Description
The universal SPA Site-Programmable Alarms
provide on/off control, warn of trouble, or provide
emergency shutdown. They accept a direct input
from transmitters, temperature sensors, and a wide
array of other monitoring and control instruments:
Current and Voltage Signals
(4-20mA, 1-5V, 0-250Vac, 0-5Aac, etc.)
23 RTD Types
(2-, 3-, and 4-wire; Pt, Cu and Ni;
10 to 1000 ohms)
8 Thermocouple Types
(J, K, E, T, R, S, B, and N)
Resistance and Potentiometer Devices
(0 to 4000 ohms)
Direct Millivolt Sources
(-10 to 120mV)
They provide two or four alarm relay outputs when a
monitored process variable falls outside of user-set
high and/or low limits. Connect the 4-wire
(line-powered) SPA to a warning light, annunciator,
bell, or shutdown system, and your process is
protected by a simple, highly reliable, independent
warning and/or shutdown strategy.
Features
Universal plant standard. Theres no need to
stock dozens of different fixed range alarm trips.
Site-programmable with on-board controls.
Your fingers are the only tools you need to get our
SPA up and running fast. All operating parameters
configure using on-board controls.
Real-time process readout. A front panel
indicator provides menu prompts during
configuration, and displays the process variable in
user-selectable engineering units.
Alarm trip and transmitter combination. The
analog output option reduces costs and installation
time when both transmitter and alarm functions are
needed at the same location (see Page 3).
Certifications
Table of Contents
Page
Family Overview of SPA Site-Programmable
2-3
Functions and Special Features
mA and Vdc Input Models (HLPRG)
4-5
Vac and Amp Input Models (ACPRG and ACIPRG)
6-7
RTD, Thermocouple, Ohm (Resistance/Potentiometer)
8-11
and mV Input Models (TPRG)
Housing and Installation Dimensions (All Models)
12-13
Terminal Designations and Hookups (All Models)
14-15
Typical SPA Universal Alarm Solutions
16
© 2007 Moore Industries-International, Inc.
224-710-06D Site-Programmable Current/Voltage
and RTD/Thermocouple Limit Alarm Trips
SPA
Page 2
On-Site Programming
Input type, range, trip points, and other frequently
changed operating parameters configure quickly and
easily from the front panel keypad. Simple prompts
on the SPAs LCD guide you through a plain-English
selection menu. Available programmable functions
include*: Input type and range Zero and full scale Alarm trip points, high or low alarm, deadband,
time delay, latching or non-latching Engineering unit readout (V, mA, %, °C, °F,
psig, mV, ohms, or optional custom engineering
units) Position of LCD decimal point for custom
engineering unit representation Upscale or downscale drive on sensor failure T/C reference junction compensation (on/off) Standard and custom linearization curves Differential or averaging of RTD inputs Current source or sink, or voltage output Security password protection
Figure 2. Menu prompts on the front panel LCD guide you through setup and viewing options
Programmable
Input
mA
V
Vac
Aac
RTD
T/C
ohms
mV
Programmable
Alarm Trip(s)
Dual Relays
Quad Relays
(Trip Points
High Alarm
Low alarm
Failsafe
Non-Failsafe
Normally Open
Normally Closed
Latching
Non-Latching)
Figure 1. Available models deliver versatile input/output choices
Quick Ranging Calibration
The SPA features our revolutionary Quick Ranging
Calibration method. Using the push buttons (instead
of potentiometers which can drift) and the integral
display, precise zero and span settings can be made
in seconds. All you have to do is scroll to the zero or
span value you want and a push of a button locks the
value into the SPAs memory.
* Some of the programmable functions listed are not applicable to, or
available on, all models.
275
DEG C
SPA
View Trip
Point for
Low Alarm
#1
000.0
AL 1L
100.0
AL 2H
View Trip
Point for
High Alarm
#2
23.5
AL 3L
View Trip
Point for
Low Alarm
#3
315.6
AL 4H
View Trip
Point for
High Alarm
#4
VIEW
SELECT
ENTR
PASS
CONF
SENS
CONF
OPTS
Enter
Password
for
Protection
Code
Set
Input Type
Set
°C or °F
Upscale or
Downscale
Linearization
(Yes/No)
CONF
ALRM
Set Trip
Points and
Other Alarm
Parameters
PASS
WORD
Change
Password
Code
CONF
Z/FS
Quick
Ranging.
Set Zero
and Full
Scale without
Input
Simulation
INP
Z/FS
Standard
Ranging.
Input Actual
Zero and
Full Scale
from the
Application
TRIM
OUT
Trim Analog
Output
(-AO
Option
Required)
SPA
VIEW
SELECT Site-Programmable Current/Voltage
and RTD/Thermocouple Limit Alarm Trips
SPA
Page 3
8mA
12mA
16mA
20mA
4mA
Input mA
0%
25%
50%
75%
100%
% Display
Full
Scale
Full
Scale
(6mA, 35%)
(8mA, 50%)
(12mA, 70%)
(16mA, 87%)
(20mA, 100%)
Output = Function of the Input
Isolated
Analog
Output
0-20mA
4-20mA
0-5V
1-5V
Figure 3. When equipped with the Analog Output (-AO) option,
the SPA is a combination alarm trip and transmitter.
Combination Alarm and
Isolated Transmitter
When ordered with the -AO (or -AOZ) Analog Output
option, the SPA provides an analog retransmission of
the input signal that can be sent to remote monitoring/
control devices like a DCS, PLC, PC, indicator, or data
recorder (Figure 3). From the front-panel keypad, you
can adjust zero and span, and whether you want the
output to be linear or non-linear with the input.
1000Vrms isolation between the case, input, output(s),
and power supply stops the effects of harmful ground
loop noise.
Continuous Self-Diagnostics
Incorporating advanced self-diagnostics, the SPA
checks its own operation and configuration upon
start up, and then continuously monitors its status
during operation. If it senses that it is not operating
properly, it displays a message on its LCD indicating
what condition has occurred.
Custom 22-Point Linearization Curves
Current and voltage SPA models can be pro-
grammed with up to 22 custom linearization points
from the front panel keypad (Figure 4). The ability to
plot a custom linearization curve is beneficial when
non-linear input signals must be converted to linear
output representations. Typical applications include
monitoring a non-linear transducer, the level of odd-
shaped tanks, and flow meter linearization.
Security Password Protection
A security password system can be used to protect
setup data from unauthorized or inadvertant
changes. Once the password protection feature is
activated, the SPAs operating parameters cannot be
altered unless the correct password has been
entered on the keypad.
Worldwide Power Auto-Sensing
Without adjustment, the SPA accepts every AC and
DC power input (22-300Vdc and 90-260Vac). Just
apply power and youre up and running.
NOTE: Units with CE approval must be ordered with
fixed power supplies (24DC, 117AC or
230AC). See the Ordering Information tables for
details.
Programmable
Input
mA
V
Vac
Aac
RTD
T/C
ohms
mV
Programmable
Alarm Trip(s)
Figure 4. Up to 22 custom linearization points can be selected and
saved in the SPAs memory to compensate for non-linear input
signals.
Custom
Linearization
Points
16.24
MA
SPA
VIEW
SELECT Site-Programmable Current/Voltage
and RTD/Thermocouple Limit Alarm Trips
SPA
Page 4
12.26
MA
SPA
VIEW
SELECT
Ordering Information
Unit Input Output Power Options Housing
SPA
Site-
Programmable
Alarm Trip
HLPRG Programs
to accept:
Current: Any
range between
0-50mA
(0-20mA,
4-20mA,
0-50mA,
10-50mA, etc.)
Voltage: Any
range between
0-10V
(0-5V, 1-5V,
0-10V, etc.)
NOTE: Recommended
minimum span is 4mA for
current inputs and 1V for
voltage inputs. Narrower
spans are possible, but
may result in degradation
of the stated output
accuracy specification.
U Universal,
4-wire (line) power;
accepts any power
input range
between
22-300Vdc or
90-260Vac
For CE approved
units, specify one
of the following:
24DC ±10%
117AC ±10%
230AC ±10%
-AO Analog output
scaleable for any range
between 0-20mA (4mA
span, minimum) into
1200 ohms
or 0-5V (1V
span, minimum) into
10 kohms
-CE EMC conformant
-DPDT Double-pole/
double-throw relay,
rated 5A@250Vac,
50/60Hz, non-inductive
(2PRG output type only)
-FMEDA Unit comes with
Failure Modes, Effects
and Diagnostic Analysis
(FMEDA) data for
evaluating the instrument
for suitability of use in a
safety-related application
-HS Hermetically sealed
relays, rated 0.5A@
117Vac and 2A@28Vdc
DIN Universal
DIN-style housing
mounts on 32mm
(EN50035) G-type
and 35mm
(EN50022) Top
Hat DIN-rails
When ordering, specify: Unit / Input / Output / Power / Options [Housing]
Model number example:
SPA / HLPRG / 4PRG / U / -AO [DIN]
mA and Vdc Input Model
This SPA connects in series on a process loop, and
accepts a direct process signal from a transmitter,
transducer, or other similar instrument. It provides
two or four relay outputs if user-selectable high and/
or low limits are exceeded.
Analog Output Option
With the -AO option the SPA provides an isolated
and scaleable analog output. The analog signal is
proportional to the monitored process variable, and
is ideal for sending to a DCS, PLC, indicator,
recorder, or similar readout device.
Custom Display Parameters
The decimal position, and zero and full scale display
settings, can be selected from the keypad. This
feature is useful for representing a specific
e