AM201

der=0 cellpadding=7 cellspacing=0 width=100% bgcolor=ccccff> « back to results for ""
Below is a cache of http://www.mscontrols.com/am201.pdf. It's a snapshot of the page taken as our search engine crawled the Web.
The web site itself may have changed. You can check the current page or check for previous versions at the Internet Archive. Yahoo! is not affiliated with the authors of this page or responsible for its content.
AM201
FEATURES

q
Input Process value and Auto command
q
4 to 20 mA scaleable output
q
Dual digital display
q
Selectable auto or manual control
q
Operation and Calibration through keyboard
on front panel
q
IP54 protection

q
User friendly installation and operation



In many process control applications it is necessary to be able to control a device manually. Often a
potentiometer or rotary switch is used, but this method cannot be easily repeatable and it may be too
coarse. Micro Systems & Controls have designed a versatile and easy-to-use selection of manual
stations, using their auto manual station AM201. AM201 provides an automatic and manual analog
control output to process controllers, speed controllers and actuated devices. Input to the station can
be a manually set process value (4 to 20 mA) or auto command from higher end system. The input
signal automatically controls the analog output from the auto manual station to the controlled device in
the auto mode. If in any circumstances the input signal gets disrupted AM201 could be transferred to
the manual mode. AM201 returns back to auto mode by ramp up or ramp down at the programmed
rate-of-change when the input signal comes to its proper normal condition to provide bumpless transfer
between modes. Front panel control enables easy modification of system parameters. The digital
display for process value and output command value along with the LEDs for status indication of auto /
manual mode provides convenient monitoring of the signals.


SPECIFICATIONS:

Input power supply
Universal SMPS suitable for 95 to 265V AC and 110 to 300V DC
Input
1. Process Value of 4 to 20mA
2. Auto command from higher end system 4 to 20 mA
Display
§
4 digit 0.56 7 segment LED for Process Value
§
4 digit 0.39 7 segment LED for output in 0 100%
§
Individual status LEDs
Output
4 to 20 mA DC
1. In auto mode, input same as higher end system input
2. In manual mode, setting from front panel keys with separate slow and
fast mode operation
Load resistance
0 to 750 ohms
Accuracy
+/- 0.25% of span
Linearity
+/- 0.25% of span
Computational Feature
Square rooting of input signal selectable from the front panel

MICRO SYSTEMS & CONTROLS
Data Sheet No:
DS-932
Issue 01 Rev 01

AM201
PV
OP
RL1
RL2
MAN PROG
MICRO SYSTEMS & CONTROLS
SET
AM201
AUTO MANUAL STATION

www.mscontrols.com

ISO 9001:2000 Certified Company contd. specifications:

Response time
Better than 1 sec
Alarm output
2 no., 1 C/O contact relay output (optional)
Relay rating
3A / 230V AC resistive max.
ENCLOSURE

Enclosure
Flame Retardant ABS
IP Rating
IP54 (Front Panel)
Mounting type
Flush on panel
Panel
cutout
92
×
92 mm
Bezel
dimension
96
×
96 mm
Depth behind panel
125 mm including terminals
ENVIRONMENT

Operating temperature
0 to 60 Deg.C
Operating humidity
Up to 95% non condensing















ORDERING CODE:



MICRO SYSTEMS & CONTROLS
Ph: (033)-2416-3135 / 2416-8933 Fax: +91-33-2416-8933, +91-33-2416-3135
26 Lake East 4
th
Road Email: sales@mscontrols.com
Santoshpur, Kolkata 700075, India Web:
http://www.mscontrols.com

As product development is a continuous process, information in this catalog is subject to change without notice. 2005.07
9
3
2
-
0
0
0
-
0
0
AUTO MANUAL STATION
AM201
DIMENSIONS IN mm:

PANEL CUTOUT
96.00mm
96.00mm
125.00mm
92.00mm
92.00mm
SIDE VIEW
FRONT VIEW