SINEAX Signal Conditioners
SINEAX Signal Conditioners
SINEAX Isolators
SINEAX Isolators
SINEAX T
SINEAX T
ransmitters
ransmitters
SINEAX Electrical Power T
SINEAX Electrical Power T
ransducers
ransducers
KINAX Position T
KINAX Position T
ransducers
ransducers
RHEIN
TACHO
New RheinT
New RheinT
acho
acho
Pr
Pr
ogrammable
ogrammable
Rotational Speed
Rotational Speed
Monitors
Monitors
SPEED API maintains a constant effort to upgrade and improve its products. Specifications
are subject to change without notice. Consult factory for your specific requirements.
202
-Camille Bauer
Div. of Absolute Process Instruments, Inc.
800-942-0315
www.apicb.com
Multi-Function Electrical Power Meters
Multi-Function Electrical Power Meters
Measure and Display
Voltage: U1, U2, U3, U12, U23, U31, max values
Current: I1, I2, I3, avg, max, avgmax values, Neutral current
Frequency: 40 to 70 Hz
Power Factor Cos

:: PF1, PF2, PF3, min values, PF , PF
min
Active Power (Watt): P1, P2, P3, max values, P , P
max
Reactive Power (VAR): Q1, Q2, Q3, max values, Q , Q
max
Apparent Power (VA): S1, S2, S3, max values, S , S
max
Active & Reactive Energy (Wh, VARh): all 4 quadrants
THD 1st-15th Harmonic, Voltage: U1, U2, U3
THD 1st-15th Harmonic, Current: I1, I2, I3
True RMS Measurements for Distorted Waveforms
Data Logging for up to 12 Variables - 63,000 values
Full DIN Size 144 x 144 mm
Active & Reactive Energy Digital Pulse Outputs
RS232/485 Interface, MODBUS-RTU Standard
LONWORKS or PROFIBUS-DP Interface Versions
2 or 4 Analog Outputs
2 Relay Outputs with Limit Setpoints
Adjustable CT & VT Ratios for Current & Voltage Inputs
Digital Input for Synchronization or Tariff Change
Specifications
Input
Single phase
3 phase 3-wire balanced, 4-wire balanced or unbal.
Phase to phase:
0 to 500 VAC max.
Phase to neutral:
0 to 290 VAC max.
Frequency:
40 to 70 Hz
Current:
0-1 A to 0-6 A
Synchronizing input: Internal or external
Sampling rate:
Adjustable, 300 ms to 30 min.
Recording duration: 1 minute to 4 days or continuous
Outputs
2 or 4 isolated analog outputs
2 digital pulse and 2 relay outputs
Accuracy
±0.25% for U and I, true RMS measurement
±0.5% for Power
±0.02% for Frequency
Display
Four 4-digit red LED displays, 14 mm H
Alphanumeric displays for units
Protection
IP 65 front panel
Dimensions
144 mm W x 144 mm H x 60 mm D
138 mm W x 138 mm H panel cutout
Order Codes
(115/230 VAC powered)
A2000-H0-A0-P1-R0-L0-U0-W1 2 Analog & 2 Pulse Outputs,
MODBUS
A2000-H0-A0-P1-R1-L0-U0-W1 2 Analog & 2 Pulse Outputs, Data
Logging, MODBUS,
A2000-H0-A1-P1-R0-L0-U0-W1 4 Analog & 2 Pulse Outputs,
MODBUS
A2000-H0-A1-P1-R1-L0-U0-W1 4 Analog & 2 Pulse Outputs, Data
Logging, MODBUS
Optional Versions

Please contact factory
DC powered, LONWORKS interface, PROFIBUS-DP interface
A2000
A2000
T
T
r
r
ue RMS Power System Measur
ue RMS Power System Measur
ement and Logging
ement and Logging
Highly Flexible
1 A or 5 A CT ratios, limit values, analog and pulse outputs
Event Monitoring
Datalogging option provides you with a clear-cut historical overview of causes
leading up to events
Cost-Effective Data
Monitor harmonic distortion to evaluate system quality
Communication Capabilities
RS 232 and MODBUS RTU are standard. PROFIBUS DP or LONWORKS inter-
faces available
Easy Operation
Separate keys for configuration and operation. Configuration values and readings
can be locked to prevent tampering
Electric Power
C
US 203
Electric
Power
-Camille Bauer
Div. of Absolute Process Instruments, Inc.
800-942-0315
www.apicb.com
Multi-Function Electrical Power
Multi-Function Electrical Power
Meters with System Analysis
Meters with System Analysis
MODBUSReg TM Schneider Electric, LONWORKSReg TM Echelon
Corporation, PROFIBUS logoReg TM PROFIBUS International
Cost Savings
One A230 or A230s replaces several instruments and associated power
transducers. You reduce planning, documentation and installation costs
Outstanding Visibility
Bright LED displays provide exceptional readability
Modular Design
Upgradeable with communications capabilities and data storage without
opening the instrument
Safety and Security
Configuration and meter readings can be locked to prevent tampering
Specifications
Input
Single phase
Three phase:
3- or 4-wire, balanced or unbalanced
4-quadrant operation
Phase to Phase:
0 to 500 VAC max.
Phase to Neutral:
0 to 290 VAC max.
Frequency:
45 to 65 Hz
Current:
0-1 A to 0-6 A
Variables
Programmable trip points or pulse rate, transformer ratio,
type of system, interval time for power average values.
Programming can be locked with jumper
Outputs
2 isolated programmable outputs
Use as digital pulse output or open collector alarm relay
Accuracy
U, I:
±0.2%
P, Q, S, PF, meters: ±0.5%
Frequency:
±0.02 Hz
Display
Three 4-digit red LED displays, 14 mm H
Alphanumeric displays for units
Variables can be configured to display sequentially
Protection
IP 66 front panel
Dimensions
A230s
96 mm W x 96 mm H x 46 mm D (69 mm D w. EMMOD)
92 mm W x 92 mm H panel cutout
A230
144 mm W x 144 mm H x 46 mm D (69 mm D w. EMMOD)
138 mm W x 138 mm H panel cutout
Order Codes
154 782
A230s power meter, 85-253 VAC/VDC powered
154 766
A230s power meter, 20-70 VAC/VDC powered
152 942
A230 power meter, 85-253 VAC/VDC powered
152 926
A230 power meter, 20-70 VAC/VDC powered
150 285
EMMOD 201 RS 485/232 interface, data logger module
with programming cable and A200 Plus software
154 055
DIN-rail adapter (can be used with EMMOD 201)
API 756
Power meter installed in NEMA 4 enclosure with
mounting bracket for 96 x 96mm power meters
154 055 DIN-rail adapter
with EMMOD 201
EMMOD 201 RS 485/232
interface & data logger
Measure and Display
Voltage: U1, U2, U3, U12, U23, U31, and min/max, N-E, N-E
max
,
U
avg
, U
avgmax
, unbalance factor, max unbalance factor
Current: I1, I2, I3, N, and max, I
avgmax
, I
avg
(bimetal/slave pointer)
Frequency: 45-65 Hz
Power Factor Cos

: (4-quadrant display) PF1, PF2, PF3, PF
avg
Power Factor: incoming/outgoing ind./cap. min.
Active Power (Watt): P1, P2, P3, and max, P
avg
, trend
Reactive Power (VAR): Q1, Q2, Q3, Q
avg
, trend
Apparent Power (VA): S1, S2, S3, S
avg
,, trend
Active & Reactive Energy (Wh, VARh): all 4 quadrants
THD Voltage: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
THD Current: 1, 2, 3
2nd-15th Harmonic, Voltage: 1-N, 2-N, 3-N, 1-2, 2-3, 3-1
2nd-15th Harmonic, Current: 1, 2, 3
Active and Reactive Energy Digital Pulse Outputs
Mean, Max., Min. Value Functions with Trend
Adjustable CT & VT Ratios for Current & Voltage Inputs
A230s ¼ DIN Size 96 x 96 mm
A230 Full DIN Size 144 x 144 mm
Order EMMOD for Input Synchronization, Tariff Change
Order EMMOD for MODBUS, 16,000 Point Data Logging
Measur
Measur
e Power System Parameters Including System Load and Har
e Power System Parameters Including System Load and Har
monics
monics
A230
A230
A230s
A230s API maintains a constant effort to upgrade and improve its products. Specifications
are subject to change without notice. Consult factory for your specific requirements.
204
-Camille Bauer
Div. of Absolute Process Instruments, Inc.
800-942-0315
www.apicb.com
Multi-Function Electrical Power Meters
Multi-Function Electrical Power Meters
Measure and Display
Voltage: U1, U2, U3, U12, U23, U31, min/max
Current: I1, I2, I3, avg, max, avgmax, Neutral current
Frequency: 45 to 65 Hz
Power Factor (Cos

): PF1, PF2, PF3, PF
Power Factor: incoming/outgoing ind./cap. minimum
Active Power (Watt): P1, P2, P3, P1
max
, P2
max
, P3
max
, P
max
Reactive Power (VAR): Q1, Q2, Q3, Q1
max
, Q2
max
, Q3
max
, Q
max
Apparent Power (VA): S1, S2, S3, S1
max
, S2
max
, S3
max
, S
max
Active & Reactive Energy (Wh, VARh): all 4 quadrants
Average Active, Reactive, and Apparent Power
Active and Reactive Energy Digital Pulse Outputs
Digital Input for Synchronization or Tariff Change Setting
Adjustable CT & VT Ratios for Current & Voltage Inputs
A210 ¼ DIN Size 96 x 96 mm
A220 Full DIN Size 144 x 144 mm
Optional MODBUS-RTU with Data Logging
A210
A210
Measur
Measur
e Power System Parameters
e Power System Parameters
A220
A220
Cost Savings
One A210 or A220 replaces several instruments and associated power
transducers. You reduce planning, documentation and installation costs
Outstanding Visibility
Bright LED displays provide exceptional readability
Modular Design
Upgradeable with communications capabilities and data storage without
opening the instrument
Safety and Security
Configuration and meter readings can be locked to prevent tampering
Specifications
Inp