FISHER PIERCE
t relay is used to switch line voltage (120 Vac) to the
open and close input control circuit of the capacitor bank.
The switch is designed to operate both motor and
solenoid type switch banks. The switch can be operated
from existing radio based capacitor control systems or
from the Fisher Pierce Model 2635 code Generator.
Additional applications include multiple or series lighting
as well as traffic control signals.
Radio Switch Standard Features
Microprocessor-based design
Standard protocols available
- 11 bit digital (Fisher Pierce)
- REMS 100, 101. 102 (G.E.)
Highly sensitive FM receiver
Independent hardware watchdog timer
Self-test on power up
DIP switch selectable addressing
Field selectable close inhibit timer
Electromechanic and/or nonvolatile counter
External or internal antenna
LED indication of trip, close and receiver test
Local operation switch for trip and close
Local radio disable switch
In line load protection fuse
The Fisher Pierce Model 2635A/R Code Generator is
used to generate digital encoded messages and control
VHF transmitter(s). The code generator can be
preprogrammed for simple operation from external
devices such as relays or panel switches or can operate
from a PC via a standard serial communication port.
Code Generator Features
Compatible with Fisher Pierce 11 bit digital protocol
Stores up to 512 digital command messages
Monitors up to 5 input alarms
Controls up to 5 output control lines
Speaker with volume control
Code generator status LEDs
Meter Sockets
FISHER PIERCE
VHF Radio Capacitor Control Switch
Magnetically Latching Switch Momentary Pulsed Switch
2635A/R Code Generator
© Fisher Pierce, 1996 FP106-1104-S-W Printed in U.S.A.
SERIES 2695D VHF RADIO CAPACITOR CONTROL SWITCH
Protocols Available for Radio Switch
and Code Generator
Fisher Pierce 11 Bit Digital - Standard protocol for
existing Fisher Pierce capacitor switches. Direct
replacement for Fisher Pierce Model 2695C-P.
Additional Protocols for Radio Switches Only
REMS 100, 101, 102 - Direct replacement for General
Electric radio capacitor control switches.
Specifications
RADIO CONTROL SWITCH
Operating Voltage: 120 VAC + 15%
Output Relay Contact Ratings: SPDT
Latching Type:
10 Amps continuous;
50 Amps, 6 cycles, 0.5 PF
Momentary Type:
10 Amps continuous
Ambient Temperature Range: -25
o
to +50
o
C
Surge Withstand Capability:
Input circuit passes ANSI/IEEE C62.45-1987.
Isolation Voltage: 1,500 Vac
(Input to output, isolated contacts)
Weight: 2.5lbs. nominal
Size: 10.51H x 7.94W x 3.12D inches
Enclosure: Glass reinforced Lexan.
NEMA 3R.
RADIO RECEIVER
Type: Narrow band FM double conversion.
Signal Sensitivity: 20 ì V/meter (typical).
Frequency Range: 150 to 174 MHz
Spurious and Image Rejection: 40 dB
Selectivity: 50 dB at 20 kHz
FCC Certified: Part 15, subpart C.
MECHANICAL
Mounting: 4 stab meter socket type.
Security: Latch suitable for meter seal or padlock.
LED Indicators:
Red - close; green - trip (open); yellow - test.
Local Toggle Switches: For remote/local operation and
manual capacitor operation.
Ordering Information:
Please consult factory.
Mechanical Data:
All dimensions in inches
4000 East 116
th
St., Cleveland, Ohio 44105-4398 USA
Tel: (216) 271-6600 · Fax: (216) 341-3615
www.joslynhivoltage.com
Email: info@joslynhv.com
C A N A D A