FNP300 AC-DC Power Supply Data Sheet

ata Sheet
12V, 24V, 48V Output, 300 Watts




Applications Telecommunications
equipment
Supply-Data-Sheet/' >
Features RoHS lead free solder and lead solder exempted
products are available Wide input voltage range 85-264 VAC Two outputs (one high current output) Low conducted and radiated EMI
(EN 55022 class B) UL recognized to UL 60950/CSA 22.2 No. 60950-00,
and TUV approved to EN 60950-1 High density design
4 x 1.65 x 8.5 cassette Highly-efficient
topology I
2
C interface Overtemperature, output overvoltage, and output
overcurrent protection Supervisory
signaling Included ORing diode for true redundant operation


Description
The FNP300 Series provides highly-efficient ac-dc power supplies, each with one high current output and an
additional standby output, which can be used in a wide range of applications. Passive current share along with
internal ORing diodes allow the FNP300's to be also used in redundant, hot-swap applications. All models meet
international safety standards and display the CE Mark for the low Voltage Directive.


Model Selection
Output 1
Output 2
Model Input
Voltage
VAC
V
o nom

VDC
I
o max

ADC
V
o nom

VDC
I
o max

ADC
Rated Power
W
FNP300-1012
85-264
12 25 12 0.7 310
FNP300-1024
85-264 24 12.5 12 0.7 310
FNP300-1048
85-264 48 6.25 12 0.7 310



Ordering Information

Options
Suffixes to Add to Part Number
RoHS lead solder exemption
No RoHS character required.
RoHS compliant for all 6 substances
Add "G" as the last character of the part number.

BCD20015-G REV. AA
Page 2 of 6
www.power-one.com
FNP300 AC-DC Power Supply Data Sheet
12V, 24V, 48V Output, 300 Watts
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings may cause performance degradation, adversely effect long-
term reliability, and cause permanent damage to the converter.

Parameter Conditions/Description
Min
Max
Units
Input Voltage
Continuous
Transient, 60 ms

264
300
VAC
VAC
Operating Temperature
Ambient
V
i min
-V
i max
, I
o nom
, cooling by internal fan
0 55 °C
Storage Temperature
Non-operational -40
85
°C

Environmental, Mechanical, & Reliability Specifications
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Conditions/Description Min
Nom
Max
Units
Operating Humidity
Relative humidity, non-condensing
10

90
%
Storage Humidity
Relative humidity, non-condensing
5

95
%
Shock
IEC/EN 60068-2-27, 11 ms


30
g
n

Sinusoidal Vibration
IEC/EN 60068-2-6
2-8 Hz
8-200 Hz
200-500 Hz


7.5
2
4


mil
g
n
g
n

MTBF
MIL-HDBK-217F Notice 2, G
B
, 25 °C
200


kh

Isolation Specifications
The electric strength test is performed in the factory as routine test in accordance with EN 550116, IEC/EN 60950,
and UL 1950 and should not be repeated in the field. Power-One will not honor any warranty claims resulting from
electric strength field tests.

Parameter Conditions/Description Min
Nom
Max
Units
Insulation Safety Rating
Input/Case
Input/Output
Output/Case
Basic
Reinforced
Functional

Electric Strength Test Voltage
Input/Case
Input/Output
Output/Case
2.121
4.2
0.5


kVDC
kVDC
kVDC

EMC Specifications
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Description Criterion
Electrostatic Discharge
IEC/EN 61000-4-2, level 4 (contact/air)
8/15 kV, criterion B
Electromagnetic Field
IEC/EN 61000-4-3, level 3
10 V/m, criterion A
Eletr. Fast Transients / Burst
IEC/EN 61000-4-4, level 4 (direct/capacitive)
2/1 kV, criterion B
Surge
IEC/EN 61000-4-5, level 3 (L/L, L/C)
1/2 kV, criterion B
Voltage Dips and Interruptions
IEC/EN 61000-4-11
Criterion B
RF Conducted Immunity
IEC/EN 61000-4-6
10 VAC, AM 80%, 1 kHz,
criterion A
Emissions Radiated/Conducted
CISPR 22/EN 55022/EN 61204
Class B
Harmonics
IEC/EN 61000-3-2
Class B
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Pass

BCD20015-G REV. AA
Page 3 of 6
www.power-one.com
FNP300 AC-DC Power Supply Data Sheet
12V, 24V, 48V Output, 300 Watts

Input Specifications
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Conditions/Description Min
Nom
Max
Units
Input Voltage

85
115/230 264
VAC
Turn-On Input Voltage
Ramping up
70
-
85
VAC
Turn-Off Input Voltage
Ramping down
70
-
85
VAC
Input
Frequency

47 50/60 63 Hz
Inrush Current Limitation
115/230 VAC


15/20
A
Power Factor
V
i nom
, I
o nom


0.96

Efficiency

V
i
= 230 VAC, I
o nom
FNP300-1012

FNP300-1024

FNP300-1048
83
86
88



%

Output Specifications
All specifications apply over specified input voltage, output load, and temperature range unless otherwise noted.

Parameter Conditions/Description Min
Nom
Max
Units
Output Voltage Setpoint Accuracy
FNP300-1012
V
i
= 230 VAC, I
o1
@ 12.5 ADC, T
C
= 25 °C
-0.5

0.5. % V
o nom
Output Voltage Setpoint Accuracy
FNP300-1024
V
i
= 230 VAC, I
o1
@ 3.125 ADC, T
C
= 25 °C
-0.5

0.5. % V
o nom
Output Voltage Setpoint Accuracy
FNP300-1048
V
i
= 230 VAC, I
o1
@ 12.5 ADC, T
C
= 25 °C
-0.5

0.5. % V
o nom
Output Current V1
Output Current V2
FNP300-1012
FNP300-1012
0
0
25
0.7
25
0.7
ADC
ADC
Output Current V1
Output Current V2
FNP300-1024
FNP300-1024
0
0
12.5
0.7
12.75
0.7
ADC
ADC
Output Current V1
Output Current V2
FNP300-1048
FNP300-1048
0
0
6.25
0.7
6.4
0.7
ADC
ADC
Static Line Regulation V1
V
i min
-V
i max
, V
i nom
, 5-100% I
o nom

-0.5

0.5
% V
o nom
Static Load Regulation V1
(Droop Characteristic)
V
i min
-V
i max
, V
i nom
, 5-100% I
o nom
-5

5
%
V
o nom
Hold-Up Time
Starting at V
i
= 230 VAC, P
o nom

20


ms
Dynamic Load Regulation
Load change =
±
33%, dI
o
/dt = 2A/ s
voltage deviation
recovery time

-2


2
400

% V
o nom s
Start-Up Time
V
i nom
, I
o nom


1
s
Output Voltage Ripple and Noise
V
i nom
, I
o nom
, 20 MHz bandwidth


120
mVpp

BCD20015-G REV. AA
Page 4 of 6
www.power-one.com
FNP300 AC-DC Power Supply Data Sheet
12V, 24V, 48V Output, 300 Watts

Protection
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Conditions/Description Min
Nom
Max
Units
Input Fuse
Not user accessible
6.3AT
Input Transient Protection
With varistor




Output
No-load and short circuit proof
short circuit proof
overload (latch style)


110



130
% I
o nom
% I
o nom
% I
o nom
Overvoltage Protection
Latch style
FNP300-1012
Latch style
FNP300-1024
Latch style
FNP300-1048
115
115
115

130
130
122
% V
o nom
% V
o no
% V
o no
Overtemperature Protection
Automatic power shutdown at T
C
= 95 °C





Control
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Conditions/Description
I
2
C Digital Bus

Reports information and monitors alarm functions
PS Seated Signal
Contact closure to GND
PS Remote Shutdown
TTL compatible signal, open collector. Power supply enabled at Low or TTL "0"
(e.g. by connecting of pin 22 to 0V or GND), and
inhibited to latching mode** at High or TTL "1", or leave it open.
AC fail pre-warning (I
2
C & OC)*
Supervisory AC input voltage;
Pre-warning time >6 ms
DC fail (I
2
C & OC)*
Supervisory under- and overvoltage pre-ORing diode of V1
Temperature Warning (I
2
C & OC)*
Indicates if unit is operating normally or in overtemperature,
Pre-warning time >10 ms
Fan OK (I
2
C & OC)*
Indicates if fan is operating or has failed
Current Share
Droop load characteristic for V1 and V2
Status Indication
LEDs: DC OK (green), AC OK (green)

* Signal provided by I
2
C interface or by open collector (OC)
** (1) Standard FNP300 models (without "H" at the end of part number) have latching inhibit function, i.e., once PSU is
inhibited, it needs input power re-cycle to allow using enable state again.
(2) FNP300 variants marked with "H" character do have non-latching inhibit function so there's no need to
re-cycle input power when enabling unit after inhibit state.
Supply-Data-Sheet/' >
Features
All specifications apply over specified input voltage, output load, and temperature range, unless otherwise noted.

Parameter Conditions/Description
Fan speed control

4 fan speed levels depending on inlet temperature
Fan speed level and temperature information available on I
2
C digital bus
µC supply voltage in-/output
(Pin 10)
If unit is operating: 5 to 7V is provided at pin 10.
If unit is NOT operating, pin 10 is input from a parallel connected unit for µC supply.

BCD20015-G REV. AA
Page 5 of 6
www.power-one.com
FNP300 AC-DC Power Supply Data Sheet
12V, 24V, 48V Output, 300 Watts

Characteristic Curves:

Figure 1. Efficiency vs. Output Load




Figure 2. Efficiency vs. Input Voltage and Ambient Temperature, I
o
= I
o nom


BCD20015-G REV. AA
Page 6 of 6
www.power-one.com
FNP300 AC-DC Power Supply Data Sheet
12V, 24V, 48V Output, 300 Watts
Mechanical Data
Mechanical Data (H, W, D)
4 (101.6mm) x 1.65 (41.9mm) x 8.5 (215.9mm)



Weight: 2.205 lb (1 kg)
Output Connector Descriptions

PIN 1
PIN 13



Rear View

Connector: Molex (15-06-0241)

Output Connector
Description
Pin
Location
Reference
Name