GRM4
www.schurter.com/pg06
EMC products
"Lock and shield" mounting, line switch, fuseh. 5x20 mm with/without voltage sel. (series-parallel)
Snap-In Version
GRM4: with shield and line filter
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Snap-In Version from rear-side
- 5 Functions:
Inlet Protection class I, Line switch 2-pole, with or without Fuseholder
for fuse-links 5 x 20 mm, with or without voltage selector, Line filter in
standard and medical version
- On phase-out, not recommended for new design
Approvals
- VDE License Number: 118913
- UL License Number: E72928
- CSA License Number: 701867
Characteristics
- Ultra-compact design
Time saving "Lock and Shield" snap-in design for rear-panel mounting
- All single elements are already wired
- Fuseholder on the inside of the equipment prevents accidental use of
incorrect fuse-links by the user
- Voltage selector for two voltage ranges
Innovative EMC-shielding with flexible steel segments for an excellent
contact to the panel
- Insulation cover on the rear-side
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Panel thickness 1.0 / 2 / 2.5 mm (max.)
- Fuseholder 1-pole
- Line switch 1-pole
- Voltage selector with other marking
References
General Product Information
Weblinks
Approvals
,
RoHS
,
CHINA-RoHS
,
e-Store
,
SCHURTER-Stock-Check
,
Distributor-Stock-Check
Technical Data
Ratings IEC
0.5 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA
0.5 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp.
-25 °C to 85 °C
Climatic Category
25/085/21 acc. to IEC 60068-1
Degree of Protection
from front side IP 40 acc. to IEC 60529
Protection Class
Suitable for appliances with protection
class I acc. to IEC 61140
Terminal
Quick connect terminals 4.8 x 0.8 mm
Solder terminal on request
Solder terminals for voltage selector
Panel Thickness s
Snap-in: 1.5 mm
(other on request)
Material: Housing
Thermoplastic, black, UL 94V-0

Appliance-Inlet /-Outlet
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
condition) pin-temperature 70 °C, 10 A,
Protection class I
Fuseholder
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Power Acceptance @ Ta >
23°C
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Line Switch
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
Voltage selector
optional, jumper, 2 digits
Line Filter
Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
MTBF
> 1'400'000 h acc. to MIL-HB-217 F 
PHASE-OUT
Power entry modules with line filter
GRM4
www.schurter.com/pg06
EMC products
Dimensions
Length
48.3 mm
GRM4
49.5
33.9
24
5
31.7
45.2
6.5
30.4
8.4
38.4
45.4
1.7
12.5
2
42.3
R5
4.5
2.2
3.9
26.0
13.4
min.8
*)
E
8.6
S 0.05
PE
6.9
34.2
R1
7
40.9
±0.05
±0.1
+0.1 0
PE
L
N
±0.1
4.5
E = 31.7 mm with fuseholder
E = 26.25 mm without fuseholder
*) Min. space to remove the fuseholder cover
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [M
]
0.5
Standard Version
2 x 24
100
2.2
-
1
Standard
Version
2 x 12
100
2.2
-
3
Standard Version
2 x 2.5
100
2.2
-
6
Standard Version
2 x 0.78
100
2.2
-
10
Standard Version
2 x 0.225
100
2.2
-
0.5
Medical Version (M5)
2 x 24
100
-
1
1
Medical Version (M5)
2 x 12
100
-
1
3
Medical Version (M5)
2 x 2.5
100
-
1
6
Medical Version (M5)
2 x 0.78
100
-
1
10
Medical Version (M5)
2 x 0.225
100
-
1
Dimensions
Step 1
Place the socket in top edge of the panel
cut-out.
Step 2
Push the socket upwards.
Step 3
Push the socket forward into the panel
cut-out.
Step 4
Release the socket. The component is
self adjusting. 
PHASE-OUT
Power entry modules with line filter
GRM4
www.schurter.com/pg06
EMC products
Diagrams
Voltage selector
GRM4 Standard version
1) Line
2) Load
GRM4 Medical version
1) Line
2) Load
Derating Curves
1-pole
Admissible po
wer ac
-
ceptance in
W
a
tt
0
20
40
60
80
100
I = << I
n
I = 0.7 I
n
I = 1.0 I
n
2.0
1.5
1.0
0.5
0.0
Ambient air temperature Ta °C
2-pole
Admissible po
wer ac
-
ceptance in
W
a
tt per P
ole
0
20
40
60
80
100
0.2
0.0
I = << I
n
I = 0.7 I
n
I = 1.0 I
n
1.6
0.6
0.4
0.8
1.2
1.0
1.4
Ambient air temperature Ta °C
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
0.5 A
1 A
3 A
6 A
10 A
Medical version (M5)
0.5 A
1 A
3 A
6 A
10 A 4
PHASE-OUT
Power entry modules with line filter
GRM4
www.schurter.com/pg06
EMC products
Variants
Basic version:
- Marking of the voltage selector 115/230
- with housing and cover on the rear-side
Rated Current
[A]
Filter-Type
Fuseholder
Line Switch
Voltage selector
Order Number
6
Standard Version
-
1 pole
l
GRM4.4401.013
0.5
Standard Version
-
2-pole

GRM4.4102.013
0.5
Standard
Version
-
2-pole
l
GRM4.4102.123
1
Standard Version
-
2-pole
l
GRM4.4202.013
1
Standard Version
-
2-pole
l
GRM4.4202.123
3
Standard Version
-
2-pole
l
GRM4.4302.013
3
Standard Version
-
2-pole
l
GRM4.4302.123
6
Standard Version
-
2-pole
l
GRM4.4402.013
6
Standard Version
-
2-pole
l
GRM4.4402.123
Distributor-Stock-Check
|
SCHURTER-Stock-Check
|
e-Store
10
Standard Version
-
2-pole
l
GRM4.4502.013
10
Standard Version
-
2-pole
l
GRM4.4502.123
0.5
Standard Version
2-pole
2-pole
l
GRM4.4122.013
0.5
Standard Version
2-pole
2-pole
l
GRM4.4122.123
1
Standard Version
2-pole
2-pole
l
GRM4.4222.013
1
Standard Version
2-pole
2-pole
l
GRM4.4222.123
3
Standard Version
2-pole
2-pole
l
GRM4.4322.013
3
Standard Version
2-pole
2-pole
l
GRM4.4322.123
6
Standard Version
2-pole
2-pole
l
GRM4.4422.013
6
Standard Version
2-pole
2-pole
l
GRM4.4422.123
10
Standard Version
2-pole
2-pole
l
GRM4.4522.013
10
Standard Version
2-pole
2-pole
l
GRM4.4522.123
0.5
Medical Version (M5)
-
2-pole
l
GRM4.5102.013
0.5
Medical Version (M5)
-
2-pole
l
GRM4.5102.123
1
Medical Version (M5)
-
2-pole
l
GRM4.5202.013
1
Medical Version (M5)
-
2-pole
l
GRM4.5202.123
3
Medical Version (M5)
-
2-pole
l
GRM4.5302.013
3
Medical Version (M5)
-
2-pole
l
GRM4.5302.123
6
Medical Version (M5)
-
2-pole
l
GRM4.5402.013
6
Medical Version (M5)
-
2-pole
l
GRM4.5402.123
10
Medical Version (M5)
-
2-pole
l
GRM4.5502.013
10
Medical Version (M5)
-
2-pole
l
GRM4.5502.123
0.5
Medical Version (M5)
2-pole
2-pole
l
GRM4.5122.013
0.5
Medical Version (M5)
2-pole
2-pole
l
GRM4.5122.123
1
Medical Version (M5)
2-pole
2-pole
l
GRM4.5222.013
1
Medical Version (M5)
2-pole
2-pole
l
GRM4.5222.123
3
Medical Version (M5)
2-pole
2-pole
l
GRM4.5322.013
3
Medical Version (M5)
2-pole
2-pole
l
GRM4.5322.123
6
Medical Version (M5)
2-pole
2-pole
l
GRM4.5422.013
6
Medical Version (M5)
2-pole
2-pole
l
GRM4.5422.123
10
Medical Version (M5)
2-pole
2-pole
l
GRM4.5522.013
10
Medical Version (M5)
2-pole
2-pole
l
GRM4.5522.123
Packaging unit
120 Pcs
The specifications, descriptions and illustrations indicated in this document are based on