10 11 12 13 14 15 16 17

Product Range
5SY6 ...-.KV, 6 kA
3/27
Siemens ET B1 T · 2007
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17 Application
U
n
: 230 V AC, 50 to 60 Hz
Standards: IEC/EN 60898, DIN VDE 0641 Part 11
1+N in 1 MW for distribution applications with little available space
Additional components can be retrofitted Selection and ordering data Dimensional drawings
5SY6 . .- . KV miniature circuit-breakers . .-.
I
n
MW
Characteristic B
Characteristic C
Weight
1 unit
approx.
PS*
P. unit
Order No.
Order No.
A
kg
Unit(s)
1-pole + N
2
1 5SY6 002-7KV
0.132
1/12
4 5SY6 004-7KV
0.132
1/12
6
5SY6 006-6KV
5SY6 006-7KV
0.132
1/12
8 5SY6 008-7KV
0.132
1/12
10
5SY6 010-6KV
5SY6 010-7KV
0.132
1/12
13
5SY6 013-6KV
5SY6 013-7KV
0.132
1/12
16
5SY6 016-6KV
5SY6 016-7KV
0.132
1/12
20
5SY6 020-6KV
5SY6 020-7KV
0.132
1/12
25
5SY6 025-6KV
5SY6 025-7KV
0.132
1/12
32
5SY6 032-6KV
5SY6 032-7KV
0.132
1/12
40
5SY6 040-6KV
5SY6 040-7KV
0.132
1/12
2
1
N
N
45 70,5
6
18
45 90
I2
_0
86
25
* You can order this quantity or a multiple thereof.
6 000
3 Miniature Circuit-Breakers
Standard Product Range
Auxiliary switches/fault signal contacts
for 5SY6 ...-.KV
3/28
Siemens ET B1 T · 2007 Benefits
An auxiliary switch or fault signal contact can be retrofitted to the
left-hand side of the circuit-breaker housing
Mounting with factory-fitted screws
Can be connected to instabus KNX EIB and AS-Interface bus or
PROFIBUS via binary inputs. Application
Auxiliary switches: indications of the circuit state of the miniature
circuit-breaker: ON/OFF
Fault signal contacts: signaling of electrical triggering, no signaling
of mechanical shut-down
Short-circuit protection ensured by miniature circuit-breakers of
characteristic B or C with
I
n
= 4 A or fuse gL 4 A
Product standards: IEC/EN 62019 (VDE 0640) Technical specifications Selection and ordering data Dimensional drawings
5ST3 018-0KV auxiliary switches/5ST3 028-0KV fault signal contacts
for 5SY6 . .-. KV miniature circuit-breakers. . .-.
I2_08258d
i n s t a b u s K N X E I B
RCBO
AS/FC
input
5ST3 018-0KV, 5ST3 028-0KV
Terminals
Conductor cross-section
mm
2
0.5 ... 2.5
Recommended tightening torque
Nm
0.6 ... 0.8
Min. contact load
50 mA/24 V
Max. contact load
230 V AC, AC-15
A
2
230 V AC, AC-13
A
3
110 V DC, DC-12
A
0.5
Version
MW
Order No.
Weight
1 unit
approx.
PS*
P. unit
kg
Unit(s)
Auxiliary switches (AS) for 5SY6 ...-.KV
1 NO + 1 NC
0.5
5ST3 018-0KV
0.037
1
Fault signal contacts (FC) for 5SY6 ...-.KV
2 W
0.5
5ST3 028-0KV
0.050
1
1 3
1 4
2 1
2 2
1 1
1 2 1 4
9 5
9 6 9 8
4564,5
6
917
45 80
I2
_0
86
25
* You can order this quantity or a multiple thereof.