VF and AR Series
Non-Cycling Refrigerated Compressed Air Dryers
Non-Cycling Refrigerated Compressed Air Dryers
iÉ~ÇáåÖ=íÜÉ=t~ó=áå=^áê=mìêáÑáÅ~íáçå
As one of the worlds leading manufacturers
of compressed air purification equipment, Donaldson
has built a comprehensive engineering, manufacturing, and customer support network to meet the most
demanding applications. With over 30 years of expertise in compressed air filtration and separation technologies,
Donaldson manufactures a complete line of drying and filtration equipment in an innovative design focused on
energy efficient operation and reliable performance. Our refrigerated dryer offering is split into two distinct
ranges: Donaldson offers a non-cycling and a cycling range of refrigerated dryers to meet all application
requirements.
Cycling range*
RFC Series (200 - 650 scfm)
DVF Series (800 - 2,000 scfm)
RTM Series (2,500 - 30,000 scfm)
Our non-cycling range
is focused on reliable, constant dew point performance in all flow conditions.
With its excellent heat transfer coefficients and low pressure drop, these dryers will outperform
the competition in protecting your compressed air system, machinery and tools; and will improve your
manufacturing processes.
Through optimization of the critical dryer components heat exchanger, separator and condensate removal
the Donaldson engineers developed a system that ensures highest performance at full- and partial-load
conditions to protect your application at all times.
Donaldson's high-efficiency
cycling range
is designed
to automatically cycle ON/OFF depending on the actual
load conditions.
Ozone-safe, 100% chlorine free, R-134a
refrigerant as standard
Donaldson uses R-134a refrigerant in all refrigerated
compressed air dryers as standard. R-134a has become
the industrys choice as the preferred refrigerant because
of its ozone depletion factor of 0.0 and low global warming
potential. R-134a is a one-blend refrigerant and, therefore,
consistent in performance (no temperature glide) and
easy to service (no mixture of different refrigerants).
All Donaldson dryers are designed to give our customers the best value available in the industry reliable
performance to CAGI ADF 100 specification while consuming the lowest amount of energy possible.
VF-150 to VF-300
* For more information on the Donaldson cycling dryers, please refer to respective brochure.
Non-cycling range
VF Compact Series (10 - 40 scfm)
VF Series (50 - 2,000 scfm)
AR Series (2,500 - 10,000 scfm)
Non-Cycling Refrigerated Compressed Air Dryers
Lightweight & compact.
Precooling and reheating of compressed air for
high efficiency and low energy consumption.
Patented Variable Flow high-efficiency
anonized aluminum heat exchanger utilizing
3-step process of Impaction, Brownian Motion,
and Surface Tension to achieve consistent
dew point at varying flow conditions.
Heat exchanger includes multi-stage separator
with removal (cleanable) stainless steel
mist eliminator.
Environmentally friendly refrigerant R-134a
ensures reliable operation in high ambient
overload conditions.
Donaldson VF Series dryers
offer highest
efficiencies at varying flow conditions in a lightweight,
compact design. No other dryer in the industry can
offer the efficiency ratings achieved by the VF Series
dryers in variable flow operation.
VF Series dryers are built with the patented Variable
Flow heat exchanger, which allows for desired dew
point performance regardless of flow variations.
Typically, other dryers with mechanical moisture
Features & Benefits
`çåëáëíÉåí=mÉêÑçêã~åÅÉ=Ñêçã=MJNMMB=iç~Ç
separators lose performance as compressed airflow
velocity increases or decreases substantially around
the nominal design point.
The VF Series high efficiency heat exchanger utilizes
a three-step process to thoroughly remove condensed
moisture from the chilled compressed air. This
process provides a separation efficiency in excess of
98% throughout the dryer's entire flow range
.
Refrigerant analyzer gauge.
Refrigerant discharge pressure gauge
(VF-200 and up).
Inlet pressure and temperature gauge
(VF-400 and up).
High efficiency scroll refrigeration
compressor (VF-500 and up).
Heavy-duty industrial powder coated
cabinet with access panel.
Optional dryer package filters sized for
each dryer (see page 4).
Aluminum Block Heat Exchanger
with integrated high efficiency separator
(VF-40 to VF-1200)
Stainless Steel Plate Heat Exchanger
(VF-10 to VF-25, VF-1400 to VF-2000)
1
Non-Cycling Refrigerated Compressed Air Dryers
Dimensions & Specifications
Model
Capacity
@ CAGI*
(scfm)
Capacity
@ ISO**
(scfm)
Connection
(inches NPT)
HP
Installed
(size)
KW
(full load)
Rated
Load
Amps
Voltage
(Standard)
Dimensions (inches)
Pressure
max.
(psig)
Weight
(lbs)
for CAGI
conditions
for ISO
conditions
Height
Width
Depth
VF-10
10
12
3/4
1/4
0.19
0.17
4.94
115-1-60
15
16
16
200
75
VF-15
15
18
3/4
1/4
0.19
0.17
4.94
115-1-60
15
16
16
200
75
VF-25
25
30
3/4
1/4
0.19
0.17
4.94
115-1-60
15
16
16
200
75
VF-40
40
47
3/4
1/4
0.19
0.17
4.94
115-1-60
18
22
15
200
75
VF-50
50
59
3/4
1/4
0.20
0.18
4.94
115-1-60
18
22
15
200
95
VF-60
60
71
3/4
1/3
0.30
0.28
7.20
115-1-60
18
22
15
200
118
VF-75
75
89
1
1/3
0.30
0.28
7.20
115-1-60
22
24
18
200
126
VF-100
100
118
1
1/2
0.50
0.48
10.20
115-1-60
22
24
18
200
132
VF-125
125
148
1
3/4
0.60
0.50
13.30
115-1-60
22
24
18
200
160
VF-150
150
177
1
3/4
0.60
0.50
13.30
115-1-60
22
24
18
200
175
VF-200
200
236
1-1/2
1
0.75
0.65
10.90
230-1-60
30
36
25
200
240
VF-250
250
295
1-1/2
1-1/2
1.12
1.00
4.70
460-3-60
30
36
25
200
360
VF-300
300
354
2
1-1/2
1.12
1.00
4.70
460-3-60
30
36
25
200
370
VF-400
400
472
2
2
1.50
1.45
5.10
460-3-60
45
34
45
200
660
VF-500
500
590
2
3
2.20
2.10
9.60
460-3-60
45
34
45
200
675
VF-600
600
708
3
3
2.60
2.50
9.60
460-3-60
45
34
45
200
710
VF-800
800
944
3
5
3.70
3.49
9.60
460-3-60
48
38
54
200
972
VF-1000
1000
1180
3
6
4.50
4.45
9.30
460-3-60
48
38
54
200
1160
VF-1200
1200
1416
3
6
4.50
4.45
9.30
460-3-60
48
38
54
200
1450
VF-1600
1600
1888
4 FLG
10
7.50
7.00
21.10
460-3-60
65
54
67
200
1625
VF-2000
2000
2360
4 FLG
13
9.70
9.00
25.00
460-3-60
65
54
67
200
2050
* Capacity rated in accordance with CAGI ADF 100 @ 100 psig, 100°F inlet, 100°F ambient, and a PDP of 38°F.
** Capacity rated in accordance with ISO 7183 @ 7 bar (101.5 psig), 35°C (95°F) inlet, 25°C (77°F) ambient and a PDP of 3°C (37.4°F).
Ambient air temperature: 35°-120°F, inlet air temperature: 140°F max., operating pressure: 200 psig max.
Hot, saturated compressed air is first
precooled by exiting cold air in the air-to-air
heat exchanger. The precooled air then enters
the evaporator where it is cooled to its final
dew point. The mixture of cold air and
condensation flows into the three-stage
separator/
mist eliminator where liquids and
contaminants are reliably removed and ejected
from the system via a programmable timer
drain valve. The cold air is then reheated by the
incoming hot air before leaving the dryer.
Air Inlet
Air Outlet
Air-to-Air
Heat Exchanger
Stainless Steel
Mist Eliminator
Separation Cell
Air -To-Refrigerant
Heat Exchanger
Refrigerant
Outlet
Refrigerant
Inlet
How the VF Heat Exchanger Works
2
VF-40 to VF-1200
Non-Cycling Refrigerated Compressed Air Dryers
3
Copper brazed stainless steel multi-plate heat
exchangers.
High-efficiency scroll refrigeration compressors
(up to 5,000 scfm).
The Donaldson AR Series
stands for reliability
and performance. Air-cooled and water-cooled
designs are available, along with a number of
customization options to exactly match the
application requirements.
Being the most efficient system in today's market,
these dryers are the preferred design in the highly
competitive automotive and industrial paint industry.
oÉäá~Äáäáíó=~åÇ=mÉêÑçêã~åÅÉ
Features & Benefits
AR-6500
How the AR Series Works
Refrigerant
Outlet
Air In
Air Out
Refrigerant
Inlet
Liquid
Receiver
Compressor
Suction
Accumulator
Fan Cycle Switch
Low Pressure Refrigerant
High Pressure Refrigerant
Refrigerant In
Thermostatic
Expansion
Valve
Hot Gas
By-Pass Valve
Air
Cooled
Condensor
Refrigerant Circuit
Compact Integrated
Stainless Steel Heat Exchanger
Warm gas enters the RECUPERATION
SECTION and exchanges heat with
the cooler leaving gas.
The gas then proceeds to the DRYER
SECTION and is cooled using
refrigeration to a designed dew point.
The gas then proceeds through a
specially designed MOISTURE
SEPARATOR SECTION, where
condensate drops out into the bottom
of the separator.
The gas then proceeds back through
the RECUPERATOR SECTION where
it is heated up by the incoming warm
gas.
Air-to-Air Recuperator
Air to Refrigerant
Heat Exchanger
Separator
High-efficiency discus refrigeration compressors
(from 6,000 scfm).
Environmentally friendly refrigerant R-134a
ensures reliable operation in high ambient
overload conditions.
Dryer Model
Prefilter
Afterfilter
VF-10 to VF-40
FF 3/4"
SMF 3/4"
VF-50 to VF-60
FF 3/4"
SMF 3/4"
VF-75 to VF-150
FF 1"
SMF 1"
VF-200 to VF-250
FF 1-1/2"
SMF 1-1/2"
VF-300 to VF-500
FF 2"
SMF 2"
VF-600 to VF-1200
FF 3"
SMF 3"
Non-Cycling Refrigerated Compressed Air Dryers
4
To protect your investment, we recommend that you
install a high performance prefilter directly in front of
your dryer. By doing this, you will not only ensure
trouble-free operation for years to come, but also
guarantee that the dryer will operate at its highest
efficiency rating thro