Jumpers & Load Pickup Tools
size=-1 color=black>
Jumpers & Load Pickup Tools
JULY 2007
HUBBELL / CHANCE CENTRALIA, MISSOURI
2301
Printed in USA
©
Copyright 2007 Hubbell210NorthAllenStreetCentralia,MO65240
NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
Jumpers
& Load Pickup Tools
Warranty - Material
Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in the Uniform Commercial Code) and to be free from defects in material and workmanship.
Buyer must notify the Company promptly of any claim under this warranty. The Buyer's exclusive remedy for breach of this warranty shall be the repair or replacement, F.O.B. factory, at the Company's
option, of any product defective under the warranty which is returned to the Company within one year from the date of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BY
OPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USE
THEREOF. The Company shall in no event be liable for any loss of profits or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the first Buyer of a
product from the Company, from the Company's distributor, or from an original equipment manufacturer reselling the Company's product, and is non-assignable and non-transferable and shall be of
no force and effect if asserted by any person other than such first Buyer. This warranty applies only to the use of the product as intended by Seller and does not cover any misapplication or misuse of
said product.
Warranty - Application
Hubbell Power Systems, Inc. does not warrant the accuracy of and results from product or system performance recommendations resulting from any engineering analysis or study. This applies
regardless of whether a charge is made for the recommendation, or if it is provided free of charge.
Responsibility for selection of the proper product or application rests solely with the purchaser. In the event of errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc., its
liability will be limited to the re-performance of any such analysis or study.
Section
2300
HUBBELL / CHANCE CENTRALIA, MISSOURI
JULY 2007
2302
Description
Pair* of
Clamps
Main Line Range
Max.
336.4
ACSR
.721"
Jumper Cable Range
Min.
#6
Copper
.162"
Max.
2/0
Min.
#2
*Cat No. T6010003 for single clamp.
Cat.
No.
G4758
25 kV Ø-Ø Rated 400 Amp Capacity
The G4765 series Jumper Clamp has the same polyethylene material in
the handle as other Chance Jumper Clamps. The handle length below
the handguard is 7
1
/
2
". The 400 amp continuous current rating is based
on using 4/0 Jumper Cable on the tap side.
Description
Pair* of
Clamps
Main Line Range
Max.
477
ACSR
.883"
Jumper Cable Range
Min.
#6
Copper
.162"
Max.
4/0
Min.
#2
*Cat. No. T6010039 for single clamp.
Cat.
No.
G4765
35 kV Ø-Ø Rated 400 Amp Capacity
The G4775 series Jumper Clamp has a larger contact opening for use
on larger contact opening for use on larger conductor distribution lines.
The handle length below the handguard is 8
3
/
8
". Easy to assemble, the
connector assemblies are interchangeable between the two sizes of 15
kV Jumper Clamps. The 400 amp continuous current rating is based on
using 4/0 Jumper Cable on the tap side.
Description
Pair* of
Clamps
Main Line Range
Max.
954
ACSR
1.165"
Jumper Cable Range
Weight
3 lb./
1.4 kg.
Min.
#6
Copper
.162"
Max.
4/0
Min.
#2
*Cat. No. T6010040 for single clamp.
Cat.
No.
G4775
Insulated Jumper Clamps
Chance Insulated Jumper Clamps are used for bypassing work areas
where equipment is under repair, the line is being upgraded, and for
making temporary or other emergency repairs. The handles are tough,
high impact strength, polyethylene with a wide hand guard flange.
ADEQUATE RUBBER GLOVES MUST BE WORN WHEN INSTALLING
OR REMOVING JUMPER CLAMPS
.
15 kV Ø-Ø Rated 300 Amp Capacity
The G4758 series Jumper Clamp has a handle length of 5
5
/
8
" below the
handguard. The bearing type floating washer lower contact improves
gripping action and prevents conductor scoring. All metal parts are of
copper alloy to improve resistance to oxidation. The 300 amp continuous
current rating is based on using 2/0 Jumper Cable on the tap side.
G4758
15kV
G4765
25kV
G4775
35kV
Style I per ASTM F 2321 Standard Specification
Style I per ASTM F 2321 Standard Specification
Style I per ASTM F 2321 Standard Specification
All Chance
®
Insulated Jumpers meet
ASTM F 2321 Standard Specification.
Weight
2
1
/
4
lb./
1.0 kg.
Weight
2
3
/
4
lb./
1.3 kg.
JULY 2007
HUBBELL / CHANCE CENTRALIA, MISSOURI
2303
Jumper Cable rated Ø-Ø 15 kV
with EPR Insulation/Jacket
Catalog No.
S10043
S10044
S10045
S10046
Size
AWG
#2
1/0
2/0
4/0
Stranding
259/No. 26
413/No. 24
273/No. 23
437/No. 21
Weight
Per
1000 Ft.
438 lb./197 kg.
598 lb./269 kg.
707 lb./318 kg.
1047 lb./471 kg.
Approx.
Ampacity
Rating, Amps
200
260
300
400
Approx.
Cable
O.D.
0.779"
0.863"
0.914"
1.065"
Approx.
Cond.
Diameter
0.322"
0.404"
0.455"
0.602"
Jumper Cable rated Ø-Ø 25 kV and 35 kV
with EPR Insulation/Jacket
Extremely flexible even at low temperatures, this cable
features an insulation/jacket combination resistant to abra-
sion, oil, heat, moisture and ozone. The natural orange color
of this mold-cured ethylene-propylene-base coating imparts
high visibility. For easy identification, AWG size and voltage
rating are embossed at 4-foot intervals.
For extended service life, an extruded screen interfaces insu-
lation and conductor. This strand screen improves voltage-
stress control by adding dielectric strength and eliminating
internal corona.
Insulation and conductor screen meet and exceed ICEA-NEMA
standard S-68-516.
For easy handling in adverse conditions, conductors are
extra flexible alloy-coated copper-stranded rope per ASTM
B-189 or B-33.
Ampacity ratings are based on 90°C conductor temperature
at 40°C ambient.
Extremely flexible even at low temperatures, this cable
features an insulation/jacket combination resistant to abra-
sion, oil, heat, moisture and ozone. The orange color of this
mold-cured ethylene-propylene-base coating imparts high
visibility. For easy identification, AWG size and voltage rat-
ing are embossed at 4-foot intervals.
For extended service life, an extruded screen interfaces insu-
lation and conductor. This strand screen improves voltage-
stress control by adding dielectric strength and eliminating
internal corona. Insulation and conductor screen meet and
exceed ICEA-NEMA standard S-68-516.
For easy handling in adverse conditions, conductors are
extra flexible alloy-coated copper-stranded rope for ASTM
B-189 or B-33.
Ampacity ratings are based on 90°C conductor temperature
at 40°C ambient.
Weight
Per
1000 ft.
801 lb./ 360.5 kg.
913 lb./410.9 kg.
985 lb./443.3 kg.
Approx.
Ampacity
Rating, Amps
260
300
260
Approx.
Cable
O.D.
1.113"
1.160"
1.287"
Approx.
Cond.
Diameter
0.404"
0.450"
0.404"
Stranding
413
266
413
Size
AWG
1/0
2/0
1/0
Catalog No.
25 kV Cable:
S11272
S11273
35 kV Cable:
S11274
For connectors installed on cable or separate, see next
page.
Type I per ASTM F 2321 Standard Specification
Type I per ASTM F 2321 Standard Specification
Type I per ASTM F 2321 Standard Specification
HUBBELL / CHANCE CENTRALIA, MISSOURI
JULY 2007
2304
Weight
per
terminal
2 oz.
Burndy
Die No.
U243
U243
U166-206
U249
Cable
Size
#2
1/0
2/0
4/0
PLUG TERMINALS (NO THREADS)
U243
U243
U166-206
U249
#2
1/0
2/0
4/0
3 oz.
STUD TERMINALS
PLUG TERMINALS
Copper Connector Assemblies are necessary to join cable and
clamp together on Jumper Clamps or Load Pickup Tools only.
Threads are
5
/
8
-11 NC for all connectors. Each Catalog Number
consists of a copper connector, nut and lockwasher.
Jumper Clamp Connector Assemblies
for 15kV, 25kV & 35kV Jumper Cable
These shrouded terminals are for use with only grounding clamps
(see Section 3000 and EPR Jumper Cable (Page 2306) as temporary
jumper assemblies (and should not be used with insulated
jumper clamps, page 2302). Extra heavy-duty shroud prevents
excessive cable stress at terminal connection. To match pressure-
type and threaded connectors on grounding clamps, both plug and
stud terminal styles are available.
Two crimps in Section A with Burndy die numbers (or
equivalent) below secure terminal to cable.
Jumper Terminals
f