www.drivesys.com/phoenix.doc

ht>







Phoenix Sensorless AC Vector Drive 

US Drives, Inc. 

Niagara Falls, NY


The Phoenix was designed with one goal in mind: 

To create the most reliable and rugged AC Drive Control in the market
today. Phoenix includes all the features required to operate in the
most demanding industrial applications, yet it is simple to use.


Standard Features:  

* TOLERATES HIGH INPUT AC LINE VOLTAGES  

* SHORT CIRCUIT AND GROUND FAULT PROTECTION  

* BUILT IN 3% DC BUS REACTOR  

* BUILT IN RFI NOISE FILTER  

* BUILT IN LINE VOLTAGE SURGE PROTECTION  

* 50º C AMBIENT TEMPERATURE RATING  

* ENGLISH LANGUAGE DISPLAY -2 LINE, 32 CHARACTER  

* SPEED SENSITIVE OVERLOAD PROTECTION, MEETS NEC 430  

* 2 SECOND POWER DIP RIDE THROUGH  

* SETPOINT CONTROL WITH P. I. D.  

* BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR)  

* CUSTOM V/ HZ PATTERNS  

* FIXED OR VARIABLE CARRIER FREQUENCY  

* AUTOLOGGING FAULT HISTORY WITH TIME / DATE STAMP  

* 8 CHANNEL DIGITAL CHART RECORDER WITH TIME / DATE STAMP  

* MUCH, MUCH MORE...  

 

Standard Options:  

* AC LINE DISCONNECT SWITCH WITH FUSES  

* MANUAL BYPASS / AUTOMATIC BYPASS  

* NEMA 12 AND NEMA 4 ENCLOSURES  

* PROCESS SIGNAL ISOLATION  

* 115VAC OPERATOR INTERFACE KIT  

* KW / KWH METERING  

* HAND / OFF / AUTO OR LOCAL / REMOTE


 


Control: 

Control Method:   Sine coded PWM with programmable carrier. Space Vector
control.


Output Voltage:   0 to rated voltage.


Output Frequency Range:  0 to 400 Hz.


Frequency Accuracy:   Analog reference: 0.1% of max frequency.


Digital reference: 0.01% of
max frequency.


Frequency Resolution:  Analog reference: 0.06Hz at 60Hz.


Digital reference: 0.0005Hz
at 60Hz.


Accel/Decel:   Adjustable 0.1 to 3600 sec.


Drive Overload:  High Overload Capacity Drives: 150% of drive rated
output for


two (2) minutes.


Normal Overload Capacity Drives:
120% of drive rated output


for two (2) minutes.


Inverse Time Overload: Programmable for class 10, 20 and 30 protection
with speed sensitive


protection to comply with N.E.C.
Article 430.


Current Limit:   Proactive current limit programmable in % of motor rated
current.


Braking Torque:  Approximately 20%.


V/HZ Curves:   Custom curve programming plus nine (9) preprogrammed standard


patterns.


Maximum Connected Motor: Two (2) times rated drive horsepower.


Control Power Ride-Thru:  Two (2) seconds or greater, depending on
load.


Ambient Temperature: 14 Deg F to 122 Deg F (-10 Deg C to 50 Deg C)


Input R.F.I. Filters:  Standard


Construction:   Steel Construction (Reduces E.M.I.)


Altitude:   Sea Level to 3000 Feet


Surge Protection:  Line transients to 6000V, IEEE C62-41-1991 Category
B


Noise Immunity:  Showering Arc 2000V Peak, EN50082-1,2 


Electrical:


Rated Input Voltage:  200-250Vac, 380-500Vac, 500-600Vac -10% of minimum,
+10% of


maximum.


Rated Input Frequency: 48 to 63HZ.


Number of Phases:  3


Displacement Power Factor: .95 or greater


Efficiency:   .97% or greater at rated current.


 


Phoenix AC Drive Dimensions*





Input Voltage


Motor HP


Drive Only


Drive With 

Disconnect & Fuses


Drive With Bypass


 

High OL 

Capacity**


Normal OL 

Capacity***


NEMA 1


NEMA 12


NEMA 1


NEMA 12


NEMA 1


NEMA 12


200 - 250


7.5 - 30 

30 - 60 

75 - 100


10 - 30 

40 - 75 

100


27x13x12 

33x21x14 

33x21x14


30x20x14 

48x24x18 

48x24x18