Lighting Integrator Data Communications Link
ntent.
Lighting Integrator Data Communications Link
LIGHTING CONTROL P
ANELS
Networking & Softwar
e
www.wattstopper.com
8 0 0 . 8 7 9 . 8 5 8 5
A45
Lighting Integrator Data Communications Link
PROJECT
LOCATION/TYPE
LED status indicators
Alarm contacts
System synchronization clock with automatic
daylight savings and leap year adjustment
Alarm contacts and LEDs to annunciate failed
devices
The Data Communications Link (HLINKCC) pro-
vides the connection between a PC and a Lighting
Integrator (LI) network outfitted with
Communication cards. It enables PCs running
WinControl software to communicate to multiple
panels linked together.
Networking
Operation
The Data Communications Link interfaces PCs with
the panel network. It connects at any point on the
shielded, twisted pair communications wire. The
device enables all the lighting control panels in a LI
system to be programmed and monitored from a
computer using WinControl software. It also pro-
vides notification of failed field devices or relays,
including a failure in the Data Communications
Link itself via an LED and a set of relay contacts.
The Data Communications Link is connected to a
PC using the cable (HCABLE-C).
PC connection to a
Lighting Integrator
panel network
Description
Product
Overview
Features
LED status indicators for power, online, and data
activity
Terminals for connection to global dataline
Clock synchronization
Industry standard RS 232
connection
The Data Communication Link enables PC control
and automation of networked LI panels. Multiple
units can be used on an LI panel network to
provide multiple operator stations or as portals to
other building control systems.
Administrators may select from additional net-
working options. For remote access via telephone
lines, the LI modem option (HMODEM) may be
selected, which connects to the Data
Communications Link. For single user access to
the Data Communications Link via a local area
network using a standard Ethernet connection, the
TCP/IP Connectivity Module (HLANCC) is available.
If multi-user access to the panel network is
desired via TCP/IP or the internet, the WebLink
appliance (WL-BASE) can be added.
LIGHTING CONTROL P
ANELS
Networking & Softwar
e
www.wattstopper.com
8 0 0 . 8 7 9 . 8 5 8 5
A46
System Layout
Networking
Options
Pub. No. 18904
Ordering
Information
Specifications
RS232 serial communications port
300/1200/2400/4800/9600/19200 auto baud
Alarm contacts rated at 28 VDC and 2 mA
maximum
115 VAC plug-in transformer power supply
Shipping weight: 3 lbs. (1.36 kg.)
UL and CUL listed
One year warranty
Networked System Layout
Data Communication Link Applications
Catalog No.
Description
HMODEM
HCABLE-M
HLANCC
WL-BASE
HDWL2
WCHSTD-xxx
HLINKCC
LI Modem
RS 232 Modem Connection Cable
TCP/IP Connectivity Module
WebLink Appliance
Shielded single twisted pair data communications wire
WinControl software
Data Communications Link with 115V power supply
Additional networking components and options:
Data
Communications
Link
HCABLE-C
Cable
Lighting Integrator Panel
(01) First Floor
Lighting Integrator Panel
(02) Second Floor
Communication
Card
Communication
Card
Other panels
Other panels
Shielded single twisted pair
data communications wire (HDLW2)
RS 232
HCABLE-C
Cable
Data
Communications
Link
To panels
Shielded single twisted pair
data communications
wire (HDLW2)
RS 232
HCABLE-C
Cable
Data
Communications
Link
To panels
Shielded single twisted pair
data communications
wire (HDLW2)
Ethernet
WL-BASE
WebLink
option
RS 232
LI panel network using communication card with PC connection via Data Communications Link
Communications components for single-user connections.
Communications components for multi-user LAN, WAN or internet connections