Description
!
!
!
!
MTP-
5P
is designed for 5 RTD inputs. The unit
supplies effective temperature protection when 3 RTD
are mounted at motor winding and 2 - at the front and
rear bearings. MTP-5P includes two relays outputs:
one for winding RTD and one for the bearings RTD.
MTP-
3P-R
includes 3 RTD inputs at motor winding
and 2 relays outputs for ALARM and TRIP.
!
!
!
!
Operation
!
!
!
!
MTP-5P alarms when inputs signal exceeds the
t
hresholds SET-A (for R,S,T inputs) and SET-B (for F.B
inputs).
Five Red LEDs R,S,T,F,B [3] are "on" at alarm. Two
other LEDs (Green and Yellow [2]) indicate relays
status: the Green LED is "off" when alarm relay (R,S,T
inputs) is off. The Yellow LED lights on alarm and
relay (F,B inputs) is on.
Both output relays change status after delay of 10 sec.
MTP-3P-R alarms when inputs signal exceeds the
t
hreshold SET-A and trip when the inputs exceed the
trip set point SET-B. Three Red LEDs R,S,T [3] are
"on" at alarm. The Green LED is "on" at normal
condition (relay is on), and "off" at alarm.
!
!
!
!
Calibration
!
!
!
!
!
!
!
!
Specifications
!
!
!
!
Accuracy
:
+0.1% F.S.
Power supply
:
110
/220+20
%VAC
or 24
V
AC/DC
Input:
5 PT100 temp. sensors (3 wire).
Option:
4-20
mA
(according to order)
Output:
2 c/o contact 220
V
/
5
A
. The relays are
activated after 10 sec delay.
Operation mode of
relay - FSH (relay A) and FSL (relay B).
Ambient Temp
.
:
-10
{
+50
}
C
Temperature stability:
0.05% at changes @10oC in ambient temp.
Display:
3.5 digits (0-199.9) LCD
size 0.5".
5 red LED indicating input- above set point.
Enclosure:
W72 x H144 and depth D150 mm
plastic case. Panel cutout 67 x 139mm.
Connection
: 2 plug-in terminals on box side
Mounting
MTP5-P-2-05-E
The device is calibrated
according to customer
requirements. Set points
can be adjusted by
potentiometers Set A
and Set B
[4]
located on
the front panel. Selector
switch
[5]
enables to
display
[1]
inputs / set-
points value.
1
2
3
4
5
6
7
8
9
10
11
12
~
0
T
R S
220 Vac
Input
PT100
13
14
15
16
17
18
19
20
21
22
23
24
F
A(RST) B
B(FB)
Input
PT100
Out
MEGATRON
MTP5P
SET SET
A B
3
4
5
1
2
T
S R
SET B F
B
A
R S T
F B
!
!
!
!
Connection
!
!
!
!
!
!
!
!
Installation
!
!
!
!
* The PT-100 connections to the MTP should
be by shielded cable. It is recommended to
join all shields together by a connector and to
ground them. Don't ground the second side
of shields.
* It is necessary to install resistors 100
1/4W to inputs without PT-100 (for instance,
4,5) and to connect two other pins
(
5,6
).
: fixed by 2 holding clamps to panel.
A metal holder for wall mounting is available.
Protection category:
IP-51.