SG Series Plus 2U RackMount UPS, 1kVA to 3kVA

ck for previous versions at the Internet Archive. Yahoo! is not affiliated with the authors of this page or responsible for its content.
SG Series Plus 2U RackMount UPS, 1kVA to 3kVA Hard Wired Series
RCHW-120SO-SP Surge Suppressor Specifications
1
970.945.2770 Direct
800.430.2770 (USA & Canada)
michael.gibson@carebase.com
www.carebase.com
Meter-Treater, Inc.

Represented by CareBase
Michael Gibson
PO Box 2987~Glenwood Spgs, CO 81602
(MS) SS132-A-01/03/03
PRODUCT APPLICATION

First Stage Surge Protection
(Residential & Llight Commercial/Industrial)

For Category C (Service Entrance) Applications

Designed For 400Amp AC Service

Ideal Protection For AC Motor Driven Applications

Interior Or Exterior Installation

Configured For 120/240 Volt Split Phase Installation

Excellent Alternative To Meter-Based Protection
PRODUCT FEATURES

UL Listed: Secondary Surge Suppressor & TVSS

Red 1000 MCD LEDs, Visible In Bright Sunlight,
Monitor Protection Status

10 Year Warranty

High Energy Withstand
(40kA or 80kA/Per Phase Leg, Depending On Model)

High MCOV

Coordinated 200kAIC Safety & Thermal Fusing

Solid State 40mm MOV Suppression Components

UL Listed Heavy Duty Metallic Enclosure
(Surge Suppressors)
UL Listed Secondary Surge Arrestors
Models: RCHW-120S0-L1 & L2
And
UL Listed TVSS Devices
Model: RCHW-120SP-L2
The RCHW hardwired surge protective devices are specifically
designed for applications in residential, commercial and light
industrial environments. These units provide superior control over
transients by delivering low clamping voltages combined with high
surge energy (40kA or 80kA/mode) handling capability.
All RCHW hardwired models are UL and CUL listed as either
secondary surge arrestors or 1449 TVSS devices. They provide an
excellent application alternative to meter-based protectors, making
them an ideal product for inclusion in Utility Power Quality Programs.
PRODUCT SPECIFICATIONS
Electrical:
Applied Voltage: 120/240vac

MCOV: 132 Volts, phase to ground,
150 Volt MCOV component used.

Protects: Each phase to neutral/ground

Surge Current Rating: -L1=40kA
per leg
, 80kA
total
-L2=80kA
per leg
, 160kA
total

(based upon 8/20祍 waveform)80kA per phase

Clamp Voltage: 400 Volts, (L-G) UL 1449, 2nd Edition

Fault Current: 200kA rms symmetrical

TVSS Unit:
Has, per UL 1449 2nd Edition, 2 black(phase)
wires, 1 white (neutral) wire & 1 green (ground)
wire with clamp voltage ratings of: L-N 400V,
L-G 400V, N-G 800V and L-L 800V.
Mechanical:

Weight: 2.5 pounds (unpackaged)

Dimensions: 6" x 4.25" x 2.9"

Lead Length Of Wires: 18"

Enclosure: Meets NEMA 1, 2, 3, 4, 12 and 13 ratings

End Caps: Polycarbonate

Color: Mill finish aluminum or anodized
Coordinated 200kAIC
Rated Fusing
RCHW HARDWIRED
RCHW-120-SO-SP-2004-11-13-CB.pdf