I N S T A L L A T I O N
timer options included)
1012FPD-1A (Cdn)
1024FPD-1A (Cdn)
2
960-MO/MOx28
Momentary Keyswitch with 2 SPDT Switch (less cylinder)
3
8310xSCS/DSS x 28
8310 Electromagnetic Lock with SCS/DSS Features
4
914
Sounder
5
1200AxSS1-36-28
36" Exit Device with Switch Module
6
9507-12
12" Flex Loop
7
BC1M (QS1 & 2)
Building Code Sign PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED
WITHIN 15 SECONDS
BC2M (QS1, 2 & 3)
Building Code Sign EMERGENCY EXIT UNLOCKED BY FIRE ALARM
BC3M (QS3)
Building Code Sign KEEP PUSHING DOOR UNLOCKS IN 15 SECONDS
Building Code
Sign
QS1-12/24, QS2-12/24, QS3-12/24
NOTE: See reverse for schematic diagram.
Riser Diagram
QS-123 RiserD.qxd 5/8/03 11:33 AM Page 1
©2002 RUTHERFORD CONTROLS INTL CORP. WWW.RUTHERFORDCONTROLS.COM
USA: 2697 INTERNATIONAL PKWY, PARKWAY 5, VIRGINIA BEACH, VA 23452 1.800.899.5625 757.427.1230 FAX: 757.427.9549 E-MAIL: SALES@RUTHERFORDUSA.COM
CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 1.800.265.6630 519.621.7651 FAX: 519.621.7939 E-MAIL: SALES@RUTHERFORDCONTROLS.COM
1 2 3 4 5 6
+
DC Output for
Electromagnetic Locks
12
34
5
6
Terminals 3&4
N/O Momentary Reset Switch
Terminals 4&5
N/C Momentary Override Switch
Terminals 5&6
N/C Fire Alarm Shutdown
TB1
TB2
N/O Request to
Exit Switch
(Panic
Exit Bar Switch)
Terminal
4 +Positive
Terminal
3 - Negative
Quick System Operation
QS1
When the Exit switch is triggered, this will activate the timer relay. Once
the timer has been activated, the sounder will operate for 15 seconds. At
the end of this time period the sounder will silence and the door will
unlock for 5 seconds before automatically resetting to the locked mode.
QS2
When the Exit switch is triggered, this will activate the timer relay. Once
the timer has been activated, the sounder will operate for 15 seconds. At
the end of this time period the sounder will silence and the door will
remain unlocked until the system is manually reset by authorized
personnel.
QS3
Once the exit switch has been activated for 3 seconds the timer will
activate. Once the timer has been activated the sounder will operate for
20 seconds. At the end of this time period the sounder will silence and the
door will remain unlocked until the system is manually reset by
authorized personnel.
NOTE:
National Building Code requires that if more than one Quick System
is used in a building, it is expected that one override/reset switch will
release and reset all devices simultaneously.
Sounder
Output
Delayed Egress QuickSystems
Installation Instructions
(Continued)
Schematic Diagram
QS-123 RiserD.qxd 5/8/03 11:33 AM Page 2