Wire Management & Marking Systems
Wire Management & Marking Systems
Wire Management
Electro-Duct Wiring Duct
Mounting slots
Standard at no extra charge on all sizes of duct. Two sizes of oblong mounting holes alternating on their own 2 inch centers. All 1 and 2 inch width duct have one row of slots along its center line. The 3 and 4 inch width duct have two rows of slots.
Design features for speed, easy installation and assembly.
Snap-Off Sidewall Fingers
Permits enlarging slot for lead-offs of any size wire and/or wire bundle; forms clean duct joints. Are pre-scored for smooth snap-off surfaces. REQUIRES NO TOOLS OR ANY CUTTING.
Type BA6
Description: Specially compounded high impact, rigid vinyl - won't peel, chip or crack; resists oils, grease, salt solutions, most midly concentrated acids, fungus; non-flammable, warp-proof, non-brittle; high dielectric and will withstand temperatures to 150癈. Easily cut to length - requires only a finetooth hand or power cutting tool for butt or mitred joints. Mechanical Properties Tensile strength: 4400 lbs/sq. in. Impact Resistance: 1.86 ft. lbs./sq. in. Coefficient of Thermal Expansion: . 2.5 x 10-5 m/m癋 Electrical Properties Dielectric Strength: 875 volts/mil Surface Resistivity: 1011 ohm Volume Resistivity: 1017 ohm cm. Relative Dielectric Constant: 3 Duct Capacity Guide
Maximum recommended number of wires used in various sizes of duct based on 50% fill capacity and derived fron the following formula: Duct W x H Number of wires = --------------------------------2 x (wire O.D.)2 This chart is a guide in selecting proper size duct. The amount may vary according to wire installation methods.
Thermal Properties Packaging: Standard length (6'6") 2 meter. Flammability: Self extinguishing UL94V-0 Sold as unit; Catalog number includes chanMaintains dimensional stability under nel and cover. . . heat: .65癈 i.e. .150癋 as per DIN standard #53458.
Colors: Available in Gray or White. For Gray - add suffix "G"; For White - add suffix "PW" to catalog number. (i.e. BA615015-PW)
Sizes, Dimensions, Ordering Data (Catalog Number includes cover):
Catalog Number
Dimensions (W x H) mm Nominal Inches Max. No. of 18 AWG at Capacity (mm2) Std. Pkg.
BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6 BA6
15015-(G or PW) 30015-(G or PW) 40015-(G or PW) 60015-(G or PW) 20025-(G or PW) 30025-(G or PW) 40025-(G or PW) 60025-(G or PW) 80025-(G or PW) 40040-(G or PW) 30040-(G or PW) 60040-(G or PW) 80040-(G or PW) 40060-(G or PW) 60060-(G or PW) 80060-(G or PW) 40080-(G or PW) 60080-(G or PW) 80080-(G or PW) 60100-(G or PW) 80100-(G or PW) 40120-(G or PW) 60120-(G or PW) 80120-(G or PW) 60150-(G or PW) 60200-(G or PW)
19 x 18 18 x 32 19 x 44 19 x 63 31 x 63 30 x 33 30 x 44 30 x 65 31 x 85 45 x 44 46 x 34 46 x 65 47 x 85 67 x 45 66 x 65 67 x 85 86 x 45 86 X 65 87 x 85 107 x 65 107 x 85 126 x 45 126 x 65 127 x 45 156 x 65 206 x 65
0.75 0.75 0.75 0.75 1.25 1.25 1.25 1.25 1.25 1.75 1.75 1.75 1.75 2.50 2.50 2.50 3.50 3.50 3.50 4.25 4.25 5.00 5.00 5.00 6.00 8.00
x 0.75 x 1.25 x 1.75 x 2.50 x 1.00 x 1.25 x 1.75 x 2.50 x 3.25 x 1.75 x 1.25 x 2.50 x 3.25 x 1.75 x 2.50 x 3.25 x 1.75 X 2.50 x 3.25 x 2.50 x 3.25 x 1.75 x 2.50 x 3.25 x 2.50 x 2.50
25 42 62 87 52 72 95 140 199 143 112 215 287 217 313 410 278 408 531 524 709 446 593 776 740 977
272 460 668 958 570 792 1056 1560 2108 1584 1250 2392 3196 2412 3432 4566 3096 4472 5916 5564 7900 4536 6552 8636 8112 10712
210 262 177 177 262 164 157 197 66 164 157 131 66 131 78 66 98 65 52 52 39 65 39 52 52 39
Meets JIC Requirements. U.S. Patent No. 908.985 Approved by CSA.
Wire Management
Type DNG
Description: Similar to BA6 but fingers are formed with wireretaining slots. Specifications: See previous page for information.
Sidewalls are prescored to permit enlarging slot for load-offs without the need for tools or cutting.
Catalog Number
Dimensions (W x H) Nominal Inches
Max. No. of Std. 18 AWG at Pkg. 50% Area Fill Ft.
DNG 20020-(G or PW) DNG 37020-(G or PW) DNG 50020-(G or PW) DNG 25025-(G or PW) DNG 50025-(G or PW) DNG 75025-(G or PW) DNG 25037-(G or PW) DNG 37037-(G or PW) DNG 50037-(G or PW) DNG 75037-(G or PW) DNG 50050-(G or PW) DNG 75050-(G or PW) DNG100050-(G or PW) DNG 50075-(G or PW) DNG 75075-(G or PW) DNG100075-(G or PW) DNG 50100-(G or PW) DNG 75100-(G or PW) DNG100100-(G or PW) DNG50125-(G or PW) DNG 75125-(G or PW)
(Catalog Number includes cover)
0.75 0.75 0.75 1.00 1.00 1.00 1.50 1.50 1.50 1.50 2.00 2.00 2.00 3.00 3.00 3.00 4.00 4.00 4.00 4.90 4.90
x x x x x x x x x x x x x x x x x x x x x
0.75 1.50 2.00 1.00 2.00 2.75 1.00 1.50 2.00 2.75 2.00 2.75 3.75 2.00 2.75 3.75 2.00 2.75 3.75 2.00 2.75
23 43 59 36 72 110 56 84 114 170 151 225 302 228 340 456 305 454 610 382 569
210 105 65 157 59 104 157 131 157 66 157 79 74 65 52 52 79 52 39 52 39
Type HNG - Noryl (Chlorine Free)
Description: For high temperature applications and where a chlorine-free environment is desired. Includes prescored snap-off fingers; snap-on/off cover design; and integral slotted mounting holes. Dimensions identical to DNG duct sizes shown above. Mechanical Properties Tensile strength: 9600 psi (675) kg/cm2 Impact resistance: 6.98 ft lbs/sq in. (