ELECTRICAL PUMP PROTECTION

PumpSavers without a NEMA 3R enclosure available upon request.
© 2005 ITT Water Technology, Inc.
Effective April, 2005
BCPSAVER
PumpSaver is a registered trademark of SymCom, Inc.
CentriPro is a brand of ITT Water Technology, Inc.
a subsidiary of ITT Industries, Inc.
CentriPro and the ITT Engineered Blocks Symbol are
registered trademarks and tradenames of ITT Industries.
PUMPSAVER 235
SPECIFICATIONS
Order No. HP
Volts Phase Hertz Reset Time Delay Enclosure Comparable to
2353RL50 5 to 7.5 230
1
50 60 2-225 minutes
NEMA 3R
AW500
2353RL75
10
230
1
50 60 2-225 minutes
NEMA 3R AW201A1015
2353RL100
15
230
1
50 60 2-225 minutes
NEMA 3R Includes appropriate current transformer Individual 235 PumpSavers without enclosures, and individual current


transformers available upon request.
APPLICATIONS SINGLE PHASE ONLY
All submersible pumps, regardless of motor
manufacturer
Centrifugal pumps
Circulating pumps
Cooling pumps
Environmental pumps
Residential water wells
Commercial water wells
Irrigation wells
Golf course systems
Protects From:
Dry well (run dry condition)
Flow restrictions (dead head)
Over current (jammed impeller)
Over voltage
Under voltage
Rapid cycling
FEATURES
Can be calibrated to specic pump / motor

combinations and various conditions
Will work with destaged pump models ending in 05R
Infrared LED communication with the INFORMER
makes diagnostics simple
Run Light indicates the unit is functioning
Run Light and Cal. Light used as diagnostic
indicators
Restart delay can be set up to 225 minutes or placed
in manual reset mode
Micro-controller provides better accuracy and higher
reliability than analog designs
5 year warranty PRINTED IN U.S.A.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
CentriPro
ITT Industries
ELECTRICAL
PUMP PROTECTION
PumpSaver by SymCom
PUMPSAVER 111 INSIDER AND 231 INSIDER
SPECIFICATIONS
Order No.
HP
Volts
Phase
Hertz Reset Time Delay Comparable to
111Insider
1 3
to 1
115
1
60
2-225 Minutes
AWQDP
231Insider
1 3
to 1
230
1
60
2-225 Minutes
APPLICATION
Submersible pump with
a quick disconnect style
control box
Protects From:
Dry well (run dry condition)
Flow restrictions
(dead head)
Over current

(jammed impeller)
Over voltage
Under voltage
FEATURES
Fits inside a 3 wire quick
disconnect style control box
Can be calibrated to specic
pump / motor combinations
and various conditions
Will work with destaged
pump models ending in 05R
Infrared LED communication
with the INFORMER makes
diagnostics simple
Quick and easy installation
less than 30 seconds
Run Light indicates the
unit is functioning
Run Light and Cal. Light
used as diagnostic indicators
Restart delay can be set up
to 225 minutes or placed in
manual reset mode
5 year warranty
INFORMER
FEATURES
The Informer is a handheld diagnstic tool designed for use with
single-phase PumpSaver models.
The Informer uses an infrared receiver to access data sent from
the PumpSaver, which can be helpful for troubleshooting the
system.
The Informer displays parameters including:
Real-time voltage, current and power
Dry-well and overload trip points
Calibration voltage
Last fault condition
Voltage, current and power at last fault condition
Highest/lowest voltage and current since last calibration
SPECIFICATIONS
Order No.
Description
INFORMER
Hand Held



Diagnostic Tool CentriPro
ITT Industries
ELECTRICAL
PUMP PROTECTION
PumpSaver by SymCom
INSIDER MOUNTED IN
SUBMERSIBLE CONTROL BOX
SOLID-STATE
SWITCH
111/231
INSIDER
B(MAIN)
Y(COMM)
BLK
RED
ORANGE
YEL
BLUE
R(START)
L2
L1
CAPACITOR
PRESSURE SWITCH
OR OTHER CONTROL
PUMPSAVER
111 / 233
L1
IN
L1
OUT
L2
IN
OUT
L2
FUSED DISCONNECT
OR CIRCUIT BREAKER
GND
L1
L2
PRESSURE
SWITCH
OR OTHER
CONTROL
L1
L1
L1
L1
L2
L2
L2
L2
GND
GND
GND
PRESSURE SWITCH MAY BE INSTALLED
AHEAD OF THE PUMPSAVER WHEN
RAPID CYCLE PROTECTION IS
NOT REQUIRED
GND
TO MOTOR OR CONTROL BOX
PUMPSAVER 111 / 233
TYPICAL WIRING DIAGRAM
To install in control box
Remove blue wire from terminal strip and solid
state switch (blue relay) and set aside.
Remove yellow jumper wire from terminal L2.
Install Insider by aligning tabs with upper L2 & L1
tabs and pushing onto tabs.
Connect yellow wire onto L2 terminal on Insider.
Connect blue wire attached to Insider to solid state
switch (blue relay). PRINTED IN U.S.A.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
CentriPro
ITT Industries
ELECTRICAL
PUMP PROTECTION
PumpSaver by SymCom
PUMPSAVER 235 TYPICAL WIRING DIAGRAM WITH DELUXE CONTROL BOX
GND L2
L1
FUSED DISCONNECT
OR CIRCUIT BREAKER
L1
L2
CT
L1
SW
L2 YEL BLK RED
DELUXE CONTROL BOX
PUMP
MOTOR
PUMP
PRESSURE SWITCH
OR OTHER CONTROL
L1
CT1
CT2 L2 IN L2 OUT