAC
Earth
Ground
SMTBM-20A
L1
L2
L3
XA1
XA2
1
2
Ground
Earth
o
o
o
ISOLATION
TRANSFO
Grounding possible
SINGLE
PHASE
220VAC
XM
.
.
MAIN
LINE
o
o
o
K
BF-35
9
Solution 1: It is mandatory when using an auto-transformer to use the 220VAC for the auxiliary
supply at the output of the auto-transformer.
Do not use direct 220VAC from the line.
Solution 2: It is also possible to use a small isolation transformer to power the auxiliary supply.
Caution:
The use of an auto-transformer means that there is no isolation between the main line
and the amplifier (and consequently to the motor). It is then MANDANTORY to
mount fuses or thermal circuit breaker (MOL) in case of a short-circuit.
It is also recommended to use the "AMP READY" logic signal from the amplifier to
open the power relay when a default occurs.
3.2.2
Direct line connections
M
U
V
W
Logic relay
1AT
20A
Power relay
220VAC
MAIN
LINE
Earth
Ground
SMTBM-20A
L1
L2
L3
XA1
XA2
1
2
Ground
Earth
o
o
o
XM
.
.
.
FN612*
* Filter type SHAFFNER FN612-20-06
Note: Maximum RMS rated current not to exceed 10ARMS
10
3.2.3
Recommended relay connections