Model T6000 Electro-Pneumatic I/P, E/P Transducer

y basic unit
to be used in the explosion-proof,
rack, wall, pipe, panel, DIN rail or 3,
5, 10, or 15 unit manifold
configurations. Servicing or
calibration is quick and easy.
84
800-334-8422
Features
Field reversible feature provides output
which is directly or inversely proportional to
the input signal.
RFI/EMI Protection eliminates susceptibility
to electromagnetic and radio interference.
Six output pressure ranges meet final
control element requirements.
Six input signal ranges meet most process
and machine requirements.
Compact size permits use in space
restricted areas.
Explosion-Proof NEMA4X, IP65,Type 4
Enclosure available for outdoor and indoor
installations.
Input and Output ports on both front and
rear simplifies pneumatic piping.
Operating Principles
Standard Range
The T6000 Series is an electro-pneumatic
device that converts a DC input signal to a
pneumatic output. This device is made up
of two sections, the Primary Converting
Section and the Pneumatic Relay Section.
The Coil and Suspension Spring, in the
Primary Converting Section, is used as a
Flapper. Together the Flapper and Nozzle
work to control the signal pressure. The
signal pressure acts on the Upper Control
Diaphragm, in the Pneumatic Relay Section,
which sets the output pressure. The output
pressure is sensed by the Lower Control
Diaphragm, in the Pneumatic Relay Section,
which maintains the output pressure.
Extended Range
The Extended Unit is made up of three
sections, the Primary Control Section, the
Pneumatic Relay Section, and an additional
Pneumatic Relay Section. The additional
Relay Section is used to amplify the output
pressure.
T6000 Standard Range
T6000 Extended Range
B
Model
T6000 Model T6000 Electro-Pneumatic I/P, E/P Transducer
85
800-334-8422
TT6000 Standard Range
TD6000 Standard Range
TR6000 Standard Range
Specifications:
T6000 Standard Range Transducers
Output
psig
3-15
3-27
6-30
Range
[BAR]
[0.2-1.0] [0.2-1.8] [0.4-2.0]
(kPa)
(20-100) (20-180) (40-200)
Supply
psig
20-120
32-120
35-120
Pressure
1
[BAR]
[1.5-8.0]
[2.2-8.0]
[2.4-8.0]
(kPa)
(150-800) (220-800) (240-800)
Minimum
psig
5
10
10
Span
[BAR]
[0.35]
[0.7]
[0.7]
(kPa)
(35)
(70)
(70)
Impedance 4-20 mA 197
204
204
(OHMS) /
10-50 mA
79
82
82
Input Signal 0-5 VDC 550
532
532
0-10 VDC 1100
1064
1064
1-5 VDC 500
483
483
1-9 VDC 1000
970
970
Air Consumption
5.0
6.0
6.0
(per ISAS51.1) SCFH
(.14 m
3
/HR) (.17 m
3
/HR) (.17 m
3
/HR)
Independent Linearity +0.5%FS +0.5%FS +0.5%FS
(per ISAS51.1)
Hysteresis & Repeatability 0.25%FS 0.25%FS 0.25%FS
(per ISAS51.1)
Supply Pressure Effect on Output
0.25psig,[0.17BAR],(1.7kPa)fora25psig,[1.7BAR],(170kPa)supply
change
Flow Rate (SCFM)
2.5(4.25m
3
/HR)@25psig,[1.7BAR,(170kPa)Supply&9psig,[0.6BAR],
(60kPa)Output.
9.0(15.3m
3
/HR)@120psig,[8.0BAR,(800kPa)Supply&9psig,[0.6
BAR],(60kPa)Output.
RFI / EMI Effect
Lessthan0.5%ofSpan@30v/mclass3BandABC(20-1000mHz)per
SAMAPMC33.11978andlessthan0.5%ofSpan@10v/mlevel3,27-500
mHzBandperIECStandard801-31984. EMCDirective89/336/EEC
EuropeanNormsEN50081-2andEN50082-2.
Temperature Range (per ISAS51.1)
-20
o
F to +150
o
F, (-30
o
C to +65
o
C)
Materials of Construction
Body and Housing...................................Aluminum
Trim ........................................Zinc Plated Steel
Diaphragm............................................Nitrile
Orifice ....................................Nickel Plated Brass
1
Supply Pressure must be no less than 5 psig, [0.35 BAR],
(35 kPa) above minimum output.
TA6000 Standard Range
NOTE: Model TR6000 Transducer is designed for use with the
TR Rack Kit. Physically, it is the same as the TT6000 Unit except
that the terminal block has been rotated to the rear.
B
Model
T6000 Model T6000 Electro-Pneumatic I/P, E/P Transducer
86
800-334-8422
TT6000 Extended Range
TD6000 Extended Range
TR6000 Extended Range
Specifications:
T6000 Extended RangeTransducers
Output
psig 0-30
0-60
0-120
Range
[BAR] [0-2.0]
[0-4.0]
[0-8.0]
(kPa) (0-200) (0-400)
(0-800)
Supply
psig 35-150
65-150 125-150
Pressure
1
[BAR] [2.5-10.0] [4.6-10.0] [8.8-10.0]
(kPa) (250-1000) (460-1000) (880-1000)
Minimum
psig
12
25
50
Span
[BAR] [0.8]
[1.5]
[3.5]
(kPa) (80)
(150)
(350)
Impedance 4-20 mA 250
256
270
(OHMS) /
10-50 mA 100
103
108
Input Signal 0-5 VDC 439
469
446
0-10 VDC 878
938
893
1-5 VDC 400
453
430
1-9 VDC 800
750
714
Air Consumption
12.0
13.0
17.0
(per ISAS51.1) SCFH
(.34 m
3
/HR) (.36 m
3
/HR) (.48 m
3
/HR)
Independent Linearity 0.75% FS 1.0% FS 1.0% FS
(per ISAS51.1)
Hysteresis & Repeatability <1.0% FS @<1.0% FS @ <1.0%FS@
(per ISAS51.1)
35 psig, 65 psig, 125 psig,
[2.5 BAR], [4.6 BAR], [8.8 BAR],
(250 kPa) (460 kPa) (880 kPa)
Supply Pressure psig 0.5
1.0
1.5
Effect on Output[BAR] [0.03]
[0.07]
[0.1]
For a 25 psig,
(kPa) (4.0)
(7.0)
(10.5)
[1.7BAR],(170kPa)
supplychange
Flow Rate (SCFM)
11(18.7m
3
/HR)@150psig,[10BAR,(1000kPa)Supply&9psig,[0.6
BAR],(60kPa)Output.
RFI / EMI Effect
Lessthan0.5%ofSpan@30v/mclass3BandABC(20-1000mHz)per
SAMAPMC33.11978andlessthan0.5%ofSpan@10v/mlevel3,27-500
mHzBandperIECStandard801-31984.EMCDirective89/336/EEC
EuropeanNormsEN50081-2andEN50082-2.
Temperature Range (per ISAS51.1)
-20
o
F to +150
o
F, (-30
o
C to +65
o
C)
Materials of Construction
Body and Housing...................................Aluminum
Orifice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nickel Plated Brass
Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Zinc Plated Steel
Diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nitrile
1
Supply Pressure must be no less than 5 psig, [0.35 BAR],
(35 kPa) above maximum output.
TA6000 Extended Range
NOTE: Model TR6000 Transducer is designed for use with the
TR Rack Kit. Physically, it is the same as the TT6000 Unit except
that the terminal block has been rotated to the rear.
B
Model
T6000 Model T6000 Electro-Pneumatic I/P, E/P Transducer
87
800-334-8422
Hazardous Area Specifications
Explosion-Proof
Intrinsically Safe
Factory Mutual
Class I, Division 1, Groups B, C and D;
Class I, II, and III, Division 1, GroupsA, B, C,
(FM) Approvals
Class II, Division 1, Groups E, F, and G;
D, E, F, and G.
NEMA4X Enclosure.
Canadian Standards Class I, Division 1, Groups B, C and D;
Class I, Division 1, GroupsA, B, C and D;
Association (CSA) Class II, Division 1, Groups E, F, and G;
Temperature Code T3C.
Approvals
Type 4 Enclosure.
Rated 4-20 mA, 30 VDC Maximum.
ATEX Approvals
II 1G EEx ia IIC T4 (T
a
= -20 C to +65 C)
Entity Parameters
Vmax
1
= 40 VDC Ci
3
= O F
Imax
2
= 125 mA Li
4
= 3 mH
1
Vmax = Max. Voltage
3
Ci = Capacitance
2
Imax = Max. Current
4
Li = Inductance
Transducer Parameters
Umax
1
= 28 V Pi
3
= 0.653 W
Imax
2
= 93 mA Ci
4
= 0
Li
5
= 0
1
Umax = Max. Voltage
3
Pi = Max. Power
2
Imax = Max. Current
4
Ci = Capacitance
5
Li = Inductance
Approvals are valid when connected
through a Shunt Zener Diode Safety
Barrier meeting the following
parametric requirements:
System Type 1:SingleChannelPolarizedRated:
28VMax.300OhmMin.
System Type 2:DualChannelPolarizedRated:
28VMax.300OhmMin.
System Type 3:a. 28VMax.300OhmMin.&
10VMax.50OhmMin.return.
b. 28.5V Max. 300 Ohm Min. &
9V Max. 50 Ohm Min. return.
1
ATEX not available for Explosion-Proof.
2
Intrinsically Safe for Current Inputs Units Only.
B
Model
T6000 Mounting Kits
Catalog Information
Model T6000 Transducer Kits
& Accessories
Mounting Bracket Kits .... 16799-1 (included with unit)
16893-1 (included with unit)
19254-1 (sold separately)
18187-1 (sold separately)
Mounting Bracket:
19254-1
Mounting Bracket:
18187-1
Mounting Bracket:
16799-1
Mounting Bracket:
16893-1
Model T6000 Electro-Pneumatic I/P, E/P Transducer
88
800-334-8422
Catalog
Number T
6 0 0 0
Electrical Connections
1/2 NPT Conduit . . . . . . . . . . . A
Fitting with Pigtail
DIN43650 Connection . . . . . . . D
Rack Mount . . . . . . . . . . . . . . . R
Terminal Block . . . . . . . . . . . . T
(leave blank for
Explosion-Proof) . . . . . . . .
Underwriting Group
Canadian Standards . . . . . . . . . . . . C
ATEX
1
. . . . . . . . . . . . . . . . . . . . . . . E
Factory Mutual . . . . . . . . . . . . . . . . F
Approval Class
Explosion-P
roof. . . . . . . . . . . . . . . . . . . . . . XPD
Dust Ignition-Proof (includes NEMA
4X/IP 65)
Intrinsically Safe
2
. . . . . . . . . . . . . . . . . . . I
None (leave blank) . . . . . . . . . . . . . . . . . .
Input
4-20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
10-50 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-5 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
0-5 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-9 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
0-10 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Output
(Select appropriate psig, [BAR], or (kPa) range.)
3-15 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 01
3-27 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
6-30 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
0-30 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
0-60 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
0-120 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
[0.2-1.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
[0.2-1.8 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
[0.4-2.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
[0-2.0 BAR] . . . .