www.geindustrial.com/products/reference/GEAD3100.pdf

width="100%" bgcolor=white>
Untitled
g
GE Digital Energy



Revolutionizing
Power Quality and Reliability
Advanced Power Systems
TM
Product Description
GE Digital Energy
2018 Powers Ferry Road
Suite 500
Atlanta, Georgia 30339

GE Proprietary Information
February 2002
g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
1/8
Product Description APS500 - APS2050



Product Description
Advanced Power Systems
TM

Models: 500 2000 kW




















Contents

Page


1. INTRODUCTION ........................................................................................................................ 2

2. STANDARD FEATURES ........................................................................................................... 2

3. OPTIONS.................................................................................................................................... 3

4. RATINGS.................................................................................................................................... 4

5. GENERATING MODULE ........................................................................................................... 5

6. CONDITIONING MODULE ........................................................................................................ 6

7. HOW THE APS WORKS ........................................................................................................... 8
g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
2/8
Product Description APS500 - APS2050


1. INTRODUCTION

The GE Digital Energy Advanced Power System
TM
(APS
TM
) is a self-contained unit designed to
provide essential (generator backed up power) and critical (UPS conditioned) power to mission
critical facilities. Multiple APS units are connected together to form a highly reliable mission
critical power system. Each APS unit is assembled and tested in the factory before shipment to
the customers site. Once on site, the GE Digital Energy commissioning team will insure the unit
is correctly installed and integrated into the power system.



2. STANDARD FEATURES

Standard Outdoor Weather Resistant Module Design
130 mph wind rating at zero feet elevation.
Seismic Zone 2 construction (Importance 1.0 Factor)
12 inches per hour rain with no rainwater entry
85db noise rating @ 21 feet
APS Diesel Generator Module Standard Features
Integral 220 gallon fuel tank with containment
Low NOx Diesel Engine
Generator Auxiliaries and Exhaust Systems
Integrated Cooling and Heating systems
APS Condition Module Standard Features
Double Conversion UPS with Static Bypass
Flywheel Energy Storage Systems
UPS Maintenance Bypass
Integrated Power Switchboard
Utility Grade Multifunction Protective Relays.
Standard APS Control System

Automatic
Open Transition Control

Standard Operator Control Switches

System alarm and status annunciator
Built in power monitoring systems.
Open communication standards
APS System Support
Standardized Factory Testing
System Integration
Single source program and warranty management
g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
3/8
Product Description APS500 - APS2050


3. OPTIONS


Premium Outdoor Weather Resistant Modules Design
150 mph wind rating at 400 feet elevation.
Seismic Zone 4 construction (Importance 1.5 Factor)
12 inches per hour rain with no rainwater entry
75db noise rating @ 21 feet (other db rating available consult with
the factory)
APS Diesel Generator Options
Integral 1500 gallon fuel tank with containment
Secondary Catalytic Reduction (SCR) emission system
Redundant starting batteries and motors
Extended enclosure cooling and heating systems.
APS Conditioning Module Options
Closed Transition Transfer
Peak Shaving Controls
Load Bank circuit breaker
Additional Flywheel reserves
APS System Support
Onsite Monitor Remote Monitoring Control
Factory Witness Testing
Startup and Commissioning Services
Technical Direction of Installation
Long Term Service Contracts
Permanent Load Banks and Controls

g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
4/8
Product Description APS500 - APS2050


4. RATINGS




Model
Generating Module
Diesel Gen Power
(kW 60 Hz / kW 50 Hz)
1

Conditioning Module
UPS Power
(kVA 60 Hz / kVA 50 Hz)
1

APS500
500 / 463
300 / 300
APS1000
1000 / 968
625 / 500
APS1500
1500 / 1452
750 / 800
APS2000
3

2000 / 1936
1250 / 1000
APS2050
3

2000
2

1500
2

1
The 60 Hz unit is based on UL standards and the 50 Hz unit is based on CE standards.
2
APS2050 currently not available in CE Product Family
3
Multi- module UPS system with 100% rated static bypass switch
Simplified APS One-line
Incoming
Utility
Essential
Power
UPS
AC
DC
DC
AC
Fly Wheel
Fly Wheel
Critical
Power
Static Bypa ss
Maintenance Bypass
Diesel - Generator
Incoming
Utility
Essential
Power
UPS
AC
DC
AC
DC
DC
AC
DC
AC
Fly Wheel
Fly Wheel
Critical
Power
Static Bypa ss
Maintenance Bypass
Diesel - Generator g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
5/8
Product Description APS500 - APS2050


5. GENERATING MODULE

Stand-by Diesel Generator
The diesel generator set includes all required radiators, ventilation, controls, and exhaust
systems.

Integral 220-gallon fuel tank
A fuel tank is included in the module along with all required valves, fuel pipes and fittings to
connect the system to an external fuel supply system. Fuel tank is designed with 110%
containment.

Dimensions
All dimension given are for the standard design enclosure. Enclosure sizes will change due
to noise rating and enclosure specifications. Roof top fans and other accessories will be
installed at site to keep the shipping height of the enclosure under 12 feet.




Generating Module Dimensions


Model
L (ft/m)
W (ft/m)
H (ft/m)
Weight (lbs)
APS500
35 / 10.5
11 / 3.3
12.3 / 3.7
70,000
APS1000
37 / 11.3
11 / 3.3
12.3 / 3.7
80,000
APS1500
38.9 / 12.2
11 / 3.3
12.3 / 3.7
86,000
APS2000
38.9 / 12.2
11 / 3.3
12.3 / 3.7
90,000
APS2050
1

38.9
11
12.3 / 3.7
90,000

1
APS2050 currently not available in CE Product Family


L
W
H g


GE Digital Energy

GE Proprietary Information

APS Product Description Rev. 0 02/20/02
6/8
Product Description APS500 - APS2050


6. CONDITIONING MODULE

Integrated Power Switchboard
The Power Switchboard contains draw-out insulated case circuit breakers, insulated bus, and at
least a 100 kaic short circuit rating. In addition, all required PT's, CT's and protective relays will
be provided to allow the generator to parallel to the incoming utility source. Each breaker in the
switchgear will contain a solid-state trip unit that will have the ability to monitor and communicate
breaker status and power values to a remote monitoring system. All breakers are operated by an
internal 24 Vdc station battery system and require no outside sources of control power.

Utility Grade Multifunction Protective Relays
One Multilin 750 relay and one Multilin 489 relay are provided to protect the incoming utility and
generator. Each relay is interfaced to the APS control system to coordinate the overall operation
of the module and system alarm detection. Each Multilin relay includes monitoring and metering
functions that can be viewed by the 40 character vacuum florescent display on the meter. This
information can be communicated to a remote monitoring system using standard Modbus RTU
protocol. All meters are factory wired to the APS ModBus network for use by the customer
remote monitoring system. An additional synchronism check relay (25) is provided to act as an
additional control permissive when paralleling the generator and utility source breakers.

UPS system
The UPS system has the following features and characteristics:
AC Input Voltage, 480V