ce
to receptacles in the operating room, it is also recommended for all flammable
anesthesia, wet and other locations
where the interruption of power cannot
be tolerated.
Isolated Power Panels
THE COMPLETE ISOLATED POWER SYSTEM
The GE Isolated Power Center adds receptacles to the Isolated Power
Panel. Depending on the units kVA rating, it can include up to eight 120V,
UL listed twist-lock, duplex or parallel blade receptacles and up to seven
ground jacks for additional grounding points. It can also feed remote and
panel-mounted receptacles. This makes it ideal for use in intensive care and
coronary care units
and suitable for cardiac catheterization labs, neonatal
units, emergency rooms, critical care and recovery areas
as well.
Isolated Power Centers
THE ISOLATED POWER SYSTEM PLUS RECEPTACLES
No power interruption with a one-line to ground fault
Visible and audible indications of hazardous situations
Reduced effects of common-mode noise
Quick, and simple field installation
Easy-to-clean stainless steel front trim
Line Isolation Monitor identifies ground faults both upstream and
downstream of the distribution circuits
Flexible design adapts to varying specifications and applications
The benefits to you
ADDED SAFETY AT NO ADDITIONAL COST
GEs commitment to quality and safety is evident in the components used in Isolated Power Panels and
Isolated Power Centers. These components include:
The value of GE
HIGH QUALITY, MAXIMUM SAFETY
CHASSIS mounts inside the back box
and supports the isolation transformer,
the LIM and the circuit breaker panel.
ISOLATION TRANSFORMER is a single-phase, stacked core with
electrostatic shield, designed for low leakage and quiet operation.
Ratings
3, 5, 7.5, 10 or 15 kVA
Primary voltage
120, 208, 220, 240, 277 or 480
Secondary voltage
120, 208, 220, 240
Maximum leakage current
3kVA, 5kVA
10 microamps
7.5 kVA
14 microamps
10kVA
25 microamps
15kVA
30 microamps
FRONT TRIM PANEL fabricated from #12 gauge,
304 stainless steel polished to a #4 satin finish
is standard. An optional continuously hinged
front trim panel is available.
BACK BOX is heavy duty,
made of galvanized steel
and designed for either
flush or surface mount-
ing. It can be shipped
ahead of the interior to
make simplify the rough-
in phase of construction
or renovation.
GROUND BUS is used to
connect all internal and
branch ground conductors.
TERMINAL BLOCK allows
for connection of remote
signal conductors.
FIELD WIRING COMPARTMENT is formed
by a baffle and fastened to the chassis.
LINE ISOLATION MONITOR (LIM) offers continuous
monitoring with non-switching circuitry. Audible and
visible alarm indicators are easily accessible and not
obscured when the circuit breaker door is opened.
Other features include:
Self-testing and self-calibrating
Low monitor hazard current of 25 microamps
5 or 2 milliamp alarm point
LED panel meter and indicator lights
Sensitivity to LIM loss of ground
Self-resetting fuses
CIRCUIT BREAKER PANEL conforms to
code requirements with high-quality
GE 2-pole bolt-on breakers. The panel
houses the primary main circuit breaker
and up to 16 secondary breakers, all
UL listed.
LOCKABLE DOOR
prevents unautho-
rized operation or
accessibility with
a Corbin lock over
the GE circuit
breaker panel.
GE Industrial Systems
General Electric Company
41 Woodford Avenue, Plainville, CT 06062
www.GEindustrial.com
© 2002 General Electric Company
DEA-337 1202
ACCESSORIES
GE offers the following accessories to complete the installation of GE Isolation Power Panels
and GE Isolation Power Centers. These accessory products are built to ensure patient safety
while making the isolation power system easier to operate and monitor.
Remote Annunciator Panels
Remote Receptacle Panels
Master Remote Annunciator Panels
Power and Ground Modules
Ground Modules/Ground Jack Panels
Master Ground Modules
Ground Cord Assemblies
kVA/Type
Approximate Dimensions (inches) *
Back Box (H x W x D)
Flush Trim (H x W)
3, 5, 7.5, 10 (vented), 15 (vented)
60 x 25 x 10
61
3
4
x 26
3
4
10 (non-vented), 15 (non-vented)
60 x 25 x 12
61
3
4
x 26
3
4
UL LISTINGS
UL 1047 Isolated Power Systems Equipment
UL 1022 Line Isolation Monitors
DIMENSIONS
Isolated Power Panels & Isolated Power Centers
*Dimensions subject to change without notice and are NOT for construction/rough-in use.