Power Generation for the 21st Century
ble>
Power Generation for the 21st Century
Power Generation for the 21st Century
®
A Subsidiar y of Regal-Beloit Cor poration
ISO 9002 Certified
Generator Ratings:
118 to 2370
(60 Hertz)
136 to 2400
(50 Hertz)
kW
kVA
S
ince its market introduction, Marathon Electrics
MAGNAMAX
DVR®
has been a technology leader and proven performer. The
MAGNAMAX
DVR®
generator line offers as standard a permanent magnet generator excitation
system with the industrys first digital voltage regulator.
Each
MAGNAMAX
DVR®
features the exclusive DVR
®
2000 digital voltage
regulator providing .25% regulation and three phase RMS sensing.
These outstanding features make
MAGNAMAX
DVR®
the ideal generator for
voltage critical applications such as:
Telecommunication Networks
Hospitals
Airports
Commercial Buildings
Computer Centers
i n n o v a t i o n ,
A
proven, top performer in every
respect, the
MAGNAMAX
DVR®
generator is a result of Marathon
Electrics fifty years of generator
experience and an intensive product
development program using cutting
edge technology. Inherent to the
MAGNAMAX
DVR®
design is excep-
tional transient performance and
strong motor starting capability.
MAGNAMAX
DVR®
meets the demands
of todays changing market offering
reliability and remarkable perform-
ance. The
MAGNAMAX
DVR®
supports
a variety of non-linear loads. Typical
non-linear loads include UPS sys-
tems and variable frequency drives.
MAGNAMAX
DVR®
provides unprece-
dented voltage regulation in the
presence of harmonic distortion
caused by non-linear loads.
Furthermore, the
MAGNAMAX
DVR®
low reactance design minimizes the
harmonic voltage distortion caused
by these loads.
Constructed for extended life,
MAGNAMAX
DVR®
utilizes Marathons
exclusive unirotor construction,
superior class H insulation, and long
life bearings.
Easy access and serviceability
combined with Marathon Electrics
commitment to long term support
make
MAGNAMAX
DVR®
the
ideal choice for extended life
applications.
Permanent Magnet
Generator...
ensures 300% short
circuit current during fault conditions
and provides the regulator with input
power isolated from load distortions.
Unirotor Construction...
incorporates single piece rotor lami-
nations, a die cast rotor core and
ammortiseur windings into an inte-
grated rotor assembly. The field
winding is wet layer wound to the
rotor assembly with thermo setting
epoxy for high mechanical and elec-
trical integrity.
Digital Voltage Regulator...
is encapsulated for reliable perform-
ance in all environments. The
DVR
®
2000 includes voltage regula-
tion to .25%, three phase RMS
sensing, adjustable volts/hertz
underspeed protection, advanced
engine unloading algorithms, inte-
grated paralleling capabilities, and
over-excitation/over-voltage protec-
tion. A VAR-PF controller is avail-
able as an optional feature.
Large Conduit Box...
provides
ample space for easy connections
and allows load line access from all
sides, top, or bottom.
Exciter and PMG
Mounting...
provides easy
access and serviceability. The PMG
is mounted external to the generator
bearing. The exciter is externally
mounted on 570 and 740 frame
generators.
Class H Insulation System...
utilizes an unsaturated polyester
varnish for optimal insulation life
and superior moisture protection.
A tropical insulation is added for
increased environmental protection.
A vacuum pressure impregnated
insulation system is an available
option.
Shielded Heavy-Duty
Bearings...
resist contamination
and give a minimum B-10 life of
40,000 hours. Regreasing provisions
are available on all generators.
Enhanced Ventilation...
created by a high efficiency fan and
optimized internal air flow patterns,
maximizes heat transfer and mini-
mizes hot spot differentials for
extended winding life.
Fully Guarded...
for operator
safety and generator protection, no
rotating or electrically energized
parts are exposed. All openings are
covered by louvers or screens.
Optimized Windings...
provide
low reactances and exceptional
motor starting capability. The stator
windings utilize a 2/3 pitch to mini-
mize harmonic distortion and facili-
tate parallel operation.
Design Specs and
Agency Approvals...
are impor-
tant at Marathon. All MAGNAMAX
DVR®
units meet NEMA MG1-22, BS5000,
CSA C22.2, IEC 34-1 and VDE 0530
requirements. Marine versions are
available to meet American Bureau
of Shipping, Lloyds, Det Norske
Veritas, or Nippon Kaiji Kyokai
requirements.
p e r f o r m a n c e , r e l i a b i l i t y. . .
F e a t u r e s
Product
®
‚
All ratings are based upon
NEMA rise by resistance.
ƒ
12 Lead
„
10 or 12 Lead
…
4 Lead
†
4 Bars or 12 Lead
‡
4 Bars
kW
ratings
60 Hertz
Three Phase, Low Voltage
4, 10 and 12 Leads
1800 RPM
0.8 Power Factor
40°C Ambient
kW
ratings
1800 RPM
0.8 Power Factor
40°C Ambient
kW Ratings at 4160 Volts
‚
Model
Class B
Class F
Class H
Number
Cont. 80°C
Cont. 105°C
Stby. 130°C
Cont. 125°C Stby. 150°C
573FSM4352
315
400
415
415
460
573FSM4354
350
450
500
500
530
574FSM4356
465
600
625
625
700
574FSM4358
550
710
760
760
840
741FSM4360
730
900
925
925
930
742FSM4364
925
1120
1200
1200
1200
742FSM4366
1120
1360
1450
1450
1450
743FSM4368
1240
1520
1600
1600
1610
743FSM4370
1370
1680
1800
1800
1800
744FSM4374
1525
1875
2050
2050
2050
60 Hertz
Three Phase, Medium Voltage
6 Leads
kW Continuous Duty
‚
kW Standby Duty
‚
Model
Class B 80°C
Class F 105°C
Class H 125°C
Class F 130°C
Class H 150°C
Number
480Y/240Y 416Y/208Y 480Y/240Y 416Y/208Y 480Y/240Y 416Y/208Y 480Y/240Y 416Y/208Y 480Y/240Y 416Y/208Y
431RSL4005
ƒ
126
118
145
132
154
138
155
138
160
138
431RSL4007
ƒ
140
132
165
150
175
160
175
160
185
168
432RSL4009
ƒ
172
166
203
187
215
200
215
200
226
200
432RSL4011
ƒ
192
183
221
207
231
219
231
221
250
221
432RSL4013
ƒ
200
193
235
219
250
231
250
235
263
250
432RSL4015
ƒ
230
232
275
262
285
262
285
262
300
262
432RSL4017
ƒ
230
238
275
275
292
287
300
287
310
310
433RSL4019
ƒ
305
290
350
325
375
350
375
350
415
360
433RSL4021
ƒ
330
305
380
345
405
365
405
370
440
400
572RSL4024
„
380
385
450
435
475
440
475
440
505
450
572RSL4027
ƒ
440
400
500
445
515
470
515
475
560
505
572RSL4028
„
445
450
535
510
560
525
560
525
610
535
572RSL4030
„
485
460
575
525
600
555
600
565
645
600
573RSL4032
„
570
570
680
650
700
685
700
700
765
725
573RSL4034
„
585
590
710
680
750
720
750
725
810
725
574RSL4036
„
670
630
800
725
825
770
825
785
900
825
741RSL4045
ƒ
865
810
1030
920
1080
970
1100
1000
1100
1020
The following are single voltage 416Y 480Y only
574RSL4038
…
720
675
860
770
915
820
920
835
970
885
575RSL4044
‡
800
760
975
890
1050
950
1060
975
1130
1040
740RSL4046
‡
950
880
1120
1020
1200
1090
1220
1110
1250
1180
742RSL4048
†
1000
950
1200
1100
1260
1160
1300
1180
1300
1250
743RSL4050
‡
1220
1110
1430
1270
1500
1340
1500
1370
1520
1410
743RSL4052
‡
1310
1400
1600
1610
1700
1610
1750
1610
1750
1620
744RSL4054
‡
1500
1420
1850
1680
1960
1800
2000
1840
2000
1840
744RSL4058
‡
1760
1640
2100
1920
2270
2050
2320
2090
2370
2240
Form wound coil designs single voltage 416Y 480Y volts only
744FSL4060
‡
1200
1190
1430
1380
1500
1440
1500
1440
1500
1440
744FSL4062
‡
1500
1510
1800
1750
1900
1830
1900
1830
1900
1830
‚
All ratings are based upon
NEMA rise by resistance.
ƒ
12 lead
„
10 or 12 lead
…
4 lead
†
4 Bars or 12 lead
‡
4 Bars
kVA
ratings
1500 RPM
0.8 Power Factor
40°C Ambient
kVA
ratings
1500 RPM
0.8 Power Factor
40°C Ambient
50 Hertz
Three Phase, Low Voltage
4, 10 and 12 Leads
50 Hertz
Three Phase, Medium Voltage
6 Leads
kVA Continuous Duty
‚
kVA Standby Duty
‚
Model
Class F 105°C
Class H 125°C
Class F 130°C
Class H 150°C
Number
415Y/208Y
380Y/190Y
415Y/208Y
380Y/190Y
415Y/208Y
380Y/190Y
415Y/208Y
380Y/190Y
431RSL4005
ƒ
136
141
145
149
148
150
151
159
431RSL4007
ƒ
155
159
164
168
168
170
173
180
432RSL4009
ƒ
189
208
203
219
206
223
214
224
432RSL4011
ƒ
208
218
221
231
225
235
234
243
432RSL4013
ƒ
231
233
244
244
250
250
255
254
432RSL4015
ƒ
253
276
275
294
279
300
290
300
432RSL4017
ƒ
258
281
278
298
283
303
294
314
433RSL4019
ƒ
338
356
363
375
363
375
394
406
433RSL4021
ƒ
366
369
394
394
400
400
413
425
572RSL4024
„
413
469
444
500
456
500
475
506
572RSL4027
ƒ
469
475
500
500
513
513
531
544
572RSL4028
„
500
550
531
588
544
594
563
600
572RSL4030
„
550
563
581
600
600
613
625
644
573RSL4032
„
650
700
700
750
713
756
738
775
573RSL4034
„
669
738
713
781
731
800
756
819
574RSL4036
„
731
769
788
819
800
831
838
888
741RSL4045
ƒ
969
1000
1038
1056
1038
1075
1106
1144
The following are single voltage 380Y 415Y only
574RSL4038
…
825
831
888
888
906
900
938
956
575RSL4044
‡
963
963
1013
1031
1025
1056
1056
1138
740RSL4046
‡
1106
1125
1188
1200
1219
1219
1275
1300
742RSL4048
†
1131
1181
1219
1250
1219
1263
1300
1338
743RSL4050
‡
1438
1363
1538
1463
1538
1500
1638
1563
743RSL4052
‡
1500
1650
1600
1775
1600
1775
1725
1850
744RSL4054
‡
1725
1750
1875
1875
1875
1913
2013
1988
744RSL4058
‡
2038
2013
2225
2150
2288
2188
2400
2337
Form wound coil designs single voltage 380Y 415Y volts only
744FSL4060
‡
1425
1450
1550
1563
1550
1563
1650
1650
744FSL4062
‡
1750
1725
1900
1875
1900
1875
2025
1963
kVA Ratings at 3300 Volts
‚
Model
Class B
Class F
Class H
Number
Cont. 80°C
Cont. 105°C
Stby. 130°C
Cont. 125°C Stby. 150°C
573FSM4352
350
425
469
456
488
573FSM4354
388
475
531
519
550
574FSM4356
500
625
681
663
706
574FSM4358
588
731
806
788
838
741FSM4360
769
913
981
981
1038
742FSM4364
963
1156
1250
1250
1325
742FSM4366
1163
1400
1500
1500
1600
743FSM4368
1300
15