Basic Characteristics Data
Basic Characteristics Data
Basic Characteristics Data
Model
Input module of ACE300F Input module of ACE450F Input module of ACE650F Input module of ACE900F Output module A-K Output module 2A-2K Output module L,M,N,P,R Output module Y,W,Z,9,Q,V Output module S,T,U
Circuit method Active filter Active filter Active filter Active filter Forward converter Forward converter Forward converter Forward converter Forward converter
Switching frequency Input current [kHz] [A] 80 80 80 80 120 120 120 120 120 3.7*1 5.7*2 8.0*3 11*4 -
Rated input fuse 250V 8A 250V 10A 250V 15A 250V 20A -
Series/Parallel PCB/Pattern Inrush current operation availability protection Material Single sided Double sided Series operation Parallel operation
SCR SCR SCR SCR -
FR-4 FR-4 FR-4 FR-4 FR-4 FR-4 FR-4 FR-4 FR-4
Yes Yes Yes Yes Yes Yes Yes Yes Yes
No No No No
No No No No
Yes*5 Yes*7 Yes*5 Yes*7 Yes*5 Yes*6 Yes*6 No No No
ACE
*1 *2 *3 *4 *5 *6 *7
Input current is based on Model AC3-HEEC-00 outputs 250W at AC100V. Input current is based on Model AC4-HHECC-00 outputs 400W at AC100V. Input current is based on Model AC6-HHECC-00 outputs 600W at AC100V. Input current is based on Model AC9-HHEECC-00 outputs 800W at AC100V. Series operation is possible with the same output modules. Series operation is possible, but series bar cannot be set by the series code. Parallel operation is possible with the same output voltage module.
C-10
ACE300F
RISE TIME & FALL TIME
+24V(H) DC Output
OUTPUT VOLTAGE [V]
20.0
OVER CURRENT CHARACTERISTICS
25.0
+24V(H) ACIN 100V IO = 100%
+12V(E) +5V(C) +3.3V(B) AC Input
15.0
10.0
+12V(E) +5V(C)
5.0
+3.3V(B)
100ms/DIV
10ms/DIV
0
10
20
30
40
OUTPUT CURRENT [A]
INSTANTANEOUS INTERRUPTION COMPENSATION (AC3-HEEC-00)
INSTANTANEOUS COMPENSATION [ms]
INRUSH CURRENT (AC3-HEEC-00)
10A/DIV
ACE
INPUT VOLTAGE 100V
75
50
Frequency 60Hz Load factor 100% Input voltage AC100V
25
0
100
200
300
50ms/DIV
OUTPUT POWER [W]
INPUT HARMONIC CURRENT AC100V (AC3-HEEC-00)
10
INPUT HARMONIC CURRENT AC230V (AC3-HEEC-00)
10
HARMONIC CURRENT [A]
1
Output power 250W Input voltage AC100V
HARMONIC CURRENT [A]
Harmonic current standard class A (at odd number)
Harmonic current standard class A (at odd number)
1
Output power 300W Input voltage AC230V
0.1
0.1
0.01
0.01
0.001 0 10 20 30 40
0.001 0 10 20 30 40
HARMONIC ORDER
HARMONIC ORDER
POWER FACTOR & INPUT CURRENT (AC3-HEEC-00)
1.0 8 7 0.9 6 5
EFFICIENCY (AC3-HEEC-00)
85.0
INPUT CURRENT [A]
POWER FACTOR
POWER FACTOR
80.0
0.8
EFFICIENCY [%]
INPUT CURRENT
4 0.7
75.0
Output power 250W Output power 125W
3 2
70.0
0.6 1 0.5 60 0 300
65.0
Output power 250W Output power 125W
60.0 60 100 140 180 220 260 300
100
140
180
220
260
INPUT VOLTAGE [V]
INPUT VOLTAGE [V]
C-11
ACE450F
RISE TIME & FALL TIME
+24V(H) DC Output
OUTPUT VOLTAGE [V]
20.0
OVER CURRENT CHARACTERISTICS
25.0
+24V(H) ACIN 100V IO = 100%
+12V(E) +5V(C) +3.3V(B) AC Input
15.0
10.0
+12V(E) +5V(C)
5.0
+3.3V(B)
100ms/DIV
10ms/DIV
0
10
20
30
40
OUTPUT CURRENT [A]
INSTANTANEOUS INTERRUPTION COMPENSATION (AC4-HHECC-00)
INRUSH CURRENT (AC4-HHECC-00)
10A/DIV
ACE
INSTANTANEOUS COMPENSATION [ms] INPUT VOLTAGE 100V
75
50
Frequency 60Hz Load factor 100% Input voltage AC100V
25
0
100
200
300
400
50ms/DIV
OUTPUT POWER [W]
INPUT HARMONIC CURRENT AC100V (AC4-HHECC-00)
10
INPUT HARMONIC CURRENT AC230V (AC4-HHECC-00)
10
HARMONIC CURRENT [A]
1
Output power 400W Input voltage AC100V
HARMONIC CURRENT [A]
Harmonic current standard class A (at odd number)
Harmonic current standard class A (at odd number)
1
Output power 450W Input voltage AC230V
0.1
0.1
0.01
0.01
0.001 0 10 20 30 40
0.001 0 10 20 30 40
HARMONIC ORDER
HARMONIC ORDER
POWER FACTOR & INPUT CURRENT (AC4-HHECC-00)
1.0 8 7 0.9
EFFICIENCY (AC4-HHECC-00)
85.0
POWER FACTOR
POWER FACTOR
0.8
6 5
INPUT CURRENT [A]
80.0
EFFICIENCY [%]
75.0
INPUT CURRENT
0.7
4 3 2
70.0
0.6
65.0
Output power 400W Output power 200W
0.5 60 100 140 180 220 260
1 0 300 60.0 60
Output power 400W Output power 200W
100 140 180 220 260 300
INPUT VOLTAGE [V]
INPUT VOLTAGE [V]
C-12
ACE650F
RISE TIME & FALL TIME
+24V(H) DC Output
OUTPUT VOLTAGE [V]
20.0
OVER CURRENT CHARACTERISTICS
25.0
+24V(H) ACIN 100V IO = 100%
+12V(E) +5V(C) +3.3V(B) AC Input
15.0
10.0
+12V(E) +5V(C)
5.0
+3.3V(B)
100ms/DIV
10ms/DIV
0
10
20
30
40
OUTPUT CURRENT [A]
INSTANTANEOUS INTERRUPTION COMPENSATION (AC6-HHECC-00)
INSTANTANEOUS COMPENSATION [ms]
INRUSH CURRENT (AC6-HHECC-00)
20A/DIV
ACE
INPUT VOLTAGE 100V
75
50
Frequency 60Hz Load factor 100% Input voltage AC100V
25
0
200
400
600
800
50ms/DIV
OUTPUT POWER [W]
INPUT HARMONIC CURRENT AC100V (AC6-HHECC-00)
10
INPUT HARMONIC CURRENT AC230V (AC6-HHECC-00)
10
HARMONIC CURRENT [A]
1
Output power 600W Input voltage AC100V
HARMONIC CURRENT [A]
Harmonic current standard class A (at odd number)
Harmonic current standard class A (at odd number)
1
Output power 650W Input voltage AC230V
0.1
0.1
0.01
0.01
0.001 0 10 20 30 40
0.001 0 10 20 30 40
HARMONIC ORDER
HARMONIC ORDER
POWER FACTOR & INPUT CURRENT (AC6-HHECC-00)
1.0 12 10
EFFICIENCY (AC6-HHECC-00)
84.0 82.0
0.9
POWER FACTOR
POWER FACTOR
8 0.8
INPUT CURRENT [A]
EFFICIENCY [%]
80.0
INPUT CURRENT
0.7
78.0
6
76.0
4 0.6
74.0
Output power 600W Output power 300W
0.5 60 100 140 180 220 260
2
72.0
Output power 600W Output power 300W
100 140 180 220 260 300
0 300
70.0 60
INPUT VOLTAGE [V]
INPUT VOLTAGE [V]
C-13
ACE900F
RISE TIME & FALL TIME
+24V(H) DC Output
OUTPUT VOLTAGE [V]
20.0
OVER CURRENT CHARACTERISTICS
25.0
+24V(H) ACIN 100V IO = 100%
+12V(E) +5V(C) +3.3V(B) AC Input
15.0
10.0
+12V(E) +5V(C)
5.0
+3.3V(B)
100ms/DIV
10ms/DIV
0
10
20
30
40
OUTPUT CURRENT [A]
INSTANTANEOUS INTERRUPTION COMPENSATION (AC9-HHEECC-00)
INRUSH CURRENT (AC9-HHEECC-00)
20A/DIV
ACE
INSTANTANEOUS COMPENSATION [ms] INPUT VOLTAGE 100V
75
50
Frequency 60Hz Load factor 100% Input voltage AC100V
25
0
250
500
750
1000
50ms/DIV
OUTPUT POWER [W]
INPUT HARMONIC CURRENT AC100V (AC9-HHEECC-00)
10
INPUT HARMONIC CURRENT AC230V (AC9-HHEECC-00)
10
HARMONIC CURRENT [A]
1
Output power 800W Input voltage AC100V
HARMONIC CURRENT [A]
Harmonic current standard class A (at odd number)
Harmonic current standard class A (at odd number)
1
Output power 900W Input voltage AC230V
0.1
0.1
0.01
0.01
0.001 0 10 20 30 40
0.001 0 10 20 30 40
HARMONIC ORDER
HARMONIC ORDER
POWER FACTOR & INPUT CURRENT (AC9-HHEECC-00)
1.0 16 14 0.9 12 10
EFFICIENCY (AC9-HHEECC-00)
85.0
INPUT CURRENT [A]
POWER FACTOR
80.0
POWER FACTOR
0.8
EFFICIENCY [%]
75.0
INPUT CURRENT
0.7
8 6 4
70.0
0.6
65.0
Output power 800W Output power 400W
0.5 60 100 140 180 220 260
2 0 300 60.0 60
Output power 800W Output power 400W
100 140 180 220 260 300
INPUT VOLTAGE [V]
INPUT VOLTAGE [V]
C-14
Modular power supply
Instruction Manual
1 2
Ordering information Series operation and Parallel operation in Modular power supply
2.1 2.2 Series operation Parallel operation
C-16
C-17
C-17 C-17
3
Function
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 Input voltage range Inrush current limiting Overcurrent protection Thermal protection Overvoltage protection Output voltage adjustment Remote sensing Remote ON/OFF Isolation
C-17 C-17 C-17 C-18 C-18 C-18 C-18 C-18 C-19 C-19 C-19 C-20 C-20 C-20 C-23 C-23
ACE
3.10 Alarm
4
Assembling and installation method
4.1 4.2 Installation method Derating
5
Option
5.1 Option outline
6 7
Input module Medical electrical equipment
7.1 7.2 7.3 Type Specification Others
C-25
C-25 C-25 C-25 C-25
C-15
Modular power supply
Instruction Manual
lPART NUMBERING EXAMPLE (1)
1 Ordering information
6 5 4 slot 3 2 1 code code Option Series code
AC9 OHHECC 01 08GW
Refer to options G W H-module available in serial connection at 24V 6.5(8)A, or 48V 6.5(8)A C-module available in parallel connection at 5V 46.8A E-module 12V 13(14)A Blank panel Unit ACE900F
AC
ACE300F 3:ACE300F ACE450/650F 4:ACE450F ACE900F 6:ACE650F 9:ACE900F Start from Slot1
(Lower voltage to higher voltage. If a module is not required, set "0" for the slot.)
Parallel code
("00" if parallel operation (Blank if not required) is not required.)
Choose from Table1.1. Series bar Shorted bar
lPART NUMBERING EXAMPLE (2)
If the parallel operating module C (5V, 46.8A) in example (1) is changed to module 2C(5V, 60A), the part number would change to AC9-0HHE2C-00-08GW.
ACE
6 5 4 3 slot 2 1
Refer to instruction manual 5.
lPART NUMBERING EXAMPLE (3)
Parallel and series operation of 2A-2K both use codes as in Table 1.1. For example, if connecting two modules 2E [12V, 25(34)A] in
slot2 slot1
Table 1.1 Parallel / Series code
code 00 01 slot6 slot5 slot4 slot3
series, and using these as 24V, 25(34)A, the part number would change to AC9-002E2E-00-02.
ACE300F ACE450/650F
02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F
lNaming rules
(1) Confirm the output voltage and current, and select the code for output modules to be installed in slots 1-6 from the output module specifications. Use an "O" to designate slots where no output module will be installed. (2) If the supply will be operated in parallel or in series, refer to Table 1.1 for the proper placement of the bus bar(s) between the output modules, and the appropriate code designation(s). Refer to section 2 for notes on settings for series and parallel operation. (3) A minimum of two slots must be filled. (4) List of modules which may be used for series or parallel operation.
Parallel setting Series setting
possible impossible possible impossible
A-K, 2A-2K L, M, N, P, R, S, T, U, Y, W, Z, 9, Q, V A-K, 2A-2K, L, M, N, P, R S, T, U, Y, W, Z, 9, Q, V
C-16
ACE900F
nSeries operation can provide a higher maximum output voltage, depending on the modules used. In addition, series operation provides a dynamic load response superior to that of parallel operation during abrupt changes in load. Therefore, we recommend operation in series for dynamic loads in order to increase power.
: Output terminal : Connection
Modular power supply
Instruction Manual
nPlease consider the following when configuring your supply for parallel operation. Please consult us as regarding usage methods for remote sensing. Peak loads cannot be obtained. When adjusting the output voltage of modules connected in parallel, all connected modules must be adjusted. If precision adjustment is required, remove the bus bar between modules, adjust the output voltage, and reinstall the bus bar. Large differences in set output voltages will lead to large variances in load. Adjust voltages to values as close together as possible, in order to minimize load variance. nAt startup, modules connected in series or in parallel, may show stepped input and output voltage waveforms. This is due to a delay in the rise time.
Input ON AC Input voltage
2 Series operation and Parallel operation in Modular power supply
2.1 Series operation
nSeries operation is possible only between identical output modules. If series operation is specified in the part number, the supply will be shipped with a series bar installed. However, series operation is possible with modules S, T, U, Y, W, Z, 9, Q, and V, but series bar cannot be specified. nThe output current in series operation is the same as that of the individual modules that are connected. nPlease consider the following items when configuring your supply for series operation: Connect only the same type of modules in series. A total rated voltage of up to 48V can be set up for series operation. Modules in the same power supply can be set up for series or parallel operation, but not both. Please consult with us for usage other than in accordance with the above conditions.
ACE
Output voltage
Fig. 2.1 Start-up waveform for series and parallel operation
3 Function
2.2 Parallel operation (applying module : A-K, 2A-2K)
nParallel operation is possible using modules with identical output voltage. If parallel operation is specified in the part number, the supply will be internally configured accordingly, and shipped with the appropriate bus bar in place. Parallel operation cannot be set up once the unit has been shipped.
nOutput current in parallel operation. Current ratings for output modules connected in parallel are derated by 10%. Ex.: AC4-HHECB-08 Parallel code 08 means slots 4 and 5 are connected in parallel. The output module for slots 4 and 5 is "H". Therefore, the current is as shown below: Current = (6.5A+6.5A) 0.9=11.7 A
3.1 Input voltage range
nThe input voltage range is from 85 VAC to 264 VAC, or 120 VDC to
350 VDC. Compliance with safety standards (agency approval) is limited to use with AC input voltage only.
nBe aware that use of voltages other than those listed above may re-
sult in the unit not operating according to specifications, or may cause damage. Avoid square waveform input voltage, commonly used in UPS units and inverters.
3.2 Inrush current limiting
nInrush current limiting is built-in. nIf a switch is being used for input, ensure that it is rated to handle the input inrush current. When turning the power OFF and then ON again within a short period of time, the inrush current limiting may be disabled, therefore, ensure sufficient time elapses before restarting. nInrush current limiting uses a thyristor, therefore primary inrush current and secondary inrush current are generated. If power is turned ON and OFF repeatedly, failure may result. Please allow enough time between power ON and OFF.
C-17
Modular power supply
Instruction Manual
3.6 Output voltage adjustment
nOutput voltage can be adjusted by turning the internal potentiom-
3.3 Overcurrent protection
nOvercurrent protection is built in (activated at 105% of the rated
current, or for operation with peak current, at 101% of the peak current); however avoid short circuits or overcurrent.The unit automatically recovers when the cause of the short or overcurrent is cleared.
eter.
nRefer to specifications for adjustment ranges. Please consult with us regarding operation outside the specified ranges. For modules Y, W, Z, 9, and Q, turning the internal potentiometer clockwise increases the positive voltage and decreases the negative voltage simultaneously.
nWhen the output voltage drops as a result of the overcurrent circuit being activated, the average output current is reduced by intermittent operation of the power supply (intermittent overcurrent mode). nAuxiliary power (AUX) Output that supplies power to the RC terminal of output modules. AUX power is designed to be used for control of the remote
3.7 Remote sensing (applying module : A-K, 2A-2K)
nEach output module incorporates remote sensing functions. nIf remote sensing is not used, then please short +S and +M, and -S and -M at the CN2 output module. Fig. 3.1 shows wiring for when remote sensing is not used. The unit is shipped with harnesses for when remote sensing is not used.
Output module OUT +V -V +M +S -S -M Load
ACE
ON/OFF function. nPeak current protection (applicable modules: 2E-2K) Peak current protection is built in (refer to Output module specifications 1 for peak current usage methods). Peak current protection operates independently for each output module. Its activation will not halt the entire power supply. Shut off input AC voltage, wait for at least 2-3 minutes, and recycle to recover output voltage( ). The recovery time varies depending on input voltages and load status during operation.
CN2
Short at connector
3.4 Thermal protection
nThermal protection is built in. If either of the following takes place,
Fig. 3.1 When the remote sensing function is not used
nWiring method with remote sensing is shown in Fig.3.2. nPlease consider the following when using remote sensing: Be sure connections are made properly. If the load wire is not connected correctly, a load current may flow through the sensing wire, which could damage circuitry inside the power supply. Wire of an appropriate type and gauge should be used to connect the power supply to the load. Line drop should be less than 0.3V. When using the remote sensing function, oscillation in the power supply output voltage, or significant variations in output voltages can be generated by wiring or load impedance. The following are ways to remedy instability in output voltage. Remove remote sensing from the negative side, and short -S and -M at the CN2 on each output module. If oscillation occurs, connect C0, C1, and R1. Please consult us for details. nEnsure that current is not drawn from the CN2 +M or -M terminals.
the thermal protection may be activated, shutting off the output:
The current or temperature is continuously in excess of the derating curve. The fan has stopped or the airflow from the fan is reduced by an obstruction. If the thermal protection is activated, shut off input voltage, remove the cause of the overheating, wait for the unit to cool down, and recycle to recover output voltage.
3.5 Overvoltage protection
nOvervoltage protection operates independently for each output
module. Its activation will not halt the entire power supply. Overvoltage protection is built in. When the overvoltage protection is activated, shut off input, wait for at least 1-2 minutes, and recycle to recover output voltage. The recovery time varies depending on input voltage, etc. When testing the power supply for overvoltage performance or applying voltage from the load circuit, please note that components inside the power supply might fail if the voltage applied exceeds the rated output voltage.
C-18
Modular power supply
Instruction Manual
Table 3.1 Remote ON/OFF specifications Connection method SW Logic Turn on Fig 3.3 Remote SW SW open (0-0.5V between RC+ and RC-) SW close (12V between RC+ and RC-) CN2 RC-
OUT
+V -V
Output module C0 Load R1
+M CN2 +S -S -M
C1
Wire +S and -S as close as possible
Turn off Bases terminal
Fig. 3.2 When the remote sensing function is used
3.9 Isolation 3.8 Remote ON/OFF
nEach output module incorporates remote ON/OFF functions. nWhen performing incoming inspections, ensure that the applied voltage is increased gradually. Additionally, when turning off power to the unit, use a dial to gradually reduce the voltage. Do not use a voltage tester in conjunction with a timer. Doing so may generate voltage several times higher than the applied voltage.
Output voltage ON/OFF can be controlled by applying a voltage to CN2 at each output module.
nDedicated auxiliary power (AUX) for remote ON/OFF. Auxiliary power (AUX) is built-in for control of remote ON/OFF. Auxiliary power (AUX) is isolated from input, output, and FG. Remote ON/OFF connection methods with AUX are shown in Fig. 3.3. nRemote ON/OFF control logic. The output stops when voltage (4.5 - 12.5V) is applied to RC+. Reverse logic option (-R) also available.Refer to section 5. Option. The built-in fan does not stop even if the output is turned OFF using remote ON/OFF. If the output has been turned OFF using remote ON/OFF, the LV alarm signal will be generated (except modules, S, T, and U). This function operates on each output module independently. nRemote ON/OFF circuits operate independently on each output module; therefore it is possible to use remote ON/OFF on individual output modules. Please be aware that this cannot turn off all outputs together. If turning off all output modules together is a requirement, we recommend use of the remote ON/OFF circuits in series or parallel. nThe remote ON/OFF circuit (RC+, RC-) is isolated from input, output, and FG.
SW Output module AUX Ri= 780 G Turn off RC+ RCCN1 CN2 Turn on
ACE
3.10 Alarm
nThe following two types of alarm function are built in. Refer to Table 3.2 for details. PR: abnormal input voltage, fan alarm LV : abnormal output module voltage (except modules S, T, and U).
Table 3.2 Explanation of alarms
Alarm Output of alarm
PR
When input voltage is abnormal (low input voltage) or the fan stops, the alarm signal is generated from CN1.
Open collector method Good : Low (0-0.8V, 1-20mA) Fail :35V max
LV
When rated output voltage decreases or stops, the alarm signal is generated from CN2. Note : In the event of overcurrent output (intermittent current), operation of the alarm will become inconsistent. The LV alarm is not isolated from output. Therefore, make sure all connections are correct when the power supply is used to supply negative voltage or is operated in series. (Refer to Fig. 3.5).
Open collector method Good : Low (0-0.8V, 1-20mA) Fail :35V max
Please consult us details. AUX PR
G
Fig. 3.3 Example of use with remote ON/OFF
Fig. 3.4 PR internal circuit
C-19
Modular power supply
Instruction Manual
100,000
+LV
+LV
+LV
Life expectancy of fan[H]
50,000 30,000
-LV -S
-LV -V
-LV COM
Applying module : A-K, 2A-2K
Applying module : L, M, N, P, R
Applying module : Y, W, Z, 9, Q, V
10,000 5,000 -10
Fig. 3.5 LV internal circuit
Input voltage AUX
0
10 20
30
40
50
60
70
Ambient temperature [ ]
Fig. 4.2 Life expectancy of fan(R(t)=90%)
0V 12V 0
nWhen mounting the power supply with screws, it is recommended
FAN trouble
ACE
Revolution of FAN
H
that this be done as shown in Fig. 4.3. If other methods are used, be sure the weight of the power supply is taken into account.
PR alarm Remote ON/OFF Output voltage LV alarm
L H L
0V H L
Top CN1 : unsetteled area H : 2V H 35V or Open, L:L 0.8V A
CN1 Top
Top
CN1
B
C
Fig. 3.6 Sequences for alarm types
Fig. 4.3 Installation method 1
nAvoid installation method 2 as shown in Fig. 4.4, which can cause
4 Assembling and installation method
4.1 Installation method
nFans for forced air cooling are built in. Ensure that the inlet (rear) and outlet (output terminal) vents are not blocked, to prevent disruption of the airflow. Option with reversed airflow (-F) is also available.
stress on the mounting holes. nMaximum length of mounting screws is 6mm (Refer to Fig. 4.5).
Chassis of customer system
Chassis of ACE series
NO
CN1
Screw M4 6mm max
Fig. 4.4 Installation method 2
Air flow
Fig. 4.5 Mounting screw
FAN
Output module
4.2 Derating
nThe ACE series comprises power supplies consisting of a combination of output modules. Make sure each output module is used within specifications, and that the total output power of all modules is equal to, or less than the rated total output power. nThe derating curve for the ambient temperature (inlet temperature for cooling) of output modules is shown in Fig. 4.6. nOperation within the hatched area will result in different ripple and ripple noise specifications.
Fig. 4.1 Air flow
nIf the unit is used in a dusty environment, an air filter should be used so the cooling efficiency of the fan is not reduced. nIf the fan stops, the thermal protection may be activated, shutting down the output. Life expectancy of the fan varies depending on usage conditions; therefore regular inspections of the fan are required for increased reliability. Should the fan become nonoperational over the course of time, it can be replaced. Refer to the optional parts section of this catalog.
C-20
Modular power supply
Instruction Manual
1100 Peak total output power
Load of output module [%]
100
60 40 20 0 -20 -10
Total output power [W]
80
1000 900 800 720 700 600 85 90 150 170 264 Input voltage [VAC]
Total output power
0
10
20
30
40
50
60
70
Ambient temperature [ ]
Fig. 4.6 Derating curve for ambient temperature
nThe derating curve with respect to input voltage is shown in Figs. 4.7 to 4.10.
350
Fig. 4.10 Derating curve for input voltage (ACE900F)
nThe ACE900F can output peak power under the following conditions.
ACE
Total output power [W]
300 250 225 200 150 85 90 150 170 264 Input voltage [VAC]
Output power [W]
Pp
: peak total output power
Pave : average power P0 0 t1 t2 Pp t1 + P0 t2 t1 + t2 t [sec]
t1
Fig. 4.7 Derating curve for input voltage (ACE300F)
500
1 [sec], Pave =
total output power,
t1 t1 + t2
0.3
Fig. 4.11 Peak output power (ACE900F only)
nDefinition of load factor
450
Total output power [W]
(Sum of each module power) A0= (Total output power)
6 k=1
100
400 360 350 300 85 90 150 170 264 Input voltage [VAC]
(Ik1
Vk1 + Ik2
Vk2)
=
(Total output power)
100
Note : Only the number with a small occupation slot number is calculated in 2A-2K. A11, A21, A31, A41, A51, A61 : Ak1=Ik1 / I0k1 A12, A22, A32, A42, A52, A62 : Ak2=Ik2 / I0k2 100 100
Fig. 4.8 Derating curve for input voltage (ACE450F)
700
Ik1 , Vk1 , I0k1: output current ( 1), voltage, and rated current ( 2) for modules S, T, and U (excepting V2). Ik2 , Vk2, I0k2 : output current, voltage, and rated current for V2 in modules S, T, and U.
600 550 540 500 85 90 150 170 264 Input voltage [VAC]
Total output power [W]
650
Total output power: Dependent upon input voltage (Refer to Figs.4.7-4.10) 1 The output current for module codes Y, W, Z, 9, Q, and V is the sum of + and - output currents. 2 Rated output for modules is as below. Excepting module codes Y, W, Z, 9, Q, and V : Refer to output module specifications
Module codes Y, W, Z, 9, Q, and V
Fig. 4.9 Derating curve for input voltage (ACE650F)
: 10A(Y), 6.4A(W) , 5A(Z), 3.2A(9) 12.8A(Q), 11A(V)
C-21
Modular power supply
Instruction Manual
[%]
100
(Sum of +current and -current) Load [%]=maximum value of A0 to A62 nLoad regulation in modules Y, W, Z, 9, Q, and V Ensure that the sum of + and - output is less than total output as follows: Y: 50W, W: 76.8W, Z: 75W, 9: 76.8W, Q: 153.6W, and V: 165W. The relationship between current and load regulation is shown in the following example(Refer to Fig. 4.12). (1) Rated current 1 : 3.2A When drawing current within the range of +3.2A and -3.2A (total 6.4A), the specifications of load
Load of V2
50
0 0.5 1 8 9 [A]
Output current of V1 Fig. 4.13 Minimum output current of V1
nUsage example [Example1] Method to confirm that AC4-LWHEC-00 can be used under the following conditions. Input voltage : 100 VAC Ambient temperature : 50 Ouput module : slot1 : 5V 15A 7A 6A 4A, -12V 1A slot2 : 12V slot3 : 24V slot4 : +12V
ACE
(2) Rated current 2 : 4.2A
regulation are as in "Load regulation 1". When drawing current within the range +4.2A and -2.2A (or +2.2A and -4.2A, total 6.4A) the specifications of load regulation are as in "Load regulation 2". (3) Peak current : 5A Loads of +5 A and -1.4 A (or +1.4 A and -5A, total 6.4A) are possible. However, refer to Output Module Specifications when drawing 4.2-5A. 1
slot5 : 3.3V 10A Calculating A11-A51 (Sum of each module power) A0 = (Total output power)
6
Load regulation
Load regulation2 Load regulation1
100
=
k=1
(Ik1
Vk1 + Ik2
Vk2)
100
(Total output power)
=396/400 100=99% A11=I11/I011 100=15/26 100=58% A21=I21/I021 100=7/13 100=54% A31=I31/I031 100=6/6.5 100=92% A41=I41/I041 100=5/6.4 100=78% A51=I51/I051 100=10/10 100=100% Accordingly, because the derating curve (Fig. 4.6) indicates that up to 100% of the maximum load can be used up to 50 and the largest value amongst A0, A11, A21, A31, A41, and A51 is 100%, this assures that these input and output conditions are acceptable.
Current
Rated current 1 Rated current 2 Peak current
Range of using Fig. 4.12 The relationship between rated current and load regulation
nMinimum output current of modules S, T, and U. The allowable load of V2 dependent upon the output current of V1 changes as follows.
C-22
Modular power supply
Instruction Manual
Table 5.1 Reduced leakage current Leakage current (230 VAC) Conducted Noise Ripple Noise -E -G 0.5mA max 0.15mA max Class A Not available 1.5 times standard 2.0 times standard
[Example2] Method to confirm that AC9-2HCSWP-00 can be used under the following conditions. Input voltage : 100 VAC Ambient temperature : 50 Ouput module : slot1 : 15V slot3 : slot4 : 5V 3A 8A, 5V 4A slot2 : +12V 3.2A, -12V 2.3A 5V 25A
l-F Specification with reversed air exhaust Differences from standard products are shown in Fig.5.1 and Fig.5.2.
Air flow
slot5 : 24V 13A Calculating A11-A51 (Sum of each module power) A0= (Total output power)
6
100
Load of output module [%]
100 80 60 40 20 0 -20 -10
Fig. 5.1 Air flow(-F)
FAN
Output module
=
k=1
(Ik1
Vk1 + Ik2
Vk2)
ACE
(Total output power)
100
=608/800 100=76% A11=I11/I011 100=3/4 100=75% A21=I21/I021 100=5.5/6.4 100=86% A31=I31/I031 100=8/10 100=80% A32=I32/I032 100=4/5 100=80% A41=I41/I041 100=25/26 100=96% A51=I51/I051 100=13/14 100=93% Accordingly, because the derating curve (Fig. 4.6) indicates that up to 100% of the maximum load can be used up to 50 and the largest value amongst A0, A11, A21, A31, A32, A41, and A51 is 96%, this assures that these input and output conditions are acceptable.
0
10
20
30
40
50
60
70
Ambient temperature [ ](-F)
Fig. 5.2 Derating curve characteristics resulting from ambient temperature (-F)
The derating curve of output modules based on input voltage is also different for the ACE900F. l-N(External specifications may vary; please contact us for details) In the event that cooling can be provided by the user's fan, the built-in fan may be eliminated (Refer to Fig.5.3). If applying for agency approval, it is necessary to measure the temperature of the transformer. Please contact us for details on cooling methods.
5 Option
5.1 Option outline
nPlease contact us in advance as regards detailed specifications
Air
and delivery.
nPlease refer to "1. Ordering information" for ordering methods. nWhile some combinations of options are possible, others are not.
Please contact us for details. l-E, -G Reduced leakage current type. Differences from standard products are shown Table 5.1.
Fig. 5.3 Dwg. of -N specification
C-23
Modular power supply
Instruction Manual
Load of output module [%]
100 80 60 40 20 0 -20 -10
l-K Specification with lower speed fan for reduced noise. The difference from standard is shown Fig.5.4.
100 80 60 40 20 0 -20 -10
Load of output module [%]
0
10
20
30
40
50
60
70
Ambient temperature [ ]
Fig. 5.5 Derating curve for operational ambient temperature (-T)
0 10 20 30 40 50 60 70
Ambient temperature [ ]
l-U Specifications for support of instantaneous voltage dips (low input voltage support). Use condition Input Output 70 VAC(100 VDC) Duty 1s/30s ACE300F 200W ACE450F 360W ACE650F 540W ACE900F 720W Avoid continuous use for more than 1 second under the conditions mentioned above, as such use can lead to damage to the power supply. l-W(External specifications may vary; please contact us for details) Specification with terminal covers attached to output modules. If -W is specified, a terminal cover is attached to all installed output modules.
ACE
l-R
Fig. 5.4 Derating curve based on ambient temperature (-K)
Specification with reversed logic for remote ON/OFF operation. If -R is specified, then even if input voltage is applied to the module, it will not function as long as voltage is not applied to the RC terminal. Turn on : 12[V] between RC+ and RCTurn off : 0-0.5[V] between RC+ and RC-R specification applies to all installed output modules. A harness is required for connecting to CN2 when using these specifications. Please use H-SN-16 to H-SN-18, etc. When the customer is to provide a harness, please note the remote sensing wiring (refer to section 3.7, "Remote Sensing"). Please consult us if specifications that mix normal logic and reverse logic are required. l-T(External specifications may vary; please contact us for details) Specification that adds a filter to prevent the entry of foreign bodies. The difference from standard products is shown in Fig.5.5. Combinations with -F and -K are not possible. Dust can result in clogging and reduced cooling; therefore it is required that the unit is used in a dust-free environment, or that it is periodically cleaned.
C-24
Modular power supply
Instruction Manual
7.2 Specification
Safety : UL2601-1 (CSA601.1), EN60601-1 Isolation : 4,000 VAC input-output, RC, AUX 1min. cutoff current 10mA leakage current : 0.3mA max (100 VAC), 0.5mA max (230 VAC) 0.1mA max. is also possible. conducted noise : complies with FCC-A, VCCI-A, CISPR22-A, EN55022-A Supported modules All modules except S, T, and U modules with "output module
6 Input module
Input terminals for the ACE300F, 450F, and 650F are upon the fan mount surface, however these can be situated on the output side. This places the input module (I) in the far left slot of each module, instead of the output module.External dimensions will change. Consult us for details.
ex : AC3 I CBA 00
Output module Input module
specification." Please note that there is no support for modules S, T, and U. Ripple noise Ripple noise is 1.5 times that of standard models.
ACE
7.3 Others
L N FG I C
If applying for medical equipment agency approval, use fuses or
B A
breakers that comply with applicable safety regulations on input terminals.
With module I specified, conducted noise is class A.
L N
or
L N
ACE450F 250 VAC10A
7 Medical electrical equipment
Specifications supporting medical electrical equipment.Types and specifications, etc. are below. Please contact us for details.
FUSE ACE300F 250 VAC8A
ACE650F 250 VAC15A ACE900F 250 VAC20A
Fig.7.1 Connecting FUSE
L N
7.1 Type
AC H When units that support use as medical electrical equipment and other options are combined, the end of the type name is as follows. AC , :other options Refer to instruction manual 5. for Option. Example of use in conjunction with option -K model (reduced fan speed). AC C : coating E : low leakage current Option -H is a low leakage current specification product. Refer to section 7.2 for details. HK Options that cannot be used in conjunction with this are as follows: H
Fig. 7.2 Connecting circuit breaker
C-25