XTE/HP/C Series
Yahoo! is not affiliated with the authors of this page or responsible for its content.
XTE/HP/C Series
Main /Branch Power Entry
120 KA, 160KA Options
AC Power Surge Suppressor / Filter
XTE/HP/C Series
Features:
Design Features
Individually Fused Suppression Modules
Thermal Cutout
Busbar Connection
Solid State Bi-directional
High Energy Parallel Design for Category C3
Applications
AC Tracking Filter with EMI/RMI Filtering Up to
50dB from 100kHz to 100MHz
Designed for Integral Installation by the Low
Voltage Distribution Equipment Manufacturer
Front Panel Alarm with Test/Silence Switch
Quality
Five Year Warranty: Includes Unlimited Module
Replacement
Burn-in Tested Prior to Shipment
Short Circuit Current Rating 200,000 rms
Symmetrical Amperes
The XTE/HP/C Series is a modular parallel
suppressor designed for internal installation for
service entrance or distribution panel board
applications. The XTE/HP/C is a multi-stage
suppression circuit consisting of field proven, fast
acting 40 mm MOVs. Each surge suppression
module is individually fused and utilizes Patented
TranSafe circuitry with thermal cutout to
ensure safe operation during severe over-
voltages and high fault current conditions. The
suppression elements are encapsulated in UL
Listed and Patented Ceramgard® providing
another level of safety. A filter network is added
to provide wave shape smoothing and a high
level of EMI/RFI noise attenuation. On-line
diagnostics continuously monitor the unit status
and feature redundant LEDs to signal a
reduction in surge capacity or loss of a
suppression circuit. An audible alarm with test
and silence features is included in the standard
diagnostic package. All CCI Surge Control®
products are designed and tested in accordance
with the recommendations and procedures of
ANSI/IEEE C62.41 and C62.45. The XTE/HP/C
Series is UL 1449 Second Edition Recognized ,
and qualified for service entrance applications
under Section 37.3 with short circuit current
ratings up to 200,000 rms symmetrical amperes.
Surge Control® is a registered mark of Circuit Components, Inc..
TranSafe is a trade mark of Advanced Protection Technologies
Ceramgard® is a registered mark of Advanced Protection Technologies Issued 12/02 © 2002 Circuit Components, Inc.. All rights reserved.
This information is not intended to and does not create any warranties, expressed or implied, including any warranty of merchantability or fitness for a particular purpose.
Circuit Components Inc. reserves the right to change specifications at any time without notice.
Circuit Components, Inc.
2400 S. Roosevelt Street Tempe, AZ
85282
Tel: 480-967-0624
Fax: 480-967-9385
Email: info@surgecontrol.com
Website: www.surgecontrol.com
A PRODUCT OF
S
URGE
C
ONTROL
®
Suitable for use on a circuit capable of delivering not more than
200,000 rms Symmetrical Amperes, 600 Volts, maximum
Description:
Second Edition
XTE/HP/C Series Performance Specifications:
Circuit Components, Inc.
2400 S. Roosevelt Street Tempe, AZ
85282
Tel: 480-967-0624
Fax: 480-967-9385
Email: info@surgecontrol.com
Website: www.surgecontrol.com
A PRODUCT OF
S
URGE
C
ONTROL
®
Voltage Specifications: UL Suppressed Voltage Rating (SVR)
Performance Features
Surge Capacity L-N N-G
120KA/phase 120K 120K
160KA/phase 160K 160K
UL 1449 Second Edition Recognized, 1283
Recognized, and CUL
200KAIR Rated Fusing
Less than 1/2 Nanosecond Response Time
5000 Category C3 Impulses with <10% Drift
Environmental Features
Relative Humidity Range: 095% Non-
Condensing
Operating Frequency: 4763 Hz
Operating Temperature: -40º C to +65º C
Mounted on Back plane for integral Installation
Standard Size: 10.75 x 10.88 x 4.5 (LxWxD)
Weight: 9.5 Lbs.
Optional Features
Notes: /CL Option not available on XTE/9,91
Ordering Information for Optional Features should be appended to the model and separated by a slash (/)
Example: XTE/2HP/CCI/CL/DS/RM
/CL Module Option increases the surge current capacity from 120KA/phase to 160KA/phase
/DS Integral Disconnect Switch when a spare 3 pole breaker is not available for connecting the suppressor, order with an internal
disconnect (Increases size to 14.75 x 12.88 x 4.5 (L x W x D).
/DC The Dry Contacts monitor each Phase providing a summary alarm. The contacts are terminated in a terminal strip.
/RM Remote Monitor with indicator lights and audible alarm is available for use with the Dry Contact Option
/SC Surge Counter option monitors the occurrence of transients entering the facility through the suppressor and is supplied with a
long life Super Cap to provide power to the counter in the event of power failure.
Model
Service Voltage
L-G
L-N
N-G
L-L
MCOV
XTE/1HP/CCI
120/240V Split Phase
330
330
700
150
XTE/2HP/CCI
120/208V three Phase WYE
330
330
700
150
XTE/3HP/CCI
120/240V Three Phase , High-Leg, DELTA
330/700
330
700/1200
150/275
XTE/4HP/CCI
277/480V Three Phase WYE
700
600
1200
320
XTE/5HP/CCI
480V Three Phase DELTA
1500
1500
575
XTE/51HP/CCI 480V Three Phase, Corner Grounded, DELTA
1500
1500
575
XTE/6HP/CCI
240V Three Phase DELTA
700
700
275
XTE/61HP/CCI 240V Three Phase, Corner Grounded, DELTA
700
700
275
XTE/7HP/CCI 220/380V Three Phase WYE
700
600
1200
320
XTE/8HP/CCI
347/600 Three Phase WYE
1000
900
1800
420
XTE/9HP/CCI
600V Three Phase DELTA
1800
1800
750
XTE/91HP/CCI 600V Three Phase, Corner Grounded, DELTA
1800
1800
750
XTE/11HP/CCI 120V Single Phase
330
330
150
XTE/12HP/CCI 240V Single Phase
600
600
275