TM1600/MA61
TM1600/MA61
TM1600/MA61
Breaker Analyzer System
The TM1600 breaker analyzer measures a circuit breaker's timing cycle. The timing channels record closings and openings of main contacts, resistor contacts and auxillary contacts. Since the timing channels are not interconnected, you can take measurements of resistor contacts and series-connected breaker chambers without having to disconnect them. A built-in program unit permits easy selection of different sequences of breaker control pulses. The delay time between pulses is set on a thumbwheel. The breaker operation unit can be used to control coil currents of up to 25 A. The time values obtained refer to the exact instant at which voltage was applied to the coil, and a builtin printer provides you with a hardcopy printout immediately after measurement. The TM1600 can be equipped with up to 24 time-measuring channels as required by the user. When more than 24 channels are needed, one or several slave units can be connected together to get an unlimited number of measurement channels. Modular design also makes it easy to combine the system with the MA61 Motion Analyzer. The TM1600 supports communication with personal computers and the CABA Win Breaker Analysis Software. The analyzer can be used for testing breakers taken out of service or for on-line testing. Fully equipped, it weighs only 12 kg (26.5 lbs).
34
MA61 MOTION ANALYZER
The MA61 Motion Analyzer is an excellent supplement to the TM1600. It combines the easy readability of an oscillograph with the extra accuracy ensured by computerized measurement and computer-processed readings. Menu-driven button selection via the built-in display makes operation simple and easy. The MA61 can be equipped with up to 6 analog channels, and it can be easily adapted to the different measurement requirements for high-voltage circuit breaker testing. It can measure and calculate contact paths and the speeds at which breaker contacts operate as well as the current in operating coils. It can also measure dynamic resistance (DRM), voltage, pressure, vibration signals and other analog entities. After measurement, the MA61 performs the necessary calculations and prints results in both diagram and table form on a connected printer (letter-size A4 paper) or via the TM1600's highspeed built-in printer. Moreover, parts of curves can be easily enlarged for closer study. The MA61 incorporates a battery-backed memory that can store up to ten measurements for subsequent processing.
TIME-MEASURING MODULE Number of channels 4 Time-measuring channels Each channel is independent of the others and has its own limited-current DC voltage source. Each channel can be set to measure main contacts, resistor contacts or to detect voltage. The input circuits are provided with 2.5 kV opto-isolators. Time-measurement at main contacts 0 to 250 . Test voltage is about 25 V. Measurement current is limited to about 150 mA. Time-measurement at resistor contacts 250 to 3 k. Test voltage is about 50 V. Measurement current is limited to about 30 mA. Voltage detection 12 to 250 V. Detection indicates that voltage is present. Independent of polarity. Provides a load of at least 3 W. Protection of inputs against transients All inputs have protective diodes. 18 kW, 8/20 µs between sockets and 4.8 kW, 8/20 µs between socket and ground. Induction protection Capacitive discharge to ground. Max 15 mA per input.
SPECIFICATIONS TM1600
Maximum configuration: 24 time-measuring channels (6 timemeasuring modules) or 16 time-measuring channels and six analog channels (4 time-measuring modules and one MA61). TIME MEASUREMENT Range 0 to 6.5 s (up to 200 s with CABA) Resolution 0.1 ms Accuracy 0.01% of printed value ± 0.1 ms Start time measurement Automatic a) when breaker is operated from the TM1600, b) when an external event actuates the trigger input or c) optionally when the status of any timemeasuring channel is changed. Trigger input Independent input with its own voltage source. Measurement starts when voltage is detected or when contacts close. Same data as for time-measuring channel when it is in the contact-measuring state or voltage detection state. Trigger output Closing capacity, up to 1 A BREAKER OPERATION Contact functions Two independent contact functions Contact properties Bounceless closing. Closing time < 0.1 ms Sequences C, O, C-O, O-C, O-C-O Make / break capacity 25 A, 250 V (AC or DC) per contact function Start breaker operation Locally via rotary switch or remotely by closing contacts at the opto-isolated start input. Time difference between control pulse and timer start Less than 0.1 ms. Pulse delay Adjustable in steps of 10 ms PRINTOUT Types of printout A number of different printout formats are available, both graphic and numeric. Printout can be obtained in English, German, French, Spanish, Italian, Swedish or Finnish. Printer Thermal printer with fixed print head Graphic resolution 6 dots/mm (150 dpi) Paper width 114 mm (4.5") POWER REQUIREMENTS 95-265 V AC or 100-375 V DC (set automatically) Mains operation Battery operation Built-in battery with automatic charger Charging time 10 h for full charge Battery operation time Typically at least 1 h of normal use Dielectric strength Complies with IEC 348 and IEC 255-5 between mains inlet, control and measurement circuits.
35
SPECIFICATIONS MA61
Number of channels Measurement ranges Measurement resolution Basic accuracy Dynamic errors Time-base accuracy Measurement interval Sampling frequency Display 1-6 Transducer resistance: 100 to 10 k. Voltage: -4 to +4 V. 0.03% (0.006% optional) 0.1% Motion: 1%. Speed: 3%. 0.02% 50, 100, 200, 400 or 1000 ms, userselectable (up to 200 s with CABA) 1-20 kHz (40 kHz optional) Back-lit LCD, two 16-character lines.
SPECIFICATIONS TM1600/MA61
Application field Intended for use in high-voltage substations and industrial environments. -20 to +50°C (-4 to +122°F) -10 to +50°C (+15 to +122°F) -30 to +70°C (-22 to +158°F) -30 to +85°C (-22 to +185°F) 400 x 250 x 153 mm (15.7" x 9.8" x 6.0") 6.5 kg (14.3 lbs) 0.6 kg (1.3 lbs) 1.1 kg (2.4 lbs) 5.1 kg (11.2 lbs)
Operating temperature, TM1600 Operating temperature, MA61 Storage temperature, TM1600 Storage temperature, MA61 Dimensions, TM1600 Basic Unit Weight, TM1600 Basic Unit Weight, time-measuring module Weight, MA61 Weight, transport case
Weight, complete TM1600/MA61 12 kg (26.5 lbs). 20 kg (44.1 lbs) with accessories and transport case. Warranty 1 year The above specifications are valid at nominal input voltage and an ambient temperature of +25°C (+77°F). Specifications are subject to change without notice.
TM1600/MA61
TM1600/MA61
APPLICATION EXAMPLE
Breaker timing with motion recording Breaker testing
Setup A typical breaker test hookup is shown here. Preparation Set the desired breaker operating sequence on the TM1600. In this case, CLOSE-OPEN (C-O). Recording Enable recording with the READY button. Start the breaker sequence and measurement simultaneously by turning the START switch. Test report The result is printed automatically. This example shows a CLOSEOPEN (C-O) sequence presented in the report 1 format (85 % of actual size). Only the initial contact closing time (for CLOSE) and final contact separation time (for OPEN) are presented in the report 1 format. Short bounces are not shown.
36
Setup Connect the transducers to the breaker. Preparation of the MA61 The following additional settings are needed when you include motion recording in breaker analysis. These settings are menudriven via the built-in display on the MA61. 1. Select test interval (50 ms to 1 s). 2. Calibrate the input(s) connected to the position transducer(s) as follows: a) Close the breaker. b) Record the closed position via a menu option. c) Open the breaker. d) Record the open position. e) Estimate or measure breaker stroke. Enter the value via the menu. f) Enter speed calculation parameters.
Close
Open
3. Enter the current range and the scale factor for the current shunt if current is to be measured. 4. Enter range and scale factor for other transducers (if used). Recording Press the READY button to prepare the TM1600 for measurement. Travel measurement, time measurement and the breaker sequence all start simultaneously when you turn the START knob. The inputs now record the input voltages obtained from the connected transducers. Test report The motion recording report includes both curves and a table. The table presents calculated breaker parameters such as closing speed, opening speed, overtravel and penetration. The diagram shows one or more time/amplitude curves and the calculated breaker parameters. The time axis scale factor can be changed to provide you with a quick overview or an enlarged view of part of the diagram.
37
The position of the curve in the diagram and the amplitude scale factor can also be changed to make best use of the available space. The damping and speed variations at closing and opening times can be studied on the speed curve obtained from each of the motion-monitoring channels.
TM1600/MA61
TM1600/MA61
OPTIONAL ACCESSORIES TM1600
CABA Win for TM1600/MA61
Breaker analysis software. Fiberoptic cable and modem included. Art.No: BL-8201X with externally powered modem (115 V) Art.No: BL-8202X with externally powered modem (230 V) Art.No: BL-8203X with internally powered modem
PIR Adapter
The adapter is used to test circuit breakers with pre-insertion resistors, when the resistance is lower than 250 or higher than 3000 . There are two versions: Art.No: BL-90080 (PIR, 15-250 Ohms) Art.No: BL-90082 (PIR2, 90-4500 Ohms)
Other
Program unit for CLOSE-OPEN-CLOSE-OPEN-CLOSE sequence. Art.No: BL-90090
Software for Long-Term Monitoring
Software for long-term monitoring of circuit breakers is available in an EPROM that can be mounted in the TM1600. There are two versions: LTM1, which starts measurement when there is a change at any of the time-measuring inputs. Art.No: BL-80010 LTM2, which functions in the same way as a standard TM1600, but returns automatically to the READY state after measurement. Art.No: BL-80011
OPTIONAL ACCESSORIES MA61
Transducers
Used to measure contact travel of circuit breakers and mechanisms. Delivered complete with cable for connection to the MA61. TLH 500 linear transducer 500 mm (20") travel. Art.No: XB-30020 LWG 225 linear transducer, 225 mm (9") travel. Art.No: XB-30117 TS 150 linear transducer 150 mm (6") travel. Art.No: XB-30030 IP 6501 rotary transducer 357° Art.No: XB-31010 Many other transducers are available. Contact Programma for more information.
Slave Unit TM1600
The slave unit provides a solution in situations where a large number of channels are needed. The general design is the same as that of the TM1600, but there are no breaker operating or printout provisions. The slave unit can be equipped with timemeasuring and analog channels as desired in the same way as the TM1600. The slave unit is delivered with a) a carrying case, b) one optical fibre cable, c) two 2 m (6.6 ft) trigger cables and d) one grounding cable. Art.No: BL-49090
Digital Transducer Converter DTC
This unit makes it possible to connect digital transducers to TM1600/MA61 and Egil. 1-channel or 3-channel models are available. Selectable range from ± 512 to ± 8192 pulses for full-scale reading. 5 V output to transducers. External power supply or powered from the MA61 printer DC-output. DTC 100, 1-channel digital transducer interface Art.No: BL-90200 DTC 103, 3-channel digital transducer interface Art.No: BL-90203
Cable sets for TM1600
The timing cable sets consist of 8 cables with clamps and banana plugs. Art.No: GA-00231 (8 x 5 m, 16.4 ft) Art.No: GA-00241 (8 x 10 m, 32.8 ft) Art.No: GA-00251 (8 x 15 m, 49.2 ft)
Cable Reel Extension
Cable reel and multi-connector for 4 timing channels, i.e. 1 timing module. Art.No: BL-90060 (without cable) Art.No: 03-10070 (cable, please specify length)
Mounting Kits for Transducers
Mounting kit for TLH, LWG, TS and IP transducers. Art.No: XB-39010 Mounting kit for linear transducers, TLH/LWH Art.No: XB-39065 Mounting kit for vibration transducers Art.No: XB-39070 Mounting kit for calibration of rotary transducer, IP6501 Art.No: XB-39095
Optical Fibre Link FB24
This optical fibre link improves personal safety by preventing any voltage from the breaker from reaching the TM1600. This also holds true for capacitively coupled voltages coming from other items of high-voltage equipment. Optical fibre link FB24 has three main parts: a) an input unit, b) a cable reel with 15 m (49 ft) of optical fibre cable and c) a receiver module. The receiver module is mounted on the TM1600 in the same way as a regular timemeasuring module. There are two versions of the receiver module. One has an optical fibre input and regular time-measuring inputs. The second has only an optical fibre input. The basic FB24 kit includes a battery charger and a transport case that accomodates three optical fibre links. Art.No: BL-91000 (basic FB24 kit including Art.No: BL-91001) Art.No: BL-91010 (basic FB24 kit including Art.No: BL-91011) The basic FB24 kit can also be supplemented with extra links. These are the same as described above, but without battery charger or transport case. Art.No: BL-91001 (optical fibre input plus time-measuring inputs) Art.No: BL-91011 (only optical fibre input)
Breaker-Specific Transducer Mounting Kits
For HPL circuit breaker (ABB). Art.No: XB-39080 For LTB circuit breaker (ABB). Art.No: XB-39090 For BLG operating mechanism (ABB). Art.No:: XB-39085 Other mounting kits are available. Contact Programma for more information.
Current Shunts
CS1601 current shunt used to measure current in operating coils. Measures closing and opening current on a single channel. Maximum current 25 A. Delivered complete with cable for connection to MA61. Art.No: BL-90050 CS1620 same as CS1601, but measures closing and opening currents on two separate channels simultaneously. Delivered complete with cable for connection to MA61. Maximum current 25 A. Art.No: BL-90053
38
HPA Adapter
Used to test the ABB (Asea Brown Boveri) HPA breaker. Connects directly to the breaker's transducer. Dimensions: 72 x 37 x 30 mm (2.8" x 1.5" x 1.2"). Weight: 0.2 kg (0.4 lbs). Art.No: BL-90010
CS1602 Measures closing and opening currents on three channels simultaneously. Delivered complete with cable for connection to MA61. Maximum current 25 A. Art.No: BL-90052
Voltage Divider VD401
The 400/1 voltage divider is suitable when you wish to measure voltage using the MA61. It can be used (for example) to take measurements on trip coils in order to check voltage drops in relays or cables. Art.No: BL-90070
Dynamic resistance measurement
Current Unit DRM1000 Used for dynamic resistance measurement of breaker contacts. The DRM1000 is connected to an external 12 V battery and can handle up to 1000 A. Art.No: BL-90041 Delivered complete, including the following: Art.No: BL-90040 Control unit DRM1000, including cable KG00702 (red) and cable KG-00706 (blue) with snap-on connector for a vehicle battery. Art.No: BL-90035 Connection box. Art.No: GA-00430 Sensing cables, two 2 m (6.5 ft) cables with clamps for connection between the breaker and the connection box. Art.No: 50-00110 Transport case. The following current cables are available: Art.No: GA-00424 (100 A) Art.No: GA-00422 (250 A) Art.No: GA-00420 (1000 A) Current Unit DRM10 Used for dynamic resistance measurement of breaker contacts. Has a built-in NiCd battery that can provide up to 50 A. Art.No: BL-90031 (115 V) Art.No: BL-90032 (230 V) Delivered complete, including the following: Art.No: BL-90030 DC source DRM10 Art.No: BL-90035 Connection box Art.No: GA-00430 Sensing cables, two 2 m (6.5 ft) cables with clamps for connection between the breaker and the connection box. Art.No: KG-00710, black + KG-00712, red. Current cables, 50 A Art.No: HC-04110, 230 V or HC-04111, 115 V. Battery charger Art.No: 50-00110 Transport case
Optical fibre link FB24
SCA 606
Vibration testing
Signal Conditioning Amplifier SCA600 Power supply, amplifier and signal conditioning filter for vibration testing using accelerometers with built-in charge amplifiers. Art.No: BL-13096 (with accessories)
Transducers for MA61
Accelerometer DYTRAN 3200B5 Art.No: XB-32010
Vibration Analysis Software
Separate CABA option for DTW-analysis. Art.No: BL-8170E
Transducer Mounting kit, BLG
39
TM1600/MA61
TM1600/MA61
ORDERING INFORMATION
The TM1600/MA61 Breaker Analyzer System can be equipped with time-measuring and analog channels as desired.
TM1600/MA61 Breaker Analyzer System
TM1600/MA61 Basic Unit for mains voltage 95-265 V. Includes two rolls of thermal printer paper, 2.5 m (8.2 ft) power cord, transport case and ground cable. TM1600/MA61 Basic unit with 16 time-measuring channels and 3 analog channels. With accessories (see MA61). Art.No: BL-39097 TM1600/MA61 Basic unit with 16 time-measuring channels and 3 analog channels. With accessories (see MA61) but external printer and keyboard excluded. Art.No: BL-39087 TM1600/MA61 Basic unit with 16 time-measuring channels and 6 analog channels. With accessories (see MA61). Art.No: BL-39098 TM1600/MA61 Basic unit with 16 time-measuring channels and 6 analog channels. With accessories (see MA61) ) but external printer and keyboard excluded. Art.No: BL-39088
TM1600 Breaker Analyzer
TM1600 Basic Unit for mains voltage 95-265 V. Includes two rolls of thermal printer paper, 2.5 m (8.2 ft) power cord, transport case and ground cable. Art.No: BL-39090 TM1600/4. TM1600 Basic Unit with 4 timing channels. Art.No: BL-39091 TM1600/8. TM1600 Basic Unit with 8 timing channels. Art.No: BL-39092 TM1600/12. TM1600 Basic Unit with 12 timing channels. Art.No: BL-39093 TM1600/16. TM1600 Basic Unit with 16 timing channels. Art.No: BL-39094 TM1600/20. TM1600 Basic Unit with 20 timing channels. Art.No: BL-39095 TM1600/24. TM1600 Basic Unit with 24 timing channels. Art.No: BL-39096 Separate module with four time-measuring channels Art.No: BL-19010
MA61 Motion Analyzer
MA61 Basic Unit. Includes external printer, printer cable, two ink cartridges, external keyboard, one 1.0 m (3.2 ft) shielded cable with female XLR connectors and banana plugs and a transport case for printer and keyboard. Art.No: BL-12090 MA61 Basic Unit, external printer and keyboard excluded Art.No: BL-12000 MA61/1. MA61 Basic Unit with 1 analog channel. Art.No: BL-12091 MA61/2. MA61 Basic Unit with 2 analog channels. Art.No: BL-12092 MA61/3. MA61 Basic Unit with 3 analog channels. Art.No: BL-12093 MA61/4. MA61 Basic Unit with 4 analog channels. Art.No: BL-12094 MA61/5. MA61 Basic Unit with 5 analog channels. Art.No: BL-12095 MA61/6. MA61 Basic Unit with 6 analog channels. Art.No: BL-12096 Separate module with one analog channel Art.No: BL-10010 Separate module with two analog channels Art.No: BL-12010 Each of the MA61/1-6 also includes one 1.0 m (3.3 ft) shielded cable/channel (with female XLR connectors and bare-wire ends), and one 7.5 m (24.6 ft) shielded cable/channel (with male and female XLR connectors). MA61S. High speed (40 kHz/14 bit) measurement module for vibration measurements with 2 analog channels. Art.No: BL-12020
Fully equipped TM1600 with 16 time-measuring channels and MA61 with six analog channels, BL-39098.
40
TM1600 Basic Unit, BL-39090.
TM1600 Basic Unit with four time-measuring channels, BL-39091.
MA61 Basic Unit, BL-12090 and MA61 Basic Unit with one analog channel, BL-12091.
Printer START/STOP and PAPER FEED button. Paper feed if pressed longer than 1 s. REMOTE START input. External short-circuit provides same result as turning the start switch (item 7). TRIG OUT. Output for synchronous start of other equipment. Short-circuits the terminals at instant of triggering. Used when several TM1600s are used together. TRIG. Input for external start of recording. Recording starts if the READY lamp is on. Input data: 0-250 polarized or 12-250 V unpolarized. Motion Analyzer MA61. Fuses for breaker control outputs.
· "PARKING" TERMINALS. Safety terminals for breaker control wires. Not connected to internal circuits. » Power ON/OFF. ¿ POWER-ON lamp. Flashing = Low battery. ´ Breaker control outputs. Two separate contact functions. ² Breaker operation SEQUENCE selector switch. C = Close, O = Open ¶ START of breaker operation and recording switch. Recording starts only if the Ready lamp is on. º CLOSE DELAY. Closing pulse delay setting. Pulse delay is measured from the start of the previous pulse. 10 ms resolution.
µ Timing channel input terminals. ¸ Timing channel mode switch. Contact mode: 0-250 . Resistor contact mode: 0-3 k. Voltage mode: 12-250 V unpolarized. ¹ READY for measuring button. Enables the timing channels. 1st touch: Prepares for normal recording. Enables the timing channels throughout 90 s. 2nd touch: Provides long-term monitoring (optional). READY lamp. Steady light: Ready for normal recording. Slow flash: Ready for long term monitoring (optional). Fast flash: Measurement in progress. PRINT MODE. Report format selector switch.
¿ » · ´
³
º ¾ ¹ ² ¶ µ ¸
Cable reel BL-90060
Cable set GA-00231
41
CS1601 Current shunt
DRM 1000
TM1600/MA61
³ Earth (ground) connection.
¾ OPEN DELAY. Trip pulse delay setting. Pulse delay is measured from the start of the previous pulse. 10 ms resolution.