SG Series Plus 2U RackMount UPS, 1kVA to 3kVA
ck for previous versions at the Internet Archive.
Yahoo! is not affiliated with the authors of this page or responsible for its content.
SG Series Plus 2U RackMount UPS, 1kVA to 3kVA
Hard Wired Series
RCHW-120SO-SP Surge Suppressor Specifications
1
970.945.2770 Direct
800.430.2770 (USA & Canada)
michael.gibson@carebase.com
www.carebase.com
Meter-Treater, Inc.
Represented by CareBase
Michael Gibson
PO Box 2987~Glenwood Spgs, CO 81602
(MS) SS132-A-01/03/03
PRODUCT APPLICATION
First Stage Surge Protection
(Residential & Llight Commercial/Industrial)
For Category C (Service Entrance) Applications
Designed For 400Amp AC Service
Ideal Protection For AC Motor Driven Applications
Interior Or Exterior Installation
Configured For 120/240 Volt Split Phase Installation
Excellent Alternative To Meter-Based Protection
PRODUCT FEATURES
UL Listed: Secondary Surge Suppressor & TVSS
Red 1000 MCD LEDs, Visible In Bright Sunlight,
Monitor Protection Status
10 Year Warranty
High Energy Withstand
(40kA or 80kA/Per Phase Leg, Depending On Model)
High MCOV
Coordinated 200kAIC Safety & Thermal Fusing
Solid State 40mm MOV Suppression Components
UL Listed Heavy Duty Metallic Enclosure
(Surge Suppressors)
UL Listed Secondary Surge Arrestors
Models: RCHW-120S0-L1 & L2
And
UL Listed TVSS Devices
Model: RCHW-120SP-L2
The RCHW hardwired surge protective devices are specifically
designed for applications in residential, commercial and light
industrial environments. These units provide superior control over
transients by delivering low clamping voltages combined with high
surge energy (40kA or 80kA/mode) handling capability.
All RCHW hardwired models are UL and CUL listed as either
secondary surge arrestors or 1449 TVSS devices. They provide an
excellent application alternative to meter-based protectors, making
them an ideal product for inclusion in Utility Power Quality Programs.
PRODUCT SPECIFICATIONS
Electrical:
Applied Voltage: 120/240vac
MCOV: 132 Volts, phase to ground,
150 Volt MCOV component used.
Protects: Each phase to neutral/ground
Surge Current Rating: -L1=40kA
per leg
, 80kA
total
-L2=80kA
per leg
, 160kA
total
(based upon 8/20祍 waveform)80kA per phase
Clamp Voltage: 400 Volts, (L-G) UL 1449, 2nd Edition
Fault Current: 200kA rms symmetrical
TVSS Unit:
Has, per UL 1449 2nd Edition, 2 black(phase)
wires, 1 white (neutral) wire & 1 green (ground)
wire with clamp voltage ratings of: L-N 400V,
L-G 400V, N-G 800V and L-L 800V.
Mechanical:
Weight: 2.5 pounds (unpackaged)
Dimensions: 6" x 4.25" x 2.9"
Lead Length Of Wires: 18"
Enclosure: Meets NEMA 1, 2, 3, 4, 12 and 13 ratings
End Caps: Polycarbonate
Color: Mill finish aluminum or anodized
Coordinated 200kAIC
Rated Fusing
RCHW HARDWIRED
RCHW-120-SO-SP-2004-11-13-CB.pdf