NTGRX-KS-__-_ Keyswitch Wallstation

black height=1> Yahoo! is not affiliated with the authors of this page or responsible for its content.
NTGRX-KS-__-_ Keyswitch Wallstation R
Job Name:
Job Number:
Model Numbers:
Page
S P E C I F I C AT I O N S U B M I T TA L
ntgrxwstns-1 1.14.08
Wallstations
Architectural Style
®
NTGRX-KS-__-_
Keyswitch Wallstation
Description
Ideal for public spaces.
Limits access to GRAFIK Eye Control Units.
Authorized personnel must use a key to adjust
lighting.
Functionality can be selected in the field.
Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
Invokes functions in just one Control Unit or a
group of up to eight Control Units.
Finish and Engraving Options
Available with engraving to meet specific
project needs.
Color and Finish Codes
Turns lights off.
Selects
scene 10.
Selects scene 14.
Restores previous scene.
Disables lockout.
Temporarily dims selected zones.
Control Units act independently: movable
wall closed to make two spaces.
Disables zone lockout.
Turns sequencing off.
Selects
scene 1.
Selects scene 9.
Selects scene 13.
Selects scene 16 (all lighting full on).
Locks all other system controls.
Temporarily brightens selected zones.
Control Units act in combination; movable
wall open to make one large space.
Allows only temporary zone adjustment.
Preset scene settings are not affected.
Loops continuously through scenes 5 to
16 using fade times entered at Control
Units.
Entrance Wallstation
Scene Selection
Panic Wallstation
Fine Tuning
Single-Partition
Status Wallstation
Zone Lockout
Sequencing
Field Selected Functionality
DIP Switch Settings
5 6 7
Turning key clockwise:
Turning key counter-clockwise:
1 R
Job Name:
Job Number:
Model Numbers:
Page
S P E C I F I C AT I O N S U B M I T TA L
ntgrxwstns-2 1.14.08
Wallstations
Architectural Style
®
2 3/4 in.
(70mm)
5/16 in.
(8mm)
1 3/8 in.
(35mm)
4 9/16 in.
(116mm)
1 2 3 4 5 6 7
4
3
2
1
Color and Finish Codes
Matte Finishes
Standard Ship in 48 hours
White
WH
Ivory
IV
Beige
BE
Gray
GR
Brown
BR
Black
BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass
BB
Bright Chrome
BC
Bright Nickel
BN
Satin Brass
SB
Satin Chrome
SC
Satin Nickel
SN
Antique Brass
QB
Antique Bronze
QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear
CLA
Black
BLA
Brass
BRA
Engraving
E
No Insert
NI
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finishes.
Dimensions
Front View
Mounting
Power
Low-voltage type Class 2 (PELV).
Operating voltage: 12/24 V Direct Current.
Key Design Features
Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
Faceplate snaps on with no visible means of
attachment.
Can be ganged to share a common faceplate
with NovaT*
®
and Vareo
®
Dimmers. Counts as
a small control for ganging.
System Communications and Capacity
Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Control Units
and other components.
Up to 8 Control Units and up to 16 total
Wallstations and/or Control Interfaces may
be linked for a total of 24 control points.
Terminals
Accept up to two #18 AWG (1.0mm
2
) typical.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Side View
Back View
DIP Switches
1-4 used to set
address
5-7 used to
select function
Terminals for
Class 2
(PELV) wiring
Class 2 (PELV)
wiring
1-Gang U.S.
Wallbox
Faceplate
Specifications
2 DIP Switch Settings
Address
1
2
3
4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Reserved for GRX-PRG, if present on link.
R
Job Name:
Job Number:
Model Numbers:
Page
S P E C I F I C AT I O N S U B M I T TA L
ntgrxwstns-3 1.14.08
Wallstations
Architectural Style
®
DIP Switches
Set DIP switches 1-4 to give the
Wallstation a unique system address
from 1 to 16.
Set additional DIP switches (if any) to
specify function as shown on the first
page of the Wallstations Specification
Submittal.
1 2 3 4 5 6
4
3
2
1
Wallstation Rear View
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
Class 2/PELV
Control Wiring
1: Common
2: 24VFW
Wallstation Installation
Low-Voltage Class 2 (PELV) Wiring
Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
Make connections inside the wallbox or in a switch/junction
box with a maximum wire length of 8 feet (2.5m) from the link
to the Wallstation.
Note:
EGRX Wallstations have a D terminal for Drain.
Connect the Drain/Shield at this terminal.
When used with GRAFIK Eye 3000 Control Units:
Two #18 AWG (1.0mm
2
) conductors for common (terminal 1)
and 12 V Direct Current (terminal 2). Ensure that the terminal 2
connection is wired correctly. Refer to GRX-3000 Specification
Submittal.
One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units:
Two #12 AWG (2.5mm
2
) conductors for common (terminal 1)
and 24 V Direct Current (terminal 2). These wont fit in
terminals. Connect as shown.
One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
Connect Drain/Shield as shown. Do not connect to Ground
(Earth) or Wallstation. Connect the bare drain wires and cut off
the outside shield.
Data Link
(1) Shielded, twisted
pair #18 AWG (1.0mm
2
)
3: MUX
4: MUX
3 ntgrxwstns-4 1.14.08
Wallstations
Architectural Style
®
Assigning Wallstation to
GRAFIK Eye Control Units:
R
Job Name:
Job Number:
Model Numbers:
Page
S P E C I F I C AT I O N S U B M I T TA L
The NTGRX-KS must be configured to
communicate with specific 3000 and 4000
series preset control units. In order for
Wallstation to communicate with a Control
Unit, each Wallstation must be individually
configured to talk by putting the Wallstation
in Setup Mode.
1
1.. Put the Wallstation in S
Se
ettu
up
p M
Mo
od
de
e.
(only one Wallstation in Setup Mode at a time).
This is done by first removing the KS control
from the backbox and locating the
programming button on the back of the
control. While turning the keyswitch
clockwise, p
prre
es
ss
s a
an
nd
d h
ho
olld
d the programming
button for three seconds.
2
2.. Identify the Control Unit(s) that you want to
listen to this Wallstation. (Control Units must
be addressed)! P
Prre
es
ss
s a
an
nd
d h
ho
olld
d the top Scene
button on the Control Unit for about three
seconds, until the LEDs flash in unison. Repeat
for each Control Unit that you want to listen
to the Wallstation.
N
No
otte
e:: (to make a listening Control Unit not
listen to Wallstation: Put the Wallstation in
Setup Mode, then press the listening Control
Units OFF button until the LEDs stop flashing).
3
3.. Exit Setup Mode. Normal operation is
restored by turning the keyswitch clockwise
while pressing the program button for three
seconds.
Control Unit
Press here
for Listen
LEDs flash in unison
4